Hitachi SJ7002 Series Instruction Manual page 141

Sj7002 series
Hide thumbs Also See for SJ7002 Series:
Table of Contents

Advertisement

Option
Terminal
Function Name
Code
Symbol
26
OL2
Overload notice advance
signal (2)
27
Odc
Analog [O] disconnect
detect
28
OIDc
Analog [OI] disconnect
detect
29
O2Dc
Analog [O2] disconnect
detect
31
FBV
PID feedback second
stage output
32
NDc
Network detection signal
33
LOG1
Logic output 1
34
LOG2
Logic output 2
35
LOG3
Logic output 3
36
LOG4
Logic output 4
37
LOG5
Logic output 5
38
LOG6
Logic output 6
39
WAC
Capacitor life warning
40
WAF
Low cooling fan speed
41
FR
Starting contact signal
42
OHF
Heat sink overheat
warning
43
LOC
Low output current signal Output current to motor is below threshold set by C039
44
MO1
General output 1
45
MO2
General output 2
46
MO3
General output 3
47
MO4
General output 4
48
MO5
General output 5
49
MO6
General output 6
50
IRDY
Inverter ready signal
51
FWR
Forward rotation signal
52
RVR
Reverse rotation signal
53
MJA
Major failure signal
54
WCO
[O] terminal window
comparator
55
WCOI
[OI] terminal window
comparator
Output Function Summary Table
Output current is more than the set Threshold 2 for the
overload signal (set with C111)
Input signal level at terminal [O] is below threshold (set with
B070)
Input signal level at terminal [OI] is below threshold (set with
B071)
Input signal level at terminal [O2] is below threshold (set with
B072)
Stage #1 inverter is indicating to Stage # inverter that the
Process Variable (PV) is in saturation. The system needs
Stage #2 output contribution to stabilize system control.
The communications watchdog timer (period specified by
C077) has timed out
Boolean operation specified by C144 has a logical "1" result
Boolean operation specified by C147 has a logical "1" result
Boolean operation specified by C150 has a logical "1" result
Boolean operation specified by C153 has a logical "1" result
Boolean operation specified by C156 has a logical "1" result
Boolean operation specified by C159 has a logical "1" result
Capacitor bank on the main board needs replacement
Cooling fan is enabled but it is rotating below normal speed
ON while the inverter receives a FW or REV command
Inverter heat sink temperature is above the threshold set by
C064
Easy sequence function, general output 1
Easy sequence function, general output 2
Easy sequence function, general output 3
Easy sequence function, general output 4
Easy sequence function, general output 5
Easy sequence function, general output 6
Inverter is ready to accept commands (FW, REV, JOG, etc.)
Inverter output is driving motor in forward direction
Inverter output is driving motor in reverse direction
Inverter trip caused by internal hardware error
[O] input is within comparator window set by B060 and B061
[OI] input is within comparator window set by B063 and
B064
SJ700
Inverter
2
Description
3–57

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents