Note 1: The base frequency is written when you store the parameter. If the new base
frequency value is outside the permissible range, a motor burnout may result.
Therefore, if the warning occurs, change the base frequency to an appropriate value.
Note 2: These parameters are checked even when the digital operator (option code 02) is not
specified for the frequency source setting (A001).
Note 3: Set frequency (speed) values are not permitted to be inside the jump frequency
ranges, if defined. When a frequency reference value from a real-time source (such as
keypad potentiometer or analog input) are inside a jump frequency range, the actual
speed is automatically forced to equal the lowest point of the jump range.