Honeywell ST 3000 User Manual page 63

Smart transmitter
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

Configuration Data
Device Information
PV transfer function
(Output Conformity)
PV Damping
(Damping Time Constant)
SV unit
(Secondary Variable)
Poll Address
Interface menus
Information available through the communicator is accessed through menus. The procedures in this manual
give the shortest path from the "Online" (or HOME) menu. There are alternate paths which, depending on
your starting point, may be better suited.
10/05
Select or key in the following device-specific information for:
Manufacturer *
Model *
Measurement Type *
PROM ID *
Tag
Date
Descriptor
* This information is fixed and is read-only.
** Write protect is jumper–selectable on the transmitter PWA.
See Section 8.
Select either:
Select one of these values (in seconds):
0.00
0.32
0.16
0.48
Select one of the temperature units for display of the secondary
variable or meter body temperature.
Deg C
Select the device address for the transmitter.
Select address 0 for a transmitter operating in analog mode, as well
as support for HART communications. (Factory set address)
Select address 1 to 15 for a transmitter operating in multidrop mode.
ST 3000 HART Transmitter Release 300 User Manual
6— Configuration - Configuration Overview
Setting or Selection
Message
Write protect **
Final assembly number
Device ID *
Revision numbers *
Linear
Square Root
1.00
4.00
16.0
2.00
8.00
32.0
deg F
deg R
Universal revision *
Field device revision *
Software revision *
K
49