Powering up and testing the power supply

The following table describes the meaning of the power supply LEDs when lit.
Table 34: Power supply LEDs
LED color
Green
Yellow
Red
To power up and test the power supply:
1
Connect the AC power cord to the power supply and route the cord to an appropriate AC outlet
using the clips provided on the unit.
NOTE:
A maximum of four power supplies can be powered from one dedicated 100–120 V, 50/60
Hz, 20-amp feeder or 200–240 V, 50/60 Hz, 10-amp feeder. Use only nonswitched outlets.
2
Plug the cord into the outlet. This powers up the power supply.
3
Check AC operation of the 1145B2 Power Supply by monitoring the LEDs:
PASS : Green and yellow LEDs at the front of the unit should be lit together. See
supply LEDs,
yellow LED should go out.
FAIL : If either green or yellow LED is not lit after powering up, check the connections. Test the
AC outlet. If power is available and the AC power cord and connections are good, replace the
power unit.
4
Disconnect the AC plug on the power supply; this activates the DC supply.
5
Check DC (battery back-up) operation of the 1145B2 Power Supply by monitoring the LEDs:
PASS : The red and green LEDs should be lit together. See
page 196.
FAIL : If either green or red LED is not lit after disconnecting AC power, check the connections.
If the connections are good, replace the power unit or batteries.
6
Reconnect AC power to the power supply.

Wiring the 1146B2 Power Distribution Unit

Wire endpoints to the 1146B2 while power from the 1145B2 is on. A red LED lights if its associated
circuit is connected to shorted wiring or to a shorted telephone. To wire the 1146B2 Power Distribution
Unit:
1
Install cross-connect jumpers to wire from the unit (the label shows polarity) to Pins 7 and 8 of the
appropriate information outlet. Route the wires through the clip provided on the unit. If a red LED
is on, see
to a telephone,
2
Mark lead destinations on the label next to each connector. Also mark the Unit Number and
Connectivity information on the label.
196
Meaning
Power Supply is providing power
Battery is charging
Power Supply is on battery reserve
on page 196. After the battery reaches full charge (maximum of 20 hours), the
Resetting LEDs on power distribution unit
on page 197.
Table 34, Power supply LEDs,
on page 197. See
Figure 94, Typical wiring
Installing the Avaya G650 Media Gateway
Table 34, Power
on
June 2004