Determining wire and fuse sizes, continued...
Motor
Output
400V
Inverter Models
HP
kW
0.5
0.75
SJ700–007HFUF2/E
1
1.5
SJ700–015HFUF2/E
2
2.2
SJ700–022HFUF2/E
3
4.0
SJ700–040HFUF2/E
7.5
5.5
SJ700–055HFUF2/E
10
7.5
SJ700–075HFUF2/E
15
11
SJ700–110HFUF2/E
20
15
SJ700–150HFUF2/E
25
18.5
SJ700–185HFU2/E
30
22
SJ700–220HFU2/E
40
30
SJ700–300HFU2/E
50
37
SJ700–370HFU2/E
60
45
SJ700–450HFU2/E
75
55
SJ700–550HFU2/E
100
75
SJ700–750HFU2/E
125
90
SJ700–900HFU2/E
150
110
SJ700–1100HFU2/E
150
132
SJ700–1320HFE2,
SJ700–1500HFU2
250
185
SJ700–1850HFU2/E
400
315
SJ700–3150HFU2/E
500
400
SJ700–4000HFU2/E
Note 1: Field wiring must be made by a UL-listed and CSA certified ring lug terminal
connector sized for the wire gauge involved. The connector must be fixed by using
the crimping tool specified by the connector manufacturer.
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use a larger wire gauge if power line length exceeds 66 ft (20m).
Note 4: Prepackaged (included) square washer is to be used when the bare wire is directly
connected to terminal without using crimp contact (such as ring lug connector).
Note 5: When replacing J300-055HF or SJ300-055HFF2 inverter with SJ700-055HFF2,
you may use power wiring size 2mm
Note 6: Wire must be rated for operation up to 75°C.
Power Lines *3
Fuse
(UL-
AWG/
2
rated,
mm
kcmil
class J,
600V)
20
1.25
10A
18
2
10A
16
2
10A
14
2
15A
12
3.5 *5
15A
10
3.5
20A
8
5.5
30A
6
8
40A
6
14
50A
4
14
60A
3
22
70A
1
38
90A
1 || 1 *6
38
125A
2/0
60
125A
1 || 1 *6
100 or
175A
38 || 38
1 || 1 *6
100 or
200A
38 || 38
1/0 || 1/0
150 or
250A
60 || 60
3/0 || 3|0
80 || 80
300A
300 ||
152 ||
400A
300
152
500 ||
253 ||
700A
500
253
800 ||
405 ||
1000A
800
405
SJ700
Wiring *1
Chassis Ground
Breaker
AWG/
AWG/
( GFI
kcmil,
kcmil,
mm
type) *2
rec.
UL
10A
20
20
1.25
10A
18
18
10A
18
18
15A
18
18
15A
10
12
20A
10
12
30A
8
10
40A
8
10
50A
4
10
60A
4
10
70A
3
10
90A
3
8
125A
1
8
125A
1
6
175A
3
8
200A
3
8
250A
1
6
300A
3/0
3/0
400A
250
250
127
700A
400
400
203
1000A
600
600
304
2
.
2–19
Inverter
2
Brake Res.
2
2
AWG
mm
20
1.25
2
18
2
2
18
2
2
18
2
3.3
10
3.5
*5
*5
3.5
10
3.5
5.5
8
5.5
8
10
8
14
10
14
14
10
14
22
38
38
60
38
38
60
80

Advertisement