SiSG121917E
7.18 Thermistor or Related Abnormality (Outdoor Unit)
H9, J3, J6, J8, J9, P4
Error Code
Outdoor Unit LED
A j 1 i 2 i 3 h 4 h 5 h
Display
Method of Error
This fault is identified based on the thermistor input voltage to the microcomputer.
Detection
A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision
The voltage between the both ends of the thermistor is above 4.96 V or below 0.04 V with
Conditions
J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
The system is shut down if all the units are judged as the J8 error.
Supposed
Disconnection of the connector for the thermistor
Causes
Thermistor corresponding to the error code is defective.
Defective heat exchanger thermistor in the case of J3 error
Defective outdoor unit PCB
Troubleshooting
In case of P4
Replace the outdoor unit PCB (main PCB).
P4 : Radiation fin thermistor
Part 6 Service Diagnosis
the power on.
temperature.
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Troubleshooting for Outdoor Unit
162