Auxiliary connector outputs (MCC1 and
Media Gateways only)
Connect a 25-pair cable from the AUX connector on the back of the expansion control carrier to a
connecting block on the trunk/auxiliary field.
Table 21, Auxiliary lead appearances at AUX connector,
•
control carrier outputs cable pinouts
•
pinouts for an external alarm
•
port circuit pack and telephone pin designations
The control carrier AUX connector outputs include:
•
Two inputs for external alarm signals
•
Seven -48 VDC power sources for emergency transfer units
•
Three -48 VDC power sources for remotely powering three attendant consoles or telephone
adjuncts
•
A relay contact that actuates a customer-supplied light, bell, or similar device. The relay can
activate when a major, minor, or warning condition occurs. The device connected to the alarm
leads must not exceed a rating of 30 VAC rms or 60 VDC at 0.75 amperes.
Installing the Avaya G650 Media Gateway
June 2004
Installing and wiring telephones and trunks
on page 164 shows the:
163