Smv Modbus Transmitter Connection To A Pc Based Modbus (Rs-485) Host; Figure 18 - Transmitter Configuration Via Modbus (Rs-485) Network Port - Honeywell SMV800 SmartLine User Manual

Multivariable transmitter
Hide thumbs Also See for SMV800 SmartLine:
Table of Contents

Advertisement

network), can cause communication failure. For improved performance, DC termination is
recommended.
Ensure power lines & Modbus communication lines are not swapped during installation/
maintenance.
NOTE: After wiring the Transmitter as outline in the next sections, torque the screws to 1.1 Nm
(10 lb-in)
5.4 SMV Modbus Transmitter Connection to a PC based Modbus
(RS-485) Host
For configuration of the transmitter using Laptop/PC based application following
wiring recommendation are to be followed: Refer
Supply voltage (9.5V to 30V DC) is to be fed between Terminal #1 & Terminal #2.
Sensor inputs can be connected on Terminals #5 to Terminals #8 as per the Sensor type
Isolated USB to RS-485 adaptor is recommended for connecting between PC based Host and
Transmitter
Default configuration of Modbus communication parameters unless otherwise changed is:
Baud rate – 9600 bps, Parity – None and Device address - 247.
Before connecting to the PC-based host the device needs to be disconnected from the
external host (if any).
Isolated RS-485 USB adaptor is recommended when connecting the transmitter to PC.
Figure 18 – Transmitter configuration via Modbus (RS-485) network port
Refer Table 10– Wiring details for SMV Modbus Terminal block
Revision 10
Figure
SMV800 Transmitter User's Manual
18.
Page 25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smv800

Table of Contents