4–64

Analog Input Operation

The following tables show the available analog input settings. Parameters A006, A005, and
input terminal [AT] determine the External Frequency Command input terminals that are avail-
able and how they function. The Trim Frequency input [O2]—[L] is available (when check
marked) for some settings. Other settings make the reverse direction (in addition to forward)
available for bipolar input settings (when check marked). A bipolar input responds to positive
input voltages with a forward motor rotation, and to negative input voltages with reverse motor
rotation.
A006
A005
[AT]
00
00
OFF
OR
ON
03
01
OFF
ON
01
00
OFF
Example
ON
1
01
OFF
ON
02
00
OFF
Example
ON
2
01
OFF
ON
02
OFF
ON
03
OFF
ON
04
OFF
ON
The table below applies when the [AT] input function is not assigned to any intelligent input
terminal. The A005 setting, normally used in conjunction with an [AT] input, is ignored.
A006
A005
[AT]
00
01
(not
assigned
to any
02
input
terminal)
03
CAUTION: Whenever the [AT] input function is not assigned to any input terminal and
reverse rotation is not desired or is unsafe, be sure to set A006 = 01. This setting makes the
[O2] input unipolar only.
External Frequency
Trim Frequency
Command Input
Command Input
[O]
[OI]
[O]
[O2]
[O]
[OI]
[O]
[O2]
[O]
[OI]
[O]
[O2
[O]
Keypad pot.
[OI]
Keypad pot.
[O2]
Keypad pot.
External Frequency
Trim Frequency
Command Input
Command Input
[O2]
Summation of
[O] and [OI]
Summation of
[O] and [OI]
Summation of
[O] and [OI]
Reverse avail.
(bipolar input)
[O2]
[O2]
[O2]
[O2]
[O2]
[O2]
[O2]
[O2]
[O2]
[O2]
[O2]
Reverse avail.
(bipolar input)
[O2]
[O2]

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents