Advertisement

Step
5
When prompted, adjust pressure source to apply pressure equal to LRV (0%), then press OK.
6
When pressure is stable, press OK. When prompted, remove pressure.
7
Choose Correct Input URV.
8
When prompted, adjust pressure source to apply pressure equal to URV (100%), then press
OK.
9
When pressure is stable, press OK. When prompted, remove pressure.
ST 3000 HART
NOTE: Polarity of communicator
connection does not matter.
10/05
Low
Pressure
Head
Dead Weight
Tester
or
Precision
Pressure Source

Figure 39 Typical Range Calibration Hookup

ST 3000 HART Transmitter Release 300 User Manual
10— Calibration - Calibrating Range
Action
250 Ω
Communicator
+
24Vdc
Power
-
Supply
DVM