Figure 27 Typical Communicator And Meter Connections For Constant-Current Source (Output) Mode - Honeywell ST 3000 User Manual

Smart transmitter
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

7— Start-up - Running Analog Output
Step
6
Check that receiving device indication is at its 100% point. If applicable, check that
milliammeter reading is 20 mA or voltmeter reading is 5.0V.
If you want to choose another output value, then press OK and go to Step 7.
If you have completed the loop test, then press OK and go to Step 8.
7
Select Other and press ENTER, then use communicator's keyboard to enter other values.
For example,
If you want an output of:
The communicator notifies you that the transmitter's output is fixed at that value.
When you have completed the loop test, press OK and go to Step 8.
8
Select "End" and press ENTER. The communicator will notify you that it is returning the
transmitter to its original output.
A screen will prompt you to return the loop to automatic control. After doing so, press OK.
Differential
Pressure
Transmitter
Figure 27 Typical Communicator and Meter Connections for Constant-Current Source
68
Transmitter output
LP
HP
ST 3000 HART Transmitter Release 300 User Manual
Action
PV in %
8.0 mA
2.0V
25%
8.8 mA
2.2V
30%
12.0 mA
3.0V
50%
16.0 mA
4.0V
75%
Field
Precision
Terminals
Milliammeter
Note: Polarity of the Communicator
connection does not matter.
(Output) Mode
Communicator keystrokes
press 8 and ENTER.
press 8.8 and ENTER.
press 12 and ENTER.
press 16 and ENTER.
Voltmeter
+
Power
Red +
250 Ω
Supply
-
+
-
-
Black -
Receiver
+
HART hand-held
Commnicator
10/05