Avaya G650 Installing page 73

Avaya media gateway
Hide thumbs Also See for G650:
Table of Contents

Advertisement

6
At the AC load center, connect a 6 AWG (#25) (6 mm
This ground wire will later be tie-wrapped to the trunk cables and connected to the Coupled
Bonding Conductor (CBC) ground block at the main distribution frame (MDF).
The coupled bonding conductor (CBC) wires are installed and terminated in
coupled bonding conductor
Figure 27: Typical media gateway ground location
Figure notes
1
Media Gateway
2
Media Gateway Frame Ground
Terminal Block
3
6 AWG (#40) (16 mm
Gateway GROUND Wire
Grounding to an AC load center more than 50 feet (15.2 meters)
from media gateway
To ground to an AC load center more than 50 feet from the media gateway:
1
Mount the single-point ground block to any surface between the media gateways and the AC load
center single-point ground. The single-point ground block must be mounted to a non-metallic
surface.
2
At the bottom rear of the first media gateway, connect a 6 AWG (#40) (16 mm
GROUND wire to the media gateway frame ground terminal block. See
gateway grounding wiring diagram,
3
Route the opposite end of the wire to the single-point ground block and connect.
Installing the Avaya G650 Media Gateway
June 2004
on page 140.
6
4
5
1
2
widmgrn2 KLC 091603
4
5
6
2
) Media
on page 74.
2
) wire to the single-point ground block.
Installing the
3
AC Load Center
Less than 50 Wire feet (15.2 m)
Approved Ground
Figure 28, Typical media
2
) media gateway
73

Advertisement