Power Distribution System Maintenance; Checking Air-Break Switch - Sagem 4450E Hardware Installation Manual

Triple play access concentrator
Table of Contents

Advertisement

CHAPTER 10
10. Power Distribution System
Maintenance

10.1. Checking Air-break Switch

The air-break switch is in the DC power distribution panel, with the overcurrent protection and short circuit
protection functions. In the normal running process, the air-break switch is ON. When a large current passes
through the air-break switch, the air-break switch switches from ON to OFF to cut off the power supply, so the
device is protected.
Usually, you do not need to check the air-break switch. When the air-break switch switches to OFF suddenly, it
indicates that there is something wrong with the power distribution system of the device or the device, and you
should carefully look for the reasons that cause the short circuit protection before switching the air-break switch
to ON.
To find the reasons, you should cut off the power supply of the device firstly, switch the air-break switch to ON,
and use the multimeter to measure the input resistance. If the value of the resistance approximates to zero Ω , it
indicates that there is the short circuit in the interior, and you need to locate each module. When plugging each
module, you can find the short circuit module by judging the change of the resistance before and after the
plugging, and you can switch the air-break switch to ON after the troubleshooting.
3P@C Installation Manual
Reproduction and communication in any form prohibited without the written permission of SAGEM SA

Advertisement

Table of Contents
loading

This manual is also suitable for:

3p@c 4450e

Table of Contents