Configure the Inverter for the Number of Motor Poles- The number of magnetic poles of a
motor is determined by the motor's internal winding arrangement. The specifications label on
the motor usually indicates its number of poles. For proper operation, verify the parameter
setting matches the motor poles. Many industrial motors have four poles, corresponding to the
default setting in the inverter.
Follow the steps in the table below to verify the motor poles setting and change it if necessary
(the table resumes action from the end of the previous table.)
Action
Press the
key.
FUNC.
Press the
key three times.
1
Press the
key.
FUNC.
Press the
key five times.
1
Press the
key.
FUNC.
2
Press the
or
key as needed.
1
Press the
key.
STR
This step concludes the parameter setups for the inverter. You are almost ready to run the motor
for the first time!
TIP: If you became lost during any of these steps, first observe the state of the PRG LED. Then
study the
"Keypad Navigational Map" on page 2–31
keypad controls and display. As long as you do not press the STR key, no parameters will be
changed by keypad entry errors. Note that power cycling the inverter will not cause it to reset to
a particular programming state.
The next section will show you how to monitor a particular parameter from the display. Then
you will be ready to run the motor.
Display
Func./Parameter
A---
"A" Group selected
H---
"H" Group selected
H00 1
First "H" parameter
H004
Motor poles parameter
4
2 = 2 poles
4 = 4 poles (default)
6 = 6 poles
8 = 8 poles
4
Set to match your motor (your
display may be different)
H004
Stores parameter, returns to "H"
Group list
to determine the current state of the