B–12
ASCII Mode Communications
Command – 05
The 05 command reads the inverter's trip history.
The frame format of command 05 follows the
diagrams and specification tables. The transmit
frame has no data field.
Element
Description
STX
Control code (STart of TeXt)
Node
Node (station) address of inverter
Command
Transmission command
BCC
Block check sum code
[CR]
Control code (carriage return)
The receive frame has a 440-byte data field. This
consists of an 8-byte total accumulated number of
trip events, followed by six 72-byte strings for the
six most recent trip events as shown below.
Data field contents
Total count
Trip 1
Element
Description
STX
Control code (STart of TeXt)
Node
Node (station) address of inverter
Data
Transmission data
BCC
Block check sum code
[CR]
Control code (carriage return)
The nine bytes of data for each trip event history is listed below. The data contains the multi-
plier to adjust the decimal point. Divide the data by that factor to derive the actual value.
No.
Monitor Item
1
Trip factor
2
Inverter Status A
3
Inverter Status B
4
Inverter Status C
5
Output frequency
6
Accumulated Run Mode time
7
Output current
8
Output voltage
9
Power ON time
Transmit frame format
STX Node
Size
1 byte
STX (0x02)
2 bytes 01 to 32
2 bytes 05
2 bytes Exclusive OR of Node,
Command, and Data
1 byte
[CR] (0x0D)
Receive frame format
STX Node
Trip 2
Trip 3
Trip 4
Size
1 byte
STX (0x02)
2 bytes 01 to 32
440
(see next table)
bytes
2 bytes Exclusive OR of Node,
Command, and Data
1 byte
[CR] (0x0D)
Units
Multiplier
Hz
10
hours
1
A
10
V
10
hours
1
Command
BCC [CR]
Value
Data
BCC [CR]
Trip 5
Trip 6
Value
Data
Notes
Size
8 bytes
Factor code
8 bytes
Same as 04
command data
8 bytes
8 bytes
8 bytes
Dec. ASCII code
8 bytes
Dec. ASCII code
8 bytes
Dec. ASCII code
8 bytes
Dec. ASCII code
8 bytes
Dec. ASCII code