Table 8 Flush Mount Transmitter Installation; Figure 10 Typical Flush Mounted Transmitter Installation - Honeywell ST 3000 User Manual

Smart transmitter
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

4— Installation - Mounting ST 3000 Transmitter
Flush mounting
ST 3000 flush mount transmitters (model STG9xx) are mounted directly to the process pipe or tank using a
1 inch weld nipple. Figure 10 shows a typical installation for a transmitter with a flush mount on a pipe.
Follow the steps in Table 8 to install a flush mount transmitter.
Step
1
Cut a hole for a 1" standard pipe in the tank or pipe where the transmitter is to be mounted
ATTENTION
On insulated tanks and pipes, remove enough insulation to accommodate the mounting
sleeve.
2
Weld the 1" mounting sleeve to the wall of the tank or to the hole cut on the pipe
3
Insert the meter body of the transmitter into the mounting sleeve and secure with the locking
bolt
4
Tighten the bolt to a torque of 6,4 Nm+/- 0,30 Nm [4.7 ft.-lbs. +/- 0.2 ft.-lbs.]
5
Once the transmitter is mounted, the electronics housing can be rotated to the desired
position. See Table 6, Step 4 for details.
24

Table 8 Flush Mount Transmitter Installation

Figure 10 Typical Flush Mounted Transmitter Installation

ST 3000 HART Transmitter Release 300 User Manual
Action
1" Pipe Mount -
316 SS Weld Nipple
(standard option)
10/05