Maintenance And Inspection - Hitachi SJ7002 Series Instruction Manual

Sj7002 series
Hide thumbs Also See for SJ7002 Series:
Table of Contents

Advertisement

Maintenance and Inspection

Monthly and
Yearly Inspection
Chart
Item Inspected
General Ambient
environment
Major devices
Power supply
voltage
Main
Ground
circuits
Insulation
Mounting
Components
Housing
Terminal block
Smoothing
capacitor
Relay(s)
Resistors
Cooling
Cooling fan
system
Heat sink
Control
General
circuit
Capacitor
Display LEDs
Inspection
Cycle
Check for...
Month
Year
Extreme
temperatures
& humidity
Abnormal
vibration,
noise
Voltage
tolerance
Adequate
resistance
No loose
screws
Overheating
Dirt, dust
Secure
connections
Leaking,
swelling
Chattering
Cracks or
discoloring
Noise
Dust
No odor,
discoloring,
corrosion
No leaks or
deformation
Legibility
SJ700
Inspection Method
Thermometer,
Ambient temperature
hygrometer
between -10 to 50°C,
non-condensing
Visual and aural
Stable environment for
electronic controls
Digital volt meter,
200V class:
measure between
200 to 240V 50/60 Hz
inverter terminals
400V class:
[L1], [L2], [L3]
380 to 460V 50/60 Hz
Megger test
500VDC, reading of 5M
ohms or greater, see next
section for test details
Torque wrench
M3: 0.5 – 0.6 Nm
M4: 0.98 – 1.3 Nm
M5: 1.5 – 2.0 Nm
Thermal trip events
No trip events
Visual
Vacuum dust and dirt
Visual
No abnormalities
Visual
No abnormalities
Aural
Single click when
switching ON or OFF
Visual
Use Ohm meter to check
braking resistors
Power down,
Rotation must be smooth
manually rotate
Visual
Vacuum to clean
Visual
No abnormalities
Visual
Undistorted appearance
Visual
All LED segments work
6–17
Inverter
2
Criteria

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents