Hitachi SJ200 Series Instruction Manual

Hitachi SJ200 Series Instruction Manual

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for SJ200 Series:
Table of Contents

Advertisement

SJ200 Series Inverter
Instruction Manual
• Single-phase Input 200V Class
• Three-phase Input 200V Class
• Three-phase Input 400V Class
Manual Number: NB650XA
March 2004
Hitachi Industrial Equipment Systems Co., Ltd.
After reading this manual,
keep it handy for future reference.

Advertisement

Table of Contents
loading

Summary of Contents for Hitachi SJ200 Series

  • Page 1 SJ200 Series Inverter Instruction Manual • Single-phase Input 200V Class • Three-phase Input 200V Class • Three-phase Input 400V Class Manual Number: NB650XA After reading this manual, keep it handy for future reference. March 2004 Hitachi Industrial Equipment Systems Co., Ltd.
  • Page 2: Safety Messages

    SJ200 Inverter Safety Messages For the best results with the SJ200 Series inverter, carefully read this manual and all of the warning labels attached to the inverter before installing and operating it, and follow the instructions exactly. Keep this manual handy for quick reference.
  • Page 3 Equipment Systems Co., Ltd. CAUTION: Be sure to connect a motor thermal disconnect switch or overload device to the SJ200 series controller to assure that the inverter will shut down in the event of an overload or an overheated motor.
  • Page 4 SJ200 Inverter WARNING: Rotating shafts and above-ground electrical potentials can be hazardous. Therefore, it is strongly recommended that all electrical work conform to the National Electrical Codes and local regulations. Installation, alignment and maintenance should be performed only by qualified personnel. Factory-recommended test procedures included in the instruction manual should be followed.
  • Page 5 Index to Warnings and Cautions in This Manual Cautions and Warnings for Orientation and Mounting Procedures CAUTION: Hazard of electrical shock. Disconnect incoming power ..2–4 before working on this control. Wait five (5) minutes before removing the front cover. CAUTION: Be sure to install the unit on flame-resistant material such as ..
  • Page 6 SJ200 Inverter WARNING: “Suitable for use on a circuit capable of delivering not more ..2–17 than 5,000 rms symmetrical amperes, 480 V maximum.” For models with suffix H. HIGH VOLTAGE: Be sure to ground the unit. Otherwise, there is a ..
  • Page 7 CAUTION: Remarks for using ground fault interrupter breakers in the ..2–21 main power supply: Adjustable frequency inverters with CE-filters (RFI- filter) and shielded (screened) motor cables have a higher leakage current toward Earth GND. Especially at the moment of switching ON this can cause an inadvertent trip of ground fault interrupters.
  • Page 8 SJ200 Inverter Warnings for Configuring Drive Parameters WARNING: When parameter B012, level of electronic thermal setting, is ..3–32 set to motor FLA rating (Full Load Ampere nameplate rating), the inverter provides solid state motor overload protection at 115% of motor FLA or equivalent.
  • Page 9 viii WARNING: Be sure not to touch the inside of the energized inverter or to ..4–3 put any conductive object into it. Otherwise, there is a danger of electric shock and/or fire. WARNING: If power is turned ON when the Run command is already ..
  • Page 10: General Warnings And Cautions

    SJ200 Inverter Warnings and Cautions for Troubleshooting and Maintenance WARNING: Wait at least five (5) minutes after turning OFF the input ..6–2 power supply before performing maintenance or an inspection. Other- wise, there is the danger of electric shock. WARNING: Make sure that only qualified personnel will perform ..
  • Page 11 CAUTION: Do not stop operation by switching OFF electromagnetic contactors on the primary or secondary sides of the inverter. Ground fault interrupter Power Input L1, L2, L3 U, V, W Motor Inverter When there has been a sudden power failure while an operation instruction is active, then the unit may restart operation automatically after the power failure has ended.
  • Page 12 SJ200 Inverter CAUTION: EFFECTS OF POWER DISTRIBUTION SYSTEM ON INVERTER In the cases below involving a general-purpose inverter, a large peak current can flow on the power supply side, sometimes destroying the converter module: 1. The unbalance factor of the power supply is 3% or higher. 2.
  • Page 13 CAUTION: When the EEPROM error E08 occurs, be sure to confirm the setting values again. CAUTION: When using normally closed active state settings (C011 to C016) for exter- nally commanded Forward or Reverse terminals [FW] or [RV], the inverter may start automatically when the external system is powered OFF or disconnected from the inverter! So, do not use normally closed active state settings for Forward or Reverse terminals [FW] or [RV] unless your system design protects against unintended motor...
  • Page 14 xiii SJ200 Inverter Terminal Tightening Torque and Wire Size The wire size range and tightening torque for field wiring terminals are presented in the tables below. Motor Output Power Terminal Torque Input Inverter Model Wiring Size Voltage ft-lbs (N-m) Range (AWG) SJ200-002NFEF/NFU SJ200-004NFEF/NFU 0.55...
  • Page 15: Motor Overload Protection

    7 1/2 SJ200-055HFEF/HFU SJ200-075HFEF/HFU Motor Overload Protection Hitachi SJ200 inverters provide solid state motor overload protection, which depends on the proper setting of the following parameters: • B012 “electronic overload protection” • B212 “electronic overload protection, 2nd motor” Set the rated current [Amperes] of the motor(s) with the above parameters. The setting range is 0.2 * rated current to 1.2 * rated current.
  • Page 16: Inverter Mounting

    SJ200 Inverter Table of Contents Safety Messages Hazardous High Voltage General Precautions - Read These First! Index to Warnings and Cautions in This Manual General Warnings and Cautions UL® Cautions, Warnings, and Instructions Table of Contents Revisions xvii Contact Information xviii Chapter 1: Getting Started Introduction...
  • Page 17: Table Of Contents

    Connecting the Inverter to ModBus B–3 Network Protocol Reference B–6 ModBus Data Listing B–19 Appendix C: Drive Parameter Settings Tables Introduction C–2 Parameter Settings for Keypad Entry C–2 Appendix D: CE–EMC Installation Guidelines CE–EMC Installation Guidelines D–2 Hitachi EMC Recommendations D–6 Index...
  • Page 18 xvii SJ200 Inverter Revisions Revision History Table Operation Revision Comments Date of Issue Manual No. Initial release of manual NB650X Feb. 2004 NB650X Revision A March 2004 NB650XA Page 4-35 – Added page on internal relay operation Pages 4-37 to 4-50 – Added relay drawing for outputs Index 1-6 –...
  • Page 19: Contact Information

    NOTE: To receive technical support for the Hitachi inverter you purchased, contact the Hitachi inverter dealer from whom you purchased the unit, or the sales office or factory contact listed above. Please be prepared to provide the following inverter nameplate information: 1.
  • Page 20: Table Of Contents

    Getting Started In This Chapter... page — Introduction ............. — SJ200 Inverter Specifications......— Introduction to Variable-Frequency Drives ..— Frequently Asked Questions ......
  • Page 21: Main Features

    • Fan has ON/OFF selection to provide longer life for cooling fan (on models with fan) A full line of accessories from Hitachi is available to complete your motor application: • Digital remote operator keypad • Panel-mount keypad bezel kit and DIN rail mounting adapter (35mm rail size) •...
  • Page 22 (below, left). A cable (part no. ICS–1 or ICS–3, 1m or 3m) connects the modular connectors of the keypad and inverter. Hitachi provides a panel mount keypad kit (below, right). It includes the mounting flange, gasket, keypad, and other hardware. You can OPE–SRmini...
  • Page 23 Introduction Inverter Specifications Label The Hitachi SJ200 inverters have product labels located on the right side of the housing, as pictured below. Be sure to verify that the specifications on the labels match your power source, motor, and application safety requirements.
  • Page 24 1–5 SJ200 Inverter SJ200 Inverter Specifications Model-specific tables for 200V and 400V class inverters The following tables are specific to SJ200 inverters for the 200V and 400V class model groups. Note that “General Specifications” on page 1–10 apply to both voltage class groups.
  • Page 25 (for Low Voltage Directive). Note 7: At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor (when selecting intelligent sensorless vector control—iSLV). Note 8: The braking torque via capacitive feedback is the average deceleration torque at the shortest deceleration (stopping from 50/60 Hz as indicated).
  • Page 26 1–7 SJ200 Inverter SJ200 Inverter Specifications, continued... Item 200V Class Specifications, continued SJ200 inverters, EU version 015NFEF 022NFEF — — — 200V models USA version 015NFU 022NFU 037LFU 055LFU 075LFU Applicable motor size *2 Rated capacity 230V 12.7 (kVA) 240V 13.3 Rated input voltage 1-phase: 200 to 240V ±10%, 50/60 Hz ±5%,...
  • Page 27 1–8 SJ200 Inverter Specifications Item 400V Class Specifications SJ200 inverters, EU version 004HFEF 007HFEF 015HFEF 022HFEF 400V models USA version 004HFU 007HFU 015HFU 022HFU Applicable motor size *2 0.75 Rated capacity (460V) kVA Rated input voltage *6 3-phase: 380 to 480V ±10%, 50/60 Hz ±5% Integrated EMC EU version Three phase filter, Category C3 *5...
  • Page 28 1–9 SJ200 Inverter Item 400V Class Specifications, continued SJ200 inverters, EU version 030HFEF 040HFEF 055HFEF 075HFEF 400V models USA version — 040HFU 055HFU 075HFU Applicable motor size *2 Rated capacity (460V) kVA 10.3 12.7 Rated input voltage *6 3-phase: 380 to 480V ±10%, 50/60 Hz ±5% Integrated EMC EU version Three phase filter, Category C3...
  • Page 29: General Specifications

    1–10 SJ200 Inverter Specifications General Specifications The following table applies to all SJ200 inverters. Item General Specifications Protective housing *1 IP20 Control method Sinusoidal Pulse Width Modulation (PWM) control Carrier frequency 2kHz to 14kHz (default setting: 5kHz) Output frequency range *4 0.5 to 400 Hz Frequency accuracy Digital command: 0.01% of the maximum frequency...
  • Page 30 1–11 SJ200 Inverter Item General Specifications Other functions AVR function, curved accel/decel profile, upper and lower limiters, 16-stage speed profile, fine adjustment of start frequency, carrier frequency change (2 to 14 kHz), frequency jump, gain and bias setting, process jogging, electronic thermal level adjustment, retry function, trip history monitor, 2nd setting selection, fan ON/OFF selection Protective function...
  • Page 31: Introduction To Variable-Frequency Drives

    Introduction to Variable-Frequency Drives The Purpose of Motor Speed Control for Industry Hitachi inverters provide speed control for 3-phase AC induction motors. You connect AC power to the inverter, and connect the inverter to the motor. Many applications benefit from a motor with variable speed, in several ways: •...
  • Page 32 Inverter Input and Three-Phase Power The Hitachi SJ200 Series of inverters includes two sub-groups: the 200V class and the 400V class inverters. The drives described in this manual may be used in either the United States or Europe, although the exact voltage level for commercial power may be slightly different from country to country.
  • Page 33 The Hitachi inverter is a rugged and reliable device. The intention is for the inverter to assume the role of controlling power to the motor during all normal operations. There- fore, this manual instructs you not to switch off power to the inverter while the motor is running (unless it is an emergency stop).
  • Page 34 For loads that continuously overhaul the motor for extended periods of time, the SJ200 may not be suitable (contact your Hitachi distributor). The inverter parameters include acceleration and deceleration, which you can set to match the needs of the application. For a particular inverter, motor, and load, there will...
  • Page 35 1–16 Introduction to Variable-Frequency Drives Velocity Profiles The SJ200 inverter is capable of sophisticated speed control. A graphical representation of Set speed Speed that capability will help you understand and configure the associated parameters. This Accel Decel manual makes use of the velocity profile graph used in industry (shown at right).
  • Page 36: Frequently Asked Questions

    What is the “Intelligent Sensorless Vector Control” feature? Intelligent Sensorless Vector Control (iSLV) is Hitachi’s newest variable speed control technology. The original sensorless vector control (SLV) did not require motor shaft position sensors (thus “sensorless)”, but still required setting several motor parameters (either manually or through an auto-tuning procedure).
  • Page 37 How many poles should the motor have? Hitachi inverters can be configured to operate motors with 2, 4, 6, or 8 poles. The greater the number of poles, the slower the top motor speed will be, but it will have higher torque at the base speed.
  • Page 38 Several options related to electrical noise suppression are available for the Hitachi inverters. How can I know if my application will require any of these options? The purpose of these noise filters is to reduce the inverter electrical noise so the operation of nearby electrical devices is not affected.
  • Page 39: Table Of Contents

    Inverter Mounting and Installation In This Chapter..page — Orientation to Inverter Features ...... — Basic System Description ....... — Step-by-Step Basic Installation......— Powerup Test ..........— Using the Front Panel Keypad ......
  • Page 40: Orientation To Inverter Features

    3. Inspect the specifications label on the side of the inverter. Make sure it matches the product part number you ordered. Main Physical Features The SJ200 Series inverters vary in size accord- ing to the current output rating and motor size for each model number. All feature the same basic keypad and connector interface for consis- tent ease of use.
  • Page 41 2–3 SJ200 Inverter Inverter Keypad Removal and Installation Keypad Removal - The SJ200 has a removable keypad. To remove the keypad, locate the retention latch as shown to the right. Press downward on the latch, while gently pulling toward you. The keypad will tilt forward, as two retaining tabs at the bottom edge of the keypad also hold it in place.
  • Page 42 2–4 Orientation to Inverter Features Front Housing Cover HIGH VOLTAGE: Hazard of electrical shock. Disconnect incoming power before working on this control. Wait five (5) minutes before removing the front cover. Housing Cover Removal - The front housing cover is held in place by two pairs of tabs. Since these are hidden from view, it is good to become familiar with their locations before attempting to remove the cover.
  • Page 43 2–5 SJ200 Inverter Logic Connector Introduction After removing the front housing cover, take a moment to become familiar with the connectors, as shown below. Relay output Logic inputs contacts Analog input/ output and logic outputs Logic Connector Removal/Replacement - The two 8-position main logic connectors are removable from the circuit board to make testing or service more convenient.
  • Page 44 2–6 Orientation to Inverter Features DIP Switch Introduction The inverter has three (3) internal DIP switches, located to the right of the logic connec- tors as shown below. This section provides an introduction, and refers you to other chapters that discuss each DIP switch in depth. The SR/SK (Source/Sink) DIP switch configures the inverter’s intelligent inputs for sinking or sourcing type circuit.
  • Page 45 2–7 SJ200 Inverter Power Wiring Access - First, ensure no power source of any kind is connected to the inverter. If power has been connected, wait five minutes after powerdown and verify the Power LED is OFF to proceed. After removing the front housing cover, the housing partition that covers the power wiring exit will be able to slide upward as shown to the right.
  • Page 46: Basic System Description

    2–8 Basic System Description Basic System Description A motor control system will obviously include a motor and inverter, as well as a breaker or fuses for safety. If you are connecting a motor to the inverter on a test bench just to get started, that’s all you may need for now.
  • Page 47: Step-By-Step Basic Installation

    2–9 SJ200 Inverter WARNING: In the cases below involving a general-purpose inverter, a large peak current can flow on the power supply side, sometimes destroying the converter module: 1.The unbalance factor of the power supply is 3% or higher. 2.The power supply capacity is at least 10 times greater than the inverter capacity (or the power supply capacity is 500 kVA or more).
  • Page 48 2–10 Step-by-Step Basic Installation Choosing a Mounting Location Step 1: Study the following caution messages associated with mounting the inverter. This is the time when mistakes are most likely to occur that will result in expensive rework, equipment damage, or personal injury. CAUTION: Be sure to install the unit on flame-resistant material such as a steel plate.
  • Page 49 2–11 SJ200 Inverter Ensure Adequate Ventilation Step 2: To summarize the caution messages—you will need to find a solid, non-flamma- ble, vertical surface that is in a relatively clean and dry environment. In order to ensure enough room for air circulation around the inverter to aid in cooling, maintain the speci- fied clearance around the inverter specified in the diagram.
  • Page 50 2–12 Step-by-Step Basic Installation Check Inverter Dimensions Step 4: Locate the applicable drawing on the following pages for your inverter. Dimensions are given in millimeters (inches) format. SJ200–002NFEF, –002NFU NOTE: Some inverter housings require two mounting screws, while others require four. Be sure to use lock washers or other means to ensure screws do not loosen due to vibration.
  • Page 51 2–13 SJ200 Inverter Dimensional drawings, continued... SJ200–004NFEF, –004NFU, –005NFEF...
  • Page 52 2–14 Step-by-Step Basic Installation Dimensional drawings, continued... SJ200–007NFEF, –007NFU, –011NFEF, –004HFEF, –004HFU...
  • Page 53 2–15 SJ200 Inverter Dimensional drawings, continued... SJ200–007HFEF, –007HFU...
  • Page 54 2–16 Step-by-Step Basic Installation Dimensional drawings, continued... SJ200–015NFEF, –015NFU, –022NFEF, –022NFU, –037LFU, –015HFEF, –015HFU, –022HFEF, –022HFU, –-030HFEF, –040HFEF, –040HFU...
  • Page 55 2–17 SJ200 Inverter Prepare for Wiring Step 5: It is very important to perform the wiring steps carefully and correctly. Before proceeding, please study the caution and warning messages below. WARNING: “Use 60/75°C Cu wire only” or equivalent. WARNING: “Open Type Equipment.” WARNING: “Suitable for use on a circuit capable of delivering not more than 5,000 rms symmetrical amperes, 240 V maximum.”...
  • Page 56 2–18 Step-by-Step Basic Installation Determining Wire and Fuse Sizes The maximum motor currents in your application determines the recommended wire size. The following table gives the wire size in AWG. The “Power Lines” column applies to the inverter input power, output wires to the motor, the earth ground connection, and any other component shown in the “Basic System Description”...
  • Page 57 2–19 SJ200 Inverter Terminal Dimensions and Torque Specs The terminal screw dimensions for all SJ200 inverters are listed in table below. This information is useful in sizing spade lug or ring lug connectors for wire terminations. CAUTION: Fasten the screws with the specified fastening torque in the table below. Check for any loosening of screws.
  • Page 58 2–20 Step-by-Step Basic Installation Please use the terminal arrangement below corresponding to your inverter model. Inverter models SJ200–002NFEF/NFU to –005NFEF/NFU Jumper – N/L3 U/T1 V/T2 W/T3 Chassis Ground Inverter models SJ200–007NFEF to –022NFEF, –007NFU to –037LFU, –004HFEF/HFU to –040HFEF/HFU Jumper –...
  • Page 59 2–21 SJ200 Inverter CAUTION: Be sure not to connect an AC power supply to the output terminals. Other- wise, there is the possibility of damage to the inverter and the danger of injury and/or fire. SJ200 Inverter Power Input Output to Motor CAUTION: Remarks for using ground fault interrupter breakers in the main power supply: Adjustable frequency inverters with CE-filters (RFI-filter) and shielded (screened) motor...
  • Page 60 2–22 Step-by-Step Basic Installation Wire the Inverter Output to Motor Step 7: The process of motor selection is beyond the scope of this manual. However, it must be an AC induction motor with three phases. It should also come with a chassis ground lug.
  • Page 61: Powerup Test

    3. Get an introduction to the use of the built-in operator keypad. The powerup test gives you an important starting point to ensure a safe and successful application of the Hitachi inverter. We highly recommend performing this test before proceeding to the other chapters in this manual.
  • Page 62 2–24 Powerup Test Pre-test and Operational Precautions The following instructions apply to the powerup test, or to any time the inverter is powered and operating. Please study the following instructions and messages before proceeding with the powerup test. 1. The power supply must have fusing suitable for the load. Check the fuse size chart presented in Step 5, if necessary.
  • Page 63: Using The Front Panel Keypad

    The display is used in programming the inverter’s parameters, as well as monitor- ing specific parameter values during operation. Power LED Display Units (Hertz / Amperes) LEDs Alarm LED Run/Stop LED POWER HITACHI Parameter Display 5 0.0 ALARM HITACHI Program/Monitor LED Run Key Enable LED...
  • Page 64 2–26 Using the Front Panel Keypad Keys, Modes, and Parameters The purpose of the keypad is to provide a way to change POWER HITACHI modes and parameters. The term function applies to both 0 0 1 ALARM HITACHI monitoring modes and parameters. These are all accessible...
  • Page 65 SJ200 Inverter Keypad Navigational Map The SJ200 Series inverter drives have many programmable functions and parameters. Chapter 3 will cover these in detail, but you need to access just a few items to perform the powerup test. The menu structure makes use of function codes and parameter codes to allow programming and monitoring with only a 4-digit display and a few keys and LEDs.
  • Page 66 Select the Potentiometer for Speed Command - Potentiometer Enable LED The inverter output frequency can be set from several sources, including an analog input, memory setting, POWER HITACHI 5 0.0 ALARM or the network, for example. The powerup test uses HITACHI the keypad potentiometer as the speed control source for your convenience.
  • Page 67 Select the Keypad for the RUN Command - The RUN Run Key Enable LED command causes the inverter to accelerate the motor to the selected speed. The Run command can arrive from POWER HITACHI 5 0.0 ALARM various sources, including the control terminals, the Run HITACHI key on the keypad, or the network.
  • Page 68 2–30 Using the Front Panel Keypad Set the Motor Base Frequency - The motor is designed to operate at a specific AC frequency. Most commercial motors are designed for 50/60 Hz operation. First, check the motor specifications. Then follow the steps below to verify the setting or correct it for your motor.
  • Page 69 2–31 SJ200 Inverter Action Display Func./Parameter A 0 0 3 (Starting point) Base frequency setting A 0 8 2 AVR voltage select key and hold until--> Press the 2 3 0 Default values for AVR voltage: key. Press the FUNC. 200V class = 230VAC 400V class = 400VAC (–xxxFEF) 4 0 0...
  • Page 70 2–32 Using the Front Panel Keypad Set the Number of Motor Poles - The motor’s internal winding arrangement deter- mines its number of magnetic poles. The specifications label on the motor usually indicates the number of poles. For proper operation, verify the parameter setting matches the motor poles.
  • Page 71: Running The Motor

    SJ200 Inverter Monitoring Parameters with the Display After using the keypad for parameter editing, it’s a good idea to switch the inverter from POWER HITACHI 5 0.0 ALARM Program Mode to Monitor Mode. The PRG HITACHI LED will be OFF, and the Hertz or Ampere LED indicates the display units.
  • Page 72 NOTE: Some factory automation devices such as PLCs have alternate Run/Program modes; the device is in either one mode or the other. In the Hitachi inverter, however, Run Mode alternates with Stop Mode, and Program Mode alternates with Monitor Mode.
  • Page 73: Configuring Drive Parameters

    Configuring Drive Parameters In This Chapter..page — Choosing a Programming Device ....— Using Keypad Devices ........— “D” Group: Monitoring Functions..... — “F” Group: Main Profile Parameters ....— “A” Group: Standard Functions ....... — “B” Group: Fine Tuning Functions ....
  • Page 74: Choosing A Programming Device

    By making specific, individual changes and observing their effects, you can achieve a finely tuned system. And, the SJ200 Series inverters feature intelligent sensorless vector control (iSLV) to eliminate the need for manually setting motor parameters, or even to do an auto-tuning procedure.
  • Page 75: Using Keypad Devices

    SJ200 Inverter Using Keypad Devices The SJ200 Series inverter front keypad contains all the elements for both monitoring and programming parameters. The keypad layout is pictured below. All other programming devices for the inverter have a similar key arrangement and function.
  • Page 76 3–4 Using Keypad Devices Keypad Navigational Map You can use the inverter’s front panel keypad to navigate to any parameter or function. The diagram below shows the basic navigational map to access these items. Monitor Mode Program Mode PRG LED=OFF PRG LED=ON Display Data Select Parameter...
  • Page 77: Operational Modes

    3–5 SJ200 Inverter Operational Modes The RUN and PRG LEDs tell just part of the story; STOP Run Mode and Program Modes are independent RESET Stop modes, not opposite modes. In the state diagram to the right, Run alternates with Stop, and Program Mode alternates with Monitor Mode.
  • Page 78 3–6 “D” Group: Monitoring Functions “D” Group: Monitoring Functions You can access important system parameter values with the “D” Group monitoring functions, whether the inverter is in Run Mode or Stop Mode. After selecting the function code number for the parameter you want to monitor, press the Function key once to show the value on the display.
  • Page 79 3–7 SJ200 Inverter “D” Function Mode Units Func. Name / Description Edit Code SRW Display D007 Scaled output frequency Displays the output frequency — Hz times monitor scaled by the constant in B086. constant Decimal point indicates range: F-Cnv 00000.00 XX.XX 0.00 to 99.99 XXX.X 100.0 to 999.9 XXXX.
  • Page 80: F" Group: Main Profile Parameters

    3–8 “F” Group: Main Profile Parameters “F” Group: Main Profile Parameters The basic frequency (speed) profile is Output defined by parameters contained in the F002 F003 frequency “F” Group as shown to the right. The set running frequency is in Hz, but accelera- F001 tion and deceleration are specified in the time duration of the ramp (from zero to...
  • Page 81: A" Group: Standard Functions

    3–9 SJ200 Inverter “A” Group: Standard Functions Control Source Settings The inverter provides flexibility in how you control Run/Stop operation and set the output frequency (motor speed). It has other control sources that can override the A001/ A002 settings. Parameter A001 sets the source selection for the inverter’s output frequency.
  • Page 82 3–10 “A” Group: Standard Functions Run Command Source Setting - For parameter A002, the following table provides a further description of each option, and a reference to other page(s) for more information Code Run Command Source Refer to page(s)... Control terminal - The [FW] or [RV] input terminals control 4–12 3–42 Run/Stop operation...
  • Page 83 3–11 SJ200 Inverter The inverter has other control sources that can temporarily override the parameter A001 setting, forcing a different output frequency source. The following table lists all frequency source setting methods and their relative priority (“1” is the highest priority). Priority A001 Frequency Source Setting Method Refer to page...
  • Page 84 3–12 “A” Group: Standard Functions Basic Parameter Settings These settings affect the most fundamental behavior of the inverter—the outputs to the motor. The frequency of the inverter’s AC output determines the motor speed. You may select from three different sources for the reference speed. During application develop- ment you may prefer using the potentiometer, but you may switch to an external source (control terminal setting) in the finished application, for example.
  • Page 85 3–13 SJ200 Inverter Analog Input Settings The inverter has the capability to accept an external analog input that can command the output frequency to the motor. Voltage input (0 –10V) and current input (4–20mA) are available on separate terminals ([O] and [OI], respectively). Terminal [L] serves as signal ground for the two analog inputs.
  • Page 86 3–14 “A” Group: Standard Functions “A” Function Defaults Mode Func. Name / –FEF –FU Description Units Edit Code SRW Display (EU) (USA) A005 [AT] selection Four options, select codes: 00... Select between [O] and AT-Slct O/OI [OI] at [AT] 01... [O] + [OI] ([AT] input is ignored) 02...
  • Page 87 3–15 SJ200 Inverter The jog speed setting is used whenever the Jog command is active. The jog speed setting range is arbitrarily limited to 10 Hz, to provide safety during manual operation. The acceleration to the jog frequency is instantaneous, but you can choose from three modes for the best method for stopping the jog operation.
  • Page 88 3–16 “A” Group: Standard Functions Torque Control Algorithms The inverter generates the motor output Inverter Torque Control Algorithms according to the V/f algorithm or the intelli- A044 gent sensorless vector control algorithm. V/f control, constant torque Parameter A044 selects the inverter algorithm for generating the frequency output, as shown Output V/f control,...
  • Page 89 3–17 SJ200 Inverter breakpoint of the boost (point A on the graph) by using parameters A042 and A043. The manual boost is calculated as an addition to the standard V/f curve. NOTE: Manual torque boost is not operational when intelligent sensorless vector control is in use.
  • Page 90 3–18 “A” Group: Standard Functions “A” Function Defaults Mode Func. Name / –FEF –FU Description Units Edit Code SRW Display (EU) (USA) A242 Manual torque boost Can boost starting torque value, 2nd motor between 0 and 20% above normal V/f curve, 2VBst V 0000.0% range is 0.0 to 20.0%...
  • Page 91 3–19 SJ200 Inverter DC Braking Settings The DC braking feature can provide additional stopping torque when Running Free run DC braking compared to a normal deceleration to a stop. DC braking is particularly useful at low speeds when normal decelera- tion torque is minimal.
  • Page 92 3–20 “A” Group: Standard Functions Frequency-related Functions Frequency Limits – Upper and lower Output limits can be imposed on the inverter frequency output frequency. These limits will apply Upper regardless of the source of the speed refer- A061 limit ence. You can configure the lower frequency limit to be greater than zero as Settable shown in the graph.
  • Page 93 3–21 SJ200 Inverter Jump Frequencies – Some motors or machines exhibit resonances at particular speed(s), which can be destructive for prolonged running at those speeds. The inverter has up to three jump frequencies as shown in the graph. The hysteresis around the jump frequencies causes the inverter output to skip around the sensitive frequency values.
  • Page 94: Pid Control

    3–22 “A” Group: Standard Functions PID Control When enabled, the built-in PID loop calculates an ideal inverter output value to cause a loop feedback process variable (PV) to move closer in value to the setpoint (SP). The frequency command serves as the SP. The PID loop algorithm will read the analog input for the process variable (you specify the current or voltage input) and calculate the output.
  • Page 95 3–23 SJ200 Inverter Automatic Voltage Regulation (AVR) Function The automatic voltage regulation (AVR) feature keeps the inverter output waveform at a relatively constant amplitude during power input fluctuations. This can be useful if the installation is subject to input voltage fluctuations. However, the inverter cannot boost its motor output to a voltage higher than the power input voltage.
  • Page 96 3–24 “A” Group: Standard Functions Second Acceleration and Deceleration Functions The SJ200 inverter features two-stage acceleration and deceleration ramps. This gives flexibility in the profile shape. You can specify the frequency transition point, the point at which the standard acceleration (F002) or deceleration (F003) changes to the second acceleration (A092) or deceleration (A093).
  • Page 97 3–25 SJ200 Inverter “A” Function Defaults Mode Func. Name / –FEF –FU Description Units Edit Code SRW Display (EU) (USA) A095 Acc1 to Acc2 frequency Output frequency at which transition point Accel1 switches to Accel2, range is 0.0 to 400.0 Hz ACC CHfr0000.0Hz A295 Acc1 to Acc2 frequency Output frequency at which...
  • Page 98 3–26 “A” Group: Standard Functions Accel/Decel Standard acceleration and deceleration is Output linear. The inverter CPU can also calculate frequency Accel. curve selection an S-curve acceleration or deceleration curve as shown. This profile is useful for Target freq. favoring the load characteristics in particu- lar applications.
  • Page 99 3–27 SJ200 Inverter Additional Analog Input Settings Input Range Settings – The parameters in the following table adjust the input charac- teristics of the analog current input. When using the inputs to command the inverter output frequency, these parameters adjust the starting and ending ranges for the current, as well as the output frequency range.
  • Page 100 3–28 “A” Group: Standard Functions Analog Input Calculate Function – The inverter can mathematically combine two input sources into one value. The Calculate function can either add, subtract, or multiply the two selected sources. This provides the flexibility needed by various applica- tions.You can use the result for the output frequency setting (use A001=10) or for the PID Process Variable (PV) input (use A075=03).
  • Page 101 3–29 SJ200 Inverter ADD Frequency – The inverter can add or subtract an offset value to the output frequency setting which is specified by A001 (will work with any of the five possible sources). The ADD Frequency is a value you can store in parameter A145. The ADD Frequency is summed with or subtracted from the output frequency setting only when the [ADD] terminal is ON.
  • Page 102: B" Group: Fine Tuning Functions

    3–30 “B” Group: Fine Tuning Functions “B” Group: Fine Tuning Functions The “B” Group of functions and parameters adjust some of the more subtle but useful aspects of motor control and system configuration. Automatic Restart Mode The restart mode determines how the inverter will resume operation after a fault causes a trip event.
  • Page 103 3–31 SJ200 Inverter “B” Function Defaults Mode Func. Name / –FEF –FU Description Units Edit Code SRW Display (EU) (USA) B001 Selection of automatic Select inverter restart method, — restart mode four option codes: 00... Alarm output after trip, IPS POWR no automatic restart 01...
  • Page 104 3–32 “B” Group: Fine Tuning Functions you must set the thermal overload threshold in terms of current (amperes) for parameter B012. The range is 20% to 120% of the rated current for each inverter model. If the current exceeds the level you specify, the inverter will trip and log an event (error E05) in the history table.
  • Page 105 3–33 SJ200 Inverter Overload Restriction If the inverter’s output current exceeds a Motor preset current level you specify during Current acceleration or constant speed, the overload Restriction area B022 restriction feature automatically reduces the output frequency to restrict the overload. This feature does not generate an alarm or trip event.
  • Page 106 3–34 “B” Group: Fine Tuning Functions Software Lock Mode The software lock function keeps personnel from accidentally changing parameters in the inverter memory. Use B031 to select from various protection levels. The table below lists all combinations of B031 option codes and the ON/OFF state of the [SFT] input.
  • Page 107 3–35 SJ200 Inverter “B” Function Defaults Mode Func. Name / –FEF –FU Description Units Edit Code SRW Display (EU) (USA) B031 Software lock mode Prevents parameter changes, in — selection four options, option codes: 00... all parameters except S-Lock B031 are locked when [SFT] terminal is ON 01...
  • Page 108 3–36 “B” Group: Fine Tuning Functions Miscellaneous Settings The miscellaneous settings include scaling factors, initialization modes, and others. This section covers some of the most important settings you may need to configure. B080: [AM] analog signal gain – This parameter allows you to scale the analog output [AM] relative to the monitored variable.
  • Page 109 3–37 SJ200 Inverter “B” Function Defaults Mode Func. Name / –FEF –FU Description Units Edit Code SRW Display (EU) (USA) B080 [AM] analog signal Adjust of analog output at 100. 100. — gain terminal [AM], range is 0 to 255 AM-Adj 00100% B082 Start frequency adjust-...
  • Page 110 3–38 “B” Group: Fine Tuning Functions B091/B088: Stop Mode / Restart Mode Configuration – You can configure how the inverter performs a standard stop (each time Run FWD and REV signals turn OFF). Setting B091 determines whether the inverter will control the deceleration, or whether it will perform a free-run stop (coast to a stop).
  • Page 111 3–39 SJ200 Inverter “B” Function Defaults Mode Func. Name / –FEF –FU Description Units Edit Code SRW Display (EU) (USA) B088 Restart mode after FRS Selects how the inverter — resumes operation when the RUN FRS free-run stop (FRS) is cancelled, two options: 00...
  • Page 112 3–40 “B” Group: Fine Tuning Functions “B” Function Defaults Mode Func. Name / –FEF –FU Description Units Edit Code SRW Display (EU) (USA) B150 Carrier mode Automatically reduces the — carrier frequency as the Cr-DEC ambient temperature increases. Two option codes: 00...
  • Page 113 3–41 SJ200 Inverter “C” Group: Intelligent Terminal Functions The six input terminals [1], [2], [3], [4], [5], and [6] can be configured for any of 19 different functions. The next two tables show how to configure the six terminals. The inputs are logical, in that they are either OFF or ON.
  • Page 114 3–42 “C” Group: Intelligent Terminal Functions The input logic convention is programmable for each of the six inputs. Most inputs default to normally open (active high), but you can select normally closed (active low) in order to invert the sense of the logic. “C”...
  • Page 115 3–43 SJ200 Inverter Input Function Summary Table – This table shows all twenty-four intelligent input functions at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Input Terminals” on page 4–9.
  • Page 116 3–44 “C” Group: Intelligent Terminal Functions Input Function Summary Table Option Terminal Function Name Description Code Symbol Unattended Start On powerup, the inverter will not resume a Run Protection command (mostly used in the US) On powerup, the inverter will resume a Run command that was active before power loss Software Lock The keypad and remote programming devices...
  • Page 117 3–45 SJ200 Inverter Input Function Summary Table Option Terminal Function Name Description Code Symbol PIDC PID Reset Resets the PID loop controller. The main conse- quence is that the integrator sum is forced to zero. No effect on PID loop controller Remote Control Accelerates (increases output frequency) motor UP Function (motor-...
  • Page 118 3–46 “C” Group: Intelligent Terminal Functions Output Terminal Configuration The inverter provides configuration for logic (discrete) and analog outputs, shown in the table below. “C” Function Defaults Mode Func. Name / –FEF –FU Description Units Edit Code SRW Display (EU) (USA) C021 Terminal [11] function —...
  • Page 119 3–47 SJ200 Inverter Output Function Summary Table – This table shows all ten functions for the logical outputs (terminals [11], [12]) at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Output Terminals”...
  • Page 120 3–48 “C” Group: Intelligent Terminal Functions Output Function Summary Table Option Terminal Function Name Description Code Symbol Logic Output when the Boolean operation specified by C143 Function has a logical “1” result when the Boolean operation specified by C143 has a logical “0” result Analog Function Summary Table –...
  • Page 121 3–49 SJ200 Inverter The Error for the PID loop is the magni- PID Error (PV–SP) deviation threshold tude (absolute value) of the difference Output between the Setpoint (desired value) and Process Variable (actual value). The PID C044 output deviation signal [OD] (output terminal function option code 04) indicates when the error magnitude has Deviation...
  • Page 122 3–50 “C” Group: Intelligent Terminal Functions Network Communication Settings The following table lists parameters that configure the inverter’s serial communications port. The settings affect how the inverter communicates with a digital operator (such as SRW–0EX), as well as a ModBus network (for networked inverter applications). The settings cannot be edited via the network, in order to ensure network reliability.
  • Page 123 3–51 SJ200 Inverter Analog Signal Calibration Settings The functions in the following table configure the signals for the analog output termi- nals. Note that these settings do not change the current/voltage or sink/source character- istics—only the zero and span (scaling) of the signals. “C”...
  • Page 124 3–52 “C” Group: Intelligent Terminal Functions Miscellaneous Functions The following table contains miscellaneous functions not in other function groups. “C” Function Defaults Mode Func. Name / –FEF –FU Description Units Edit Code SRW Display (EU) (USA) C091 Debug mode enable Displays debug parameters.
  • Page 125 3–53 SJ200 Inverter Output Logic and Timing Logic Output Function – The inverter has a built-in logic output feature. You can select any two of the other nine intelligent output options for internal inputs. Then, configure the logic function to apply the logical AND, OR, or XOR (exclusive OR) operator as desired to the two inputs.
  • Page 126 3–54 “C” Group: Intelligent Terminal Functions “C” Function Defaults Mode Func. Name / –FEF –FU Description Units Edit Code SRW Display (EU) (USA) C143 Logic function select Applies a logic function to — calculate [LOG] output state, LogicOPE three options: 00...
  • Page 127: H" Group: Motor Constants Functions

    3–55 SJ200 Inverter “H” Group: Motor Constants Functions The “H” Group parameters configure the Inverter Torque Control Algorithms inverter for the motor characteristics. You A044 must manually set H003 and H004 values to V/f control, constant torque match the motor. Parameters H006 and H007 are factory-set.
  • Page 128 Operations and Monitoring In This Chapter..page — Introduction ............. — Connecting to PLCs and Other Devices ..— Control Logic Signal Specifications ....— Intelligent Terminal Listing....... — Using Intelligent Input Terminals ..... — Using Intelligent Output Terminals ....—...
  • Page 129 4–2 Introduction Introduction The previous material in Chapter 3 gave a reference listing of all the programmable functions of the inverter. We suggest that you first scan through the listing of inverter functions to gain a general familiarity. This chapter will build on that knowledge in the following ways: 1.
  • Page 130 4–3 SJ200 Inverter Warning Messages for Operating Procedures Before continuing, please read the following Warning messages. WARNING: Be sure to turn ON the input power supply only after closing the front case. While the inverter is energized, be sure not to open the front case. Otherwise, there is the danger of electric shock.
  • Page 131: Connecting To Plcs And Other Devices

    Connecting to PLCs and Other Devices Connecting to PLCs and Other Devices Hitachi inverters (drives) are useful in many types of applications. During installation, the inverter keypad (or other programming device) will facilitate the initial configura- tion. After installation, the inverter will generally receive its control commands through the control logic connector or serial interface from another controlling device.
  • Page 132: Example Wiring Diagram

    4–5 SJ200 Inverter Example Wiring Diagram The schematic diagram below provides a general example of logic connector wiring, in addition to basic power and motor wiring covered in Chapter 2. The goal of this chapter is to help you determine the proper connections for the various terminals shown below for your specific application needs.
  • Page 133: Control Logic Signal Specifications

    4–6 Control Logic Signal Specifications Control Logic Signal Specifications The control logic connectors are located just behind the front housing cover. The relay contacts are just to the left of the logic connectors. Connector labeling is shown below. Logic inputs Relay Analog Analog...
  • Page 134: Intelligent Terminal Listing

    4–7 SJ200 Inverter Intelligent Terminal Listing Intelligent Inputs Use the following table to locate pages for intelligent input material in this chapter. Intelligent INPUTS Symbol Code Name Page Forward Run/Stop 4–12 Reverse Run/Stop 4–12 Multi-speed Select, Bit 0 (LSB) 4–13 Multi-speed Select, Bit 1 4–13 Multi-speed Select, Bit 2...
  • Page 135 4–8 Intelligent Terminal Listing Intelligent Outputs Use the following table to locate pages for intelligent output material in this chapter. Intelligent OUTPUTS Symbol Code Name Page Run Signal 4–37 Frequency Arrival Type 1 – Constant Speed 4–38 Frequency Arrival Type 2 – Over-frequency 4–38 Overload Advance Notice Signal 4–40...
  • Page 136: Using Intelligent Input Terminals

    4–9 SJ200 Inverter Using Intelligent Input Terminals Terminals [1], [2], [3], [4], [5], and [6] are identical, programmable inputs for general use. The input circuits can use the inverter’s internal (isolated) +24V field supply or an external power supply. This section describes input circuits operation and how to connect them properly to switches or transistor outputs on field devices.
  • Page 137 4–10 Using Intelligent Input Terminals The two diagrams below show input wiring circuits using the inverter’s internal +24V supply. Each diagram shows the connection for simple switches, or for a field device with transistor outputs. Note that in the lower diagram, it is necessary to connect terminal [L] only when using the field device with transistors.
  • Page 138 4–11 SJ200 Inverter The two diagrams below show input wiring circuits using an external supply. If using the upper wiring diagram, be sure to use a diode with the external supply. This will prevent a power supply contention in case the SR/SK switch is accidentally placed in the incorrect position.
  • Page 139 4–12 Using Intelligent Input Terminals Forward Run/Stop and Reverse Run/Stop Commands: When you input the Run command via the terminal [FW], the inverter executes the Forward Run command (high) or Stop command (low). When you input the Run command via the terminal [RV], the inverter executes the Reverse Run command (high) or Stop command (low).
  • Page 140 4–13 SJ200 Inverter Multi-Speed Select The inverter can store up to 16 different target frequencies (speeds) that the motor output uses for Input Function steady-state run condition. These speeds are acces- Multi- speed sible through programming four of the intelligent CF4 CF3 CF2 CF1 terminals as binary-encoded inputs CF1 to CF4 per Speed 0...
  • Page 141 4–14 Using Intelligent Input Terminals Option Terminal Input Function Name Description Code Symbol State C001, C002, C003, C004, Example (some CF inputs require input Valid for inputs: C005, C006 configuration; some are default inputs—see page 3–41): F001, A001 = 02, Required settings: (MSB) (LSB)
  • Page 142 4–15 SJ200 Inverter Jogging Command The Jog input [JG] is used to command the [JG] motor to rotate slowly in small increments for manual operation. The speed is limited to [FW], [RV] 10 Hz. The frequency for the jogging opera- tion is set by parameter A038.
  • Page 143 4–16 Using Intelligent Input Terminals External Signal for DC Braking When the terminal [DB] is turned ON, the Scenario 1 DC braking feature is enabled. Set the follow- ing parameters when the external DC braking [FW, RV] terminal [DB] is to be used: •...
  • Page 144: Set Second Motor

    4–17 SJ200 Inverter Set Second Motor If you assign the [SET] function to an intelligent input terminal, you can select between two sets of motor parameters. The second parameters store an alternate set of motor characteristics. When the terminal [SET] is turned ON, the inverter will use the second set of parameters to generate the frequency output to the motor.
  • Page 145 4–18 Using Intelligent Input Terminals Two-stage Acceleration and Deceleration When terminal [2CH] is turned ON, the Output target inverter changes the rate of acceleration and frequency frequency deceleration from the initial settings (F002 second and F003) to use the second set of accelera- initial tion/deceleration values.
  • Page 146 4–19 SJ200 Inverter Free-run Stop When the terminal [FRS] is turned ON, the inverter stops the output and the motor enters the free-run state (coasting). If terminal [FRS] is turned OFF, the output resumes sending power to the motor if the Run command is still active. The free-run stop feature works with other parameters to provide flexibility in stopping and starting motor rotation.
  • Page 147: External Trip

    4–20 Using Intelligent Input Terminals External Trip When the terminal [EXT] is turned ON, the inverter enters the trip state, indicates error code E12, and stops the output. This is a general purpose interrupt type feature, and the meaning of the error depends on what you connect to the [EXT] terminal. Even if the [EXT] input is turned OFF, the inverter remains in the trip state.
  • Page 148: Unattended Start Protection

    4–21 SJ200 Inverter Unattended Start Protection If the Run command is already set when power is turned ON, the inverter starts running immediately after powerup. The Unattended Start Protection (USP) function prevents that automatic startup, so that the inverter will not run without outside intervention. When USP is active and you need to reset an alarm and resume running, either turn the Run command OFF, or perform a reset operation by the terminal [RS] input or the keypad Stop/reset key.
  • Page 149: Software Lock

    4–22 Using Intelligent Input Terminals Software Lock When the terminal [SFT] is turned ON, the data of all the parameters and functions (except the output frequency, depending on the setting of B031) is locked (prohibited from editing). When the data is locked, the keypad keys cannot edit inverter parameters. To edit parameters again, turn OFF the [SFT] terminal input.
  • Page 150 4–23 SJ200 Inverter Analog Input Current/Voltage Select The [AT] terminal selects whether the inverter uses the voltage [O] or current [OI] input terminals for external frequency control. When intelligent input [AT] is ON, you can set the output frequency by applying a current input signal at [OI]-[L]. When the [AT] input is OFF, you can apply a voltage input signal at [O]-[L] to set the output frequency.
  • Page 151: Reset Inverter

    4–24 Using Intelligent Input Terminals Reset Inverter The [RS] terminal causes the inverter to 12 ms execute the reset operation. If the inverter is minimum in Trip Mode, the reset cancels the Trip state. [RS] When the signal [RS] is turned ON and OFF, approx.
  • Page 152: Thermistor Thermal Protection

    4–25 SJ200 Inverter Thermistor Thermal Protection Motors that are equipped with a thermistor can be protected from overheating. Input terminal [6] has the unique ability to sense a thermistor resistance. When the resistance value of the thermistor connected to terminal [TH] (6) and [L] is more than 3 k Ω ±10%, the inverter enters the Trip Mode, turns OFF the output to the motor, and indicates the trip status E35.
  • Page 153 4–26 Using Intelligent Input Terminals Three-wire Interface Operation The 3-wire interface is an industry standard motor control interface. This function uses two inputs for momentary contact start/stop control, and a third for selecting forward or reverse direction. To implement the 3-wire interface, assign 20 [STA] (Start), 21 [STP] (Stop), and 22 [F/R] (Forward/Reverse) to three of the intelligent input terminals.
  • Page 154 4–27 SJ200 Inverter The diagram below shows the use of 3-wire control. STA (Start Motor) is an edge-sensi- tive input; an OFF-to-ON transition gives the Start command. The control of direction is level-sensitive, and the direction may be changed at any time. STP (Stop Motor) is also a level-sensitive input.
  • Page 155 4–28 Using Intelligent Input Terminals PID ON/OFF and PID Clear The PID loop function is useful for controlling motor speed to achieve constant flow, pressure, temperature, etc. in many process applications. The PID Disable function temporarily suspends PID loop execution via an intelligent input terminal. It overrides the parameter A071 (PID Enable) to stop PID execution and return to normal motor frequency output characteristics.
  • Page 156 4–29 SJ200 Inverter Remote Control Up and Down Functions The [UP] [DWN] terminal functions can adjust the output frequency for remote control while the motor is running. The acceleration time and deceleration time of this function is same as normal operation ACC1 and DEC1 (2ACC1,2DEC1). The input terminals operate according to these principles: •...
  • Page 157 4–30 Using Intelligent Input Terminals It is possible for the inverter to retain the frequency set from the [UP] and [DWN] termi- nals through a power loss. Parameter C101 enables/disables the memory. If disabled, the inverter retains the last frequency before an UP/DWN adjustment. Use the [UDC] terminal to clear the memory and return to the original set output frequency.
  • Page 158 4–31 SJ200 Inverter Force Operation from Digital Operator This function permits a digital operator interface to override the following two settings in the inverter: • A001 - Frequency source setting • A002 - Run command source setting When using the [OPE] terminal input, typically A001 and A002 are configured for sources other than the digital operator interface for the output frequency and Run command sources, respectively.
  • Page 159: Add Frequency Enable

    4–32 Using Intelligent Input Terminals ADD Frequency Enable The inverter can add or subtract an offset value to the output frequency setting which is specified by A001 (will work with any of the five possible sources). The ADD Frequency is a value you can store in parameter A145. The ADD Frequency is summed with or subtracted from the output frequency setting only when the [ADD] terminal is ON.
  • Page 160: Force Terminal Mode

    4–33 SJ200 Inverter Force Terminal Mode The purpose of this intelligent input is to allow a device to force the inverter to allow control of the following two parameters via the control terminals: • A001 - Frequency source setting (01 = control terminals [FW] and [RV] •...
  • Page 161: Using Intelligent Output Terminals

    4–34 Using Intelligent Output Terminals Using Intelligent Output Terminals The intelligent output terminals are programmable in a similar way to the intelligent input terminals. The inverter has several output functions that you can assign individu- ally to three physical logic outputs. Two of the outputs are open-collector transistors, and the third output is the alarm relay (form C –...
  • Page 162 4–35 SJ200 Inverter Internal Relay Output The inverter has an internal relay output with Inverter logic normally open and normally closed contacts (Type circuit board 1 form C). The output signal that controls the relay is configurable; the Alarm Signal is the default setting.
  • Page 163 4–36 Using Intelligent Output Terminals Output Signal ON/OFF Delay Function Intelligent outputs including terminals [11], [12], and the output relay, have configurable signal transition delays. Each output can delay either the OFF-to-ON or ON-to-OFF transitions, or both. Signal transition delays are variable from 0.1 to 100.0 seconds. This feature is useful in applications that must tailor inverter output signals to meet timing requirements of certain external devices.
  • Page 164: Run Signal

    4–37 SJ200 Inverter Run Signal When the [RUN] signal is selected as an [FW], intelligent output terminal, the inverter [RV] outputs a signal on that terminal when it is in Run Mode. The output logic is active low, and B082 is the open collector type (switch to ground).
  • Page 165 4–38 Using Intelligent Output Terminals Frequency Arrival Signals The Frequency Arrival group of outputs help coordinate external systems with the current velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output frequency arrives at the standard set frequency (parameter F001). Output [FA2] relies on programmable accel/ decel thresholds for increased flexibility.
  • Page 166 4–39 SJ200 Inverter Frequency arrival output [FA1] uses the Output standard output frequency (parameter 1.5 Hz freq. F001) as the threshold for switching. In 0.5 Hz F001 F001 the figure to the right, Frequency Arrival 1.5 Hz [FA1] turns ON when the output 0.5 Hz frequency gets within 0.5 Hz below or 1.5 Hz above the target constant...
  • Page 167: Overload Advance Notice Signal

    4–40 Using Intelligent Output Terminals Overload Advance Notice Signal When the output current exceeds a preset Current threshold value, the [OL] terminal signal turns ON. C041 power running The parameter C041 sets the overload threshold. The overload detection circuit C041 regeneration operates during powered motor opera- threshold...
  • Page 168: Output Deviation For Pid Control

    4–41 SJ200 Inverter Output Deviation for PID Control The PID loop error is defined as the SP, PV Process variable magnitude (absolute value) of the differ- ence between the Setpoint (target value) C044 Setpoint and the Process Variable (actual value). C044 When the error magnitude exceeds the preset value for C044, the [OD] terminal...
  • Page 169: Alarm Signal

    4–42 Using Intelligent Output Terminals Alarm Signal The inverter alarm signal is active when a fault has STOP occurred and it is in the Trip Mode (refer to the RESET Stop diagram at right). When the fault is cleared the alarm signal becomes inactive.
  • Page 170 4–43 SJ200 Inverter The alarm relay output can be configured in two main ways: • Trip/Power Loss Alarm – The alarm relay is configured as normally closed (C036=1) by default, shown below (left). An external alarm circuit that detects broken wiring also as an alarm connects to [AL0] and [AL1].
  • Page 171: Analog Input Disconnect Detect

    4–44 Using Intelligent Output Terminals Analog Input Disconnect Detect This feature is useful when the inverter receives a speed reference from an external device. Upon input signal loss at either the [O] or [OI] terminal, the inverter normally just decelerates the motor to a stop. However, the inverter can use the intelligent output terminal [Dc] to signal other machinery that a signal loss has occurred.
  • Page 172: Pid Second Stage Output

    4–45 SJ200 Inverter PID Second Stage Output The inverter has a built-in PID loop feature for two-stage control, useful for certain applications such as building ventilation or heating and cooling (HVAC). In an ideal control environment, a single PID loop controller (stage) would be adequate. However, in certain conditions, the maximum output energy from the first stage is not enough to maintain the Process Variable (PV) at or near the Setpoint (SP).
  • Page 173 4–46 Using Intelligent Output Terminals To use the PID Second Stage Output feature, you will need to choose upper and lower limits for the PV, via C053 and C052 respectively. As the timing diagram below shows, these are the thresholds Stage #1 inverter uses to turn ON or OFF Stage #2 inverter via the [FBV] output.
  • Page 174 4–47 SJ200 Inverter Option Terminal Output Function Name Description Code Symbol State Feedback Value • Transitions to ON when the inverter is in RUN Check Mode and the PID Process Variable (PV) is less than the Feedback Low Limit (C053) •...
  • Page 175 4–48 Using Intelligent Output Terminals Network Detection Signal The Network Detection Signal output indicates the general status of network communi- cations. The inverter has a programmable watchdog timer to monitor network activity. Parameter C077 sets the time-out period. If communications stop or pause longer than the specified time-out period, the Ndc output turns ON.
  • Page 176: Logic Output Function

    4–49 SJ200 Inverter Master Slave Watchdog timer Time-out C077 =xx.xx sec. [NDc] Alarm C076 =00 or 01 Logic Output Function The Logic Output Function uses the inverter’s built-in logic feature. You can select any two of the other nine intelligent output options for internal inputs (use C141 and C142). Then, use C143 to configure the logic function to apply the logical AND, OR, or XOR (exclusive OR) operator as desired to the two inputs.
  • Page 177 4–50 Using Intelligent Output Terminals Option Terminal Output Function Name Description Code Symbol State Logic Output when the Boolean operation specified by C143 Function has a logical “1” result when the Boolean operation specified by C143 has a logical “0” result 11, 12, AL0 –...
  • Page 178: Analog Input Operation

    4–51 SJ200 Inverter Analog Input Operation The SJ200 inverters provide for analog input H O OI AM CM2 12 11 to command the inverter frequency output +V Ref. value. The analog input terminal group includes the [L], [OI], [O], and [H] terminals Voltage input on the control connector, which provide for Current input...
  • Page 179 4–52 Analog Input Operation The following table shows the available analog input settings. Parameter A005 and the input terminal [AT] determine the External Frequency Command input terminals that are available, and how they function. The analog inputs [O] and [OI] use terminal [L] as the reference (signal return).
  • Page 180: Analog Output Operation

    4–53 SJ200 Inverter Analog Output Operation In inverter applications it is useful to monitor H O OI AM CM2 12 11 the inverter operation from a remote location or – from the front panel of an inverter enclosure. In Analog A GND some cases, this requires only a panel-mounted Voltage Output...
  • Page 181: Pid Loop Operation

    4–54 PID Loop Operation PID Loop Operation In standard operation, the inverter uses a reference source selected by parameter A001 for the output frequency, which may be a fixed value (F001), a variable set by the front panel potentiometer, or value from an analog input (voltage or current). To enable PID operation, set A071 = 01.
  • Page 182 4–55 SJ200 Inverter PID Loop Configuration The inverter’s PID loop algorithm is configurable for various applications. PID Output Limit - The PID loop controller has a built-in output limit function. This function monitors the difference between the PID setpoint and the loop output (inverter output frequency), measured as a percentage of the full scale range of each.
  • Page 183: Configuring The Inverter For Multiple Motors

    4–56 Configuring the Inverter for Multiple Motors Configuring the Inverter for Multiple Motors Simultaneous Connections For some applications, you may need to connect two or more motors (wired in parallel) to a single inverter’s output. For example, this is common in conveyor applications where two separate conveyors need to SJ200 have approximately the same speed.
  • Page 184 4–57 SJ200 Inverter Having two motor profiles lets you store two “personalities” for motors in one inverter’s memory. The inverter allows the final selection between the two motor types to be made in the field through the use of an intelligent input terminal function [SET]. This provides an extra level of flexibility needed in particular situations.
  • Page 185 Inverter System Accessories In This Chapter..page — Introduction ............. — Component Descriptions......... — Dynamic Braking ..........
  • Page 186 5–3 ALI–x2–xxx LPF–xxx R–2–xxx RF noise Note: The Hitachi part number series for accesso- filter ries includes different sizes of each part type, specified by the –x suffix. Hitachi product litera- AC reactor, or ture can help match size and rating of your LCR filter inverter to the proper accessory size.
  • Page 187: Component Descriptions

    5–3 SJ200 Inverter Component Descriptions AC Reactors, Input Side This is useful in suppressing harmonics induced on the power supply lines, or when the main power voltage imbalance exceeds 3% (and power source capacity is more than 500 kVA), or to smooth out line fluctuations. It also improves the power factor. In the following cases for a general-purpose inverter, a large peak current flows on the main power supply side, and is able to destroy the inverter module: •...
  • Page 188 5–4 Component Descriptions Zero-phase Reactor (RF Noise Filter) The zero-phase reactor helps reduce radiated noise from the inverter wiring. It can be used on the input or output side of the inverter. The example zero-phase reactor shown to the right comes with a mounting bracket.
  • Page 189: Dynamic Braking

    5–5 SJ200 Inverter Dynamic Braking Introduction The purpose of dynamic braking is to improve the ability of the inverter to stop (decelerate) the motor and load. This becomes neces- sary when an application has some or all of the following characteris- tics: •...
  • Page 190 5–6 Dynamic Braking Dynamic Braking Usage Ratio The inverter controls braking via a duty cycle method (percent of the time braking is ON versus total time). Parameter B090 sets the dynamic braking usage ratio. In the graph to the right, the example shows three uses of dynamic braking in a 100-second period.
  • Page 191 Troubleshooting and Maintenance In This Chapter..page — Troubleshooting..........— Monitoring Trip Events, History, & Conditions — Restoring Factory Default Settings ....— Maintenance and Inspection ......— Warranty............
  • Page 192: Troubleshooting

    6–2 Troubleshooting Troubleshooting Safety Messages Please read the following safety messages before troubleshooting or performing mainte- nance on the inverter and motor system. WARNING: Wait at least five (5) minutes after turning OFF the input power supply before performing maintenance or an inspection. Otherwise, there is the danger of electric shock.
  • Page 193: Troubleshooting Tips

    6–3 SJ200 Inverter Troubleshooting Tips The table below lists typical symptoms and the corresponding solution(s). Symptom/condition Probable Cause Solution • • Is the frequency command source Make sure the parameter A001 parameter setting correct? setting A001 is correct. • • Is the Run command source A002 Make sure the parameter parameter setting correct?
  • Page 194 6–4 Troubleshooting Symptom/condition Probable Cause Solution • • If using the analog input, is the Check the wiring. current or voltage at [O] or [OI]? • Check the potentiometer or signal generating device. • • Is the load too heavy? Reduce the load.
  • Page 195: Error Codes

    6–5 SJ200 Inverter Monitoring Trip Events, History, & Conditions Fault Detection and Clearing The microprocessor in the inverter detects a variety STOP of fault conditions and captures the event, record- RESET Stop ing it in a history table. The inverter output turns OFF, or “trips”...
  • Page 196 6–6 Monitoring Trip Events, History, & Conditions Error Name Cause(s) Code E 1 1 CPU error A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the E 2 2 motor. E 1 2 External trip A signal on an intelligent input terminal configured as EXT has occurred.
  • Page 197 6–7 SJ200 Inverter Trip History and Inverter Status We recommend that you first find the cause of the fault before clearing it. When a fault occurs, the inverter stores important performance data at the moment of the fault. To access the data, use the monitor functions (Dxxx) and select D081 for details about the present fault (E ).
  • Page 198: Restoring Factory Default Settings

    6–8 Restoring Factory Default Settings Restoring Factory Default Settings You can restore all inverter parameters to the original factory (default) settings for the intended country of use. After initializing the inverter, use the powerup test in Chapter 2 to get the motor running again. To initialize the inverter, follow the steps below. Action Display Func./Parameter...
  • Page 199: Maintenance And Inspection

    6–9 SJ200 Inverter Maintenance and Inspection Monthly and Yearly Inspection Chart Inspection Cycle Inspection Item Inspected Check for... Criteria Method Month Year Ambient Extreme Thermometer, Ambient temperature environment temperatures hygrometer between -10 to 40°C, & humidity non-condensing Major devices Abnormal Visual and aural Stable environment for Overall...
  • Page 200: Megger Test

    6–10 Maintenance and Inspection Megger Test The megger is a piece of test equipment that uses a high voltage to determine if an insulation degradation has occurred. For inverters, it is important that the power termi- nals be isolated from the Earth GND terminal via the proper amount of insulation. The circuit diagram below shows the inverter wiring for performing the megger test.
  • Page 201: Spare Parts

    6–11 SJ200 Inverter Spare parts We recommend that you stock spare parts to reduce down time, including these parts: Quantity Part description Symbol Notes Used Spare Cooling fan 015NF, 022NF, 030LF, 015HF to 075HF Case • Front case • Key cover •...
  • Page 202 6–12 Maintenance and Inspection General Inverter Electrical Measurements The following table specifies how to measure key system electrical parameters. The diagrams on the next page show inverter-motor systems and the location of measurement points for these parameters. Circuit location Measuring Parameter Notes Reference Value...
  • Page 203 6–13 SJ200 Inverter The figures below show measurement locations for voltage, current, and power measure- ments listed in the table on the previous page. The voltage to be measured is the funda- mental wave effective voltage. The power to be measured is the total effective power. Single-phase Measurement Diagram Inverter Motor...
  • Page 204 6–14 Maintenance and Inspection Inverter Output Voltage Measurement Techniques Taking voltage measurements around drives equipment requires the right equipment and a safe approach. You are working with high voltages and high-frequency switching waveforms that are not pure sinusoids. Digital voltmeters will not usually produce reliable readings for these waveforms.
  • Page 205 6–15 SJ200 Inverter IGBT Test Method The following procedure will check the inverter transistors (IGBTs) and diodes: 1. Disconnect input power to terminals [R, S, and T] and motor terminals [U, V, and W]. 2. Disconnect any wires from terminals [+] and [RB] for regenerative braking. 3.
  • Page 206: Warranty Terms

    (18) months from the date of purchase, or twelve (12) months from the date of installation, whichever occurs first. The warranty shall cover the repair or replacement, at Hitachi's sole discretion, of ONLY the inverter that was installed.
  • Page 207: Glossary And Bibliography

    Glossary and Bibliography In This Appendix..page — Glossary ............— Bibliography ............
  • Page 208 Auto-tuning is a common feature of process controllers with PID loops. Hitachi inverters feature auto tuning to determine motor parameters for optimal commutation. Auto-tuning is avail- able as a special command from a digital operator panel. See also Digital Operator Panel.
  • Page 209 Digital Operator Panel For Hitachi inverters, “digital operator panel” (DOP) refers first to the operator keypad on the front panel of the inverter. It also includes hand-held remote keypads, which connect to the inverter via a cable.
  • Page 210 Insulated Gate Bipolar Transistor (IGBT) – A semiconductor transistor capable of conducting very large currents when in satura- tion and capable of withstanding very high voltages when it is OFF. This high-power bipolar transistor is the type used in Hitachi invert- ers. Inertia The natural resistance a stationary object to being moved by an external force.
  • Page 211 The ability of a motor drive to store preset discrete speed levels for the motor, and control motor speed according to the currently selected speed preset. The Hitachi inverters have 16 preset speeds. Motor Load In motor terminology, motor load consists of the inertia of the physical mass that is moved by the motor and the related friction from guiding mechanisms.
  • Page 212 A–6 Glossary PID Loop Proportional - Integral-Derivative - A mathematical model used for process control. A process controller maintains a process variable (PV) at a setpoint (SP) by using its PID algorithm to compensate for dynamic conditions and vary its output to drive the PV toward the desired value.
  • Page 213 Hot varies sinusoidally above and below Neutral. This power source is named Single Phase to differentiate it from three-phase power sources. Some Hitachi inverters can accept single phase input power, but they all output three-phase power to the motor. See also Three-phase.
  • Page 214 The saturation voltage has been decreasing, resulting in less heat dissipation. Hitachi inverters use state-of-the- art semiconductors to provide high performance and reliability in a compact package. See also IGBT and Saturation Voltage.
  • Page 215 ModBus Network Communications In This Appendix..page — Introduction ............. — Connecting the Inverter to ModBus....— Network Protocol Reference ......— ModBus Data Listing ........
  • Page 216 B–2 Introduction Introduction SJ200 Series inverters have built-in RS-485 serial communications, featuring the ModBus RTU protocol. The inverters can connect directly to existing factory networks or work with new networked applications, without any extra interface equipment. The specifications for SJ200 serial communications are in the following table.
  • Page 217: Connecting The Inverter To Modbus

    B–3 SJ200 Inverter Connecting the Inverter to ModBus Follow the steps in this section to connect the inverter to the ModBus network. 1. Keypad Removal - The inverter keypad uses the serial communications interface connector on the front of the inverter. To access the RJ45 modular connector, you will need to remove the keypad.
  • Page 218 B–4 Connecting the Inverter to ModBus 4. Terminate Network Wiring - The RS-485 wiring must be terminated at each physical end to suppress electrical reflections and help decrease transmission errors. The SJ200 communications port does not include a termination resistor. Therefore, you will need to add termination to the inverter if it is at the end of the network wiring.
  • Page 219 B–5 SJ200 Inverter 6. Inverter Parameter Setup - The inverter has several settings related to ModBus communications. The table below lists them together. The Required column indicates which parameters must be set properly to allow communications. You may need to refer to the host computer documentation in order to match some of its settings.
  • Page 220: Network Protocol Reference

    B–6 Network Protocol Reference Network Protocol Reference Transmission procedure The transmission between the external control equipment and the inverter takes the procedure below Query External control equipment Response Inverter Latency time (silent interval plus C078 setting) • Query - A frame sent from the external control equipment to the inverter •...
  • Page 221 B–7 SJ200 Inverter Data: • A function command is set here. • The data format used in the SJ200 series is corresponding to the Modbus data format below. Name of Data Description Coil Binary data that can be referenced and changed (1 bit long)
  • Page 222 B–8 Network Protocol Reference Message Configuration: Response Transmission time required: • A time period between reception of a query from the master and transmission of a response from the inverter is the sum of the silent interval (3.5 characters long) + C078 (transmission latency time).
  • Page 223 B–9 SJ200 Inverter No response occurs: In the cases below, the inverter ignores a query and returns no response. • When receiving a broadcasting query • When detecting a transmission error in reception of a query • When the slave address set in the query is not equal to the slave address of the inverter •...
  • Page 224 B–10 Network Protocol Reference Explanation of function codes Read Coil Status [01h]: This function reads the status (ON/OFF) of selected coils. An example follows below. • Read intelligent input terminals [1] to [6] of an inverter having a slave address “8.” •...
  • Page 225 B–11 SJ200 Inverter • When a read coil is outside the defined coils, the final coil data to be transmitted contains “0“as the status of the coil outside the range. • When the Read Coil Status command cannot be executed normally, see the exception response.
  • Page 226 B–12 Network Protocol Reference The data set in the response is as follows: Response Buffer Coil Number + 0 (high + 0 (low + 1 (high + 1 (low + 2 (high + 2 (low order) order) order) order) order) order) Coil Status Trip data...
  • Page 227 B–13 SJ200 Inverter When writing in a selected coil fails, see the exception response. Write in Holding Register [06h]: This function writes data in a specified holding register. An example follows: • Write “50Hz” as the first Multi-speed 0 (A020) in an inverter having slave address “5.”...
  • Page 228 B–14 Network Protocol Reference Loopback Test [08h]: This function checks a master-slave transmission using any test data. An example follows: • Send test data to an inverter having slave address “1” and receiving the test data from the inverter (as a loopback test). Query: Response: Example...
  • Page 229 B–15 SJ200 Inverter Write in Coils [0Fh]: This function writes data in consecutive coils. An example follows: • Change the state of intelligent input terminal [1] to [6] of an inverter having a slave address “5.” • This example assumes the intelligent input terminals have terminal states listed below. Item Data Intelligent input terminal...
  • Page 230 B–16 Network Protocol Reference Writing in Holding Registers [10h]: This function writes data in consecutive holding registers. An example follows: • Write “3000 seconds” as the first acceleration time 1 (F002) in an inverter having a slave address “1.” • This example uses change data “300000(493E0h)” to set “3000 seconds” as the data resolution of the registers “0024h”...
  • Page 231 B–17 SJ200 Inverter Exception Response: When sending a query (excluding a broadcasting query) to an inverter, the master always requests a response from the inverter. Usually, the inverter returns a response according to the query. However, when finding an error in the query, the inverter returns an excep- tion response.
  • Page 232 B–18 Network Protocol Reference Store New Register Data (ENTER command) After being written in a selected holding register by the Write in Holding Register command (06h) or in selected holding registers by the Write in Holding Registers command (10h), new data is temporary and still outside the storage element of the inverter.
  • Page 233: Modbus Data Listing

    B–19 SJ200 Inverter ModBus Data Listing ModBus Coil List The following tables list the primary coils for the inverter interface to the network. The table legend is given below. • Coil Number - The network address to the coil, which is a single bit (binary) value •...
  • Page 234 B–20 ModBus Data Listing List of Coil Numbers Coil Name Description Number 0014h Alarm signal 0 ..Normal 1 ..Trip 0015h PID deviation signal 0 ..OFF 1 ..ON 0016h Overload signal 0017h Frequency arrival signal (set frequency or above) 0018h Frequency arrival signal (at constant speed) 0019h Run Mode signal...
  • Page 235 B–21 SJ200 Inverter ModBus Holding Registers The following tables list the holding registers for the inverter interface to the network. The table legend is given below. • Function Code - The inverter’s reference code for the parameter or function (same as inverter keypad display) •...
  • Page 236 B–22 ModBus Data Listing List of Holding Registers Network Data Func. Name Description Code Reg. Range Res. D001 Output frequency Real-time display of output 00Ah 0 to 0.1 Hz monitor frequency to motor, from 4000 0.0 to 400.0 Hz D002 Output current monitor Filtered display of output 00Bh...
  • Page 237 B–23 SJ200 Inverter Note 1: Assume that the inverter current rating is 1000 (for D002). The following table lists holding registers for the “D” Group Monitor Functions. Holding Registers, “D” Group Monitor Functions Network Data Func. Name Description Code Reg. Res.
  • Page 238 B–24 ModBus Data Listing The table below lists the holding registers for the “F” Group Main Profile Parameters. Holding Registers, “F” Group Main Profile Parameters Network Data Func. Name Description Code Reg. Range Res. F001 Output frequency R/W Standard default target 0023h 0 / (start 0.1 Hz...
  • Page 239 B–25 SJ200 Inverter The following table lists the holding registers for the “A” Group Standard Functions. Holding Registers for “A” Group Standard Functions Network Data Func. Name Description Code Reg. Range Res. A001 Frequency source R/W Five options; select codes: 002Dh 0 to 3, 10 —...
  • Page 240 B–26 ModBus Data Listing Holding Registers for “A” Group Standard Functions Network Data Func. Name Description Code Reg. Range Res. A015 Pot./O–L input start R/W Two options; select codes: 0038h 0, 1 — frequency enable 00... Use offset (A011 value) 01...
  • Page 241 B–27 SJ200 Inverter Holding Registers for “A” Group Standard Functions Network Data Func. Name Description Code Reg. Range Res. A042 Manual torque boost R/W Can boost starting torque 004Fh 0 to 200 0.1 % value between 0 and 20% above normal V/f curve, A242 Manual torque boost...
  • Page 242 B–28 ModBus Data Listing Holding Registers for “A” Group Standard Functions Network Data Func. Name Description Code Reg. Range Res. A056 DC braking / edge or R/W Two options; select codes: 0061h 0, 1 — level detection for [DB] 00... Edge detection input 01...
  • Page 243 B–29 SJ200 Inverter Holding Registers for “A” Group Standard Functions Network Data Func. Name Description Code Reg. Range Res. A077 Reverse PID action R/W Two option codes: 00E1h 0, 1 — 00... PID input = SP – PV 01... PID input = –(SP – PV) A078 PID output limit R/W Sets the limit of PID output as...
  • Page 244 B–30 ModBus Data Listing Holding Registers for “A” Group Standard Functions Network Data Func. Name Description Code Reg. Range Res. A094 Select method to switch R/W Two options for switching 007Ch 0, 1 — to Acc2/Dec2 profile from 1st to 2nd accel/decel: 00...
  • Page 245 B–31 SJ200 Inverter Holding Registers for “A” Group Standard Functions Network Data Func. Name Description Code Reg. Range Res. A141 A input select for calcu- R/W Five options: 00E3h 0 to 4 — late function 00... Digital operator 01... Keypad potentiometer 02...
  • Page 246 B–32 ModBus Data Listing The following table lists the holding registers for the “B” Group Fine Tuning Functions. “B” Group Fine Tuning Functions Network Data Func. Name Description Code Reg. Range Res. B001 Selection of automatic R/W Select inverter restart method, 0089h 0, 1, 2, 3 —...
  • Page 247 B–33 SJ200 Inverter “B” Group Fine Tuning Functions Network Data Func. Name Description Code Reg. Range Res. B021 Overload restriction R/W Select the operating mode 0092h 0, 1, 2 — operation mode during overload conditions, three options, option codes: 00... Disabled 01...
  • Page 248 B–34 ModBus Data Listing “B” Group Fine Tuning Functions Network Data Func. Name Description Code Reg. Range Res. B085 Country code for initial- — Select default parameter values 009Bh — — ization (not accessible for country on initialization. to ModBus) Note: Write not allowed from network.
  • Page 249 B–35 SJ200 Inverter “B” Group Fine Tuning Functions Network Data Func. Name Description Code Reg. Range Res. B130 Over-voltage R/W Pauses deceleration ramp when 00A4h 0, 1 — LADSTOP enable DC bus voltage rises above threshold level, in order to avoid over-voltage trip.
  • Page 250 B–36 ModBus Data Listing The following table lists the holding registers for the “C” Group Intelligent Input Functions. “C” Group Intelligent Terminal Functions Network Data Func. Name Description Code Reg. Range Res. C001 Terminal [1] function 00A7h 0, 1, 2, 3, —...
  • Page 251 B–37 SJ200 Inverter “C” Group Intelligent Terminal Functions Network Data Func. Name Description Code Reg. Range Res. C041 Overload level setting R/W Sets the overload signal level 00BBh 0 to 0.01 % between 0% and 200% (from 0 20000 to two times the rated current of the inverter) C042 Frequency arrival...
  • Page 252 B–38 ModBus Data Listing “C” Group Intelligent Terminal Functions Network Data Func. Name Description Code Reg. Range Res. C082 OI input span calibra- R/W Scale factor between the 00C8h 0 to 2000 0.1 % tion external frequency command on terminals L – OI (current input) and the frequency output, range is 0.0 to 200.0% C085...
  • Page 253 B–39 SJ200 Inverter “C” Group Intelligent Terminal Functions Network Data Func. Name Description Code Reg. Range Res. C146 Terminal [12] ON delay R/W Range is 0.0 to 100.0 sec. 00F4h 0 to 1000 0.1 sec C147 Terminal [12] OFF R/W Range is 0.0 to 100.0 sec. 00F5h 0 to 1000 0.1 sec delay...
  • Page 254: Drive Parameter Settings Tables

    Drive Parameter Settings Tables In This Appendix..page — Introduction ............. — Parameter Settings for Keypad Entry....
  • Page 255: Parameter Settings For Keypad Entry

    Parameter Settings for Keypad Entry SJ200 series inverters provide many functions and parameters that can be configured by the user. We recommend that you record all parameters that have been edited, in order to help in troubleshooting or recovery from a loss of parameter data.
  • Page 256: Standard Functions

    C–3 SJ200 Inverter Standard Functions “A” Group Parameters Default Setting User Func. -FEF Setting Name Code (EU) (USA) A001 Frequency source setting A002 Run command source setting A003 Base frequency setting 50.0 60.0 A203 Base frequency setting, 2nd 50.0 60.0 motor A004 Maximum frequency setting...
  • Page 257 C–4 Parameter Settings for Keypad Entry “A” Group Parameters Default Setting User Func. -FEF Setting Name Code (EU) (USA) A031 Multi-speed 11 setting A032 Multi-speed 12 setting A033 Multi-speed 13 setting A034 Multi-speed 14 setting A035 Multi-speed 15 setting A038 Jog frequency setting 1.00 1.00...
  • Page 258 C–5 SJ200 Inverter “A” Group Parameters Default Setting User Func. -FEF Setting Name Code (EU) (USA) A062 Frequency lower limit setting A262 Frequency lower limit setting, 2nd motor A063, Jump (center) frequency setting A065, A067 A064, Jump (hysteresis) frequency A066, width setting A068 A071...
  • Page 259 C–6 Parameter Settings for Keypad Entry “A” Group Parameters Default Setting User Func. -FEF Setting Name Code (EU) (USA) A296 Dec1 to Dec2 frequency transi- tion point, 2nd motor A097 Acceleration curve selection A098 Deceleration curve selection A101 [OI]–[L] input active range start frequency A102 [OI]–[L] input active range end...
  • Page 260 C–7 SJ200 Inverter Fine Tuning Functions “B” Group Parameters Default Setting User Func. -FEF Setting Name Code (EU) (USA) B001 Selection of automatic restart mode B002 Allowable under-voltage power failure time B003 Retry wait time before motor restart B004 Instantaneous power failure / under-voltage trip alarm enable B005 Number of restarts on power...
  • Page 261 C–8 Parameter Settings for Keypad Entry “B” Group Parameters Default Setting User Func. -FEF Setting Name Code (EU) (USA) B087 STOP key enable B088 Restart mode after FRS B090 Dynamic braking usage ratio B091 Stop mode selection B092 Cooling fan control B095 Dynamic braking control B096...
  • Page 262 C–9 SJ200 Inverter Intelligent Terminal Functions “C” Group Parameters Default Setting User Func. -FEF Setting Name Code (EU) (USA) C001 Terminal [1] function C002 Terminal [2] function C003 Terminal [3] function C004 Terminal [4] function C005 Terminal [5] function C006 Terminal [6] function C011 Terminal [1] active state...
  • Page 263 C–10 Parameter Settings for Keypad Entry “C” Group Parameters Default Setting User Func. -FEF Setting Name Code (EU) (USA) C075 Communication stop bit selection C076 Communication error select C077 Communication erorr time-out 0.00 0.00 C078 Communication wait time C081 O input span calibration 100.0 100.0 C082...
  • Page 264 C–11 SJ200 Inverter Motor Constants Functions “H” Group Parameters Default Setting User Func. -FEF Setting Name Code (EU) (USA) H003 Motor capacity Specified Specified by the by the inverter inverter capacity capacity H203 Motor capacity, 2nd setting Specified Specified by the by the inverter inverter...
  • Page 265 CE–EMC Installation Guidelines In This Appendix..page — CE–EMC Installation Guidelines ..... — Hitachi EMC Recommendations .....
  • Page 266: Ce–Emc Installation Guidelines

    D–2 CE–EMC Installation Guidelines CE–EMC Installation Guidelines You are required to satisfy the EMC directive (89/336/EEC) when using an SJ200 inverter in an EU country. To satisfy the EMC directive and to comply with standard, follow the guidelines in this section. 1.
  • Page 267 D–3 SJ200 Inverter 4. Take measures to minimize interference that is frequently coupled in through installa- tion cables. • Separate interfering cables with 0.25m minimum from cables susceptible to inter- ference. A particularly critical point is laying parallel cables over longer distances. If two cables intersect (one crosses over the other), the interference is smallest if they intersect at an angle of 90°.
  • Page 268 D–4 CE–EMC Installation Guidelines SJ200 inverter designed for use in Europe (–xxxLFEF/xxxHFEF models) have built-in line filters. In the event your application needs additional filtering, the following diagrams show control panel mounting and wiring examples for different filter types. SJ200 inverter with footprint-type filter...
  • Page 269 D–5 SJ200 Inverter SJ200 inverter with book-type filter...
  • Page 270: Hitachi Emc Recommendations

    D–6 Hitachi EMC Recommendations Hitachi EMC Recommendations WARNING: This equipment should be installed, adjusted, and serviced by qualified personal familiar with construction and operation of the equipment and the hazards involved. Failure to observe this precaution could result in bodily injury.
  • Page 271 Index A Group functions 3–9 B Group functions 3–30 AC reactors 5–3 Base frequency 2–30, A–2 Acceleration 1–16, 3–8 setting 3–12 characteristic curves 3–26 Bibliography A–8 second function 3–24 Braking 1–15 two-stage 4–18 dynamic 5–5 Access levels 3–5, 3–34, 4–22 resistive 1–18 Accessories...
  • Page 272 Index–2 Choke 2–8, 5–4, A–2 Chopper frequency 3–36 Editing parameters 2–25, 2–28 Circuit breaker sizes in Run Mode 3–5, 3–34, 4–22 Clearance for ventilation 2–11 Electromagnetic compatibility D–2 Coasting 3–38 Electronic thermal overload Connectors configuration 3–31 logic terminals 2–5 error code 6–5 removal 2–5...
  • Page 273 Index–3 SJ200 Inverter Glossary of terms A–2 Keypad 1–3, 2–2, 3–2 features 2–25, 3–3 navigation 2–27, 3–4 navigation, trip events 6–7 H Group parameters 3–55 removal and installation 2–3 Harmonics A–4 History of trip events 3–7 Horsepower A–4 LEDs 2–3, 2–24, 2–25, 2–33, 3–3 Line reactor A–5...
  • Page 274 Index–4 Nameplate 1–4 Parameter editing 2–25, 2–28 Navigational map 2–27, 3–4 Parameter settings 1–15, 2–26 trip events 6–7 listings C–2 A–5 PID loop 1–19 NEMA clear input 4–28 definition A–5 configuration 4–55 rated installation 1–3 definition A–6 Network communications 1–17, 2–3, B–2 error 4–41, A–3...
  • Page 275 Index–5 SJ200 Inverter Ratings label 1–4 Safety messages Reactance A–6 Saturation voltage A–6 Read/write copy unit 1–3 Scaling 3–36 Rectifier A–6 S-curve accel/decel 3–26 Reduced torque 3–16 Second accel and decel 3–24 Regenerative braking A–6 Second motor 4–17 Regulation A–6 Second stage output 4–45 Regulatory agency approvals...
  • Page 276 Index–6 Tachometer A–7 V/f control 3–16 Technical support xviii Variable torque 3–16 Term definitions A–2 Variable-frequency drives Terminal/program source configuration 2–6, introduction 1–12 2–28, 3–10 Velocity profile 1–16 Terminals Ventilation 2–11, 2–23 arrangement 2–20 Voltage gain 3–17 listing 4–7 Voltage input 3–13 torque specs xiii, 2–19...