Miscellaneous
The miscellaneous settings include scaling factors, initialization modes, and others. This
section covers some of the most important settings you may need to configure.
Settings
Func.
Name/
Code
Description
B034
Run/power-on warning time
B035
Rotational direction restriction
B036
Reduced voltage start selection
Function Display
The inverter has the (optional) capability to suppress the display and editing of certain parame-
Settings
ters. Use B037 to select the display options. The purpose of this feature is to hide particular
secondary parameters that become unused or not applicable based on more fundamental param-
eter settings. For example, setting A001 = 01 configures the inverter to get its frequency
command from the front keypad potentiometer. In this case, the inverter will not use the analog
inputs nor their adjustment parameters for an external frequency command.
Func.
Name/
Code
Description
B037
Function code display
restriction
B038
Initial display selection
B039
Automatic user parame-
ter function enable
For example, you can set B037=01 to have the inverter suppress the displaying of all analog
input parameters when A001=01, as shown in the first row of the following table.
Keypad
SRW
OPE
00
FREE
0 1
FW
02
RV
Keypad
SRW
OPE
00
ALL
Display all
0 1
FUNCTION
Display only utilized functions (see
table on next page)
02
USER
Display user-selected functions only
(configure with U01 to U12)
03
COMPARE
Data comparison display
04
BASIC
Basic display
00
STR
Last value dislayed when STR key
was pressed
0 1
FM
D001
02
D002
Iout
03
Dir
D003
04
F-CNV
D007
05
F-SET
F001
00
OFF
Disable
0 1
ON
Enable
Function
Data
Code
A001
01
A005, A006, A011 – A016, A101 –
A114, C081 – C083, C121 – C123
Range and Settings
0 to 9999. (0 to 99990), 1000 to
6553 (10000 to 655300) (hours)
Enable for both directions
Enable for forward only
Enable for reverse only
000 (short) to 255 (long)
Range and Settings
Resulting Non-displayed
Functions (when B37 = 01)
3–39
SJ700
Inverter
2
Defaults
Run
Mode
FEF2
FUF2
FF2
Edit
FE2
FU2
F2
Lo Hi
(EU)
(USA)
(Jpn)
✘ ✔
0.
0.
0.
✘ ✘
00
00
00
✘ ✘
✘ ✘
✘ ✔
06
06
06
Defaults
Run
Mode
xFE2
xFU2
xFF2
Edit
(EU)
(USA)
(Jpn)
Lo Hi
✘ ✔
04
04
04
✘ ✔
01
01
01
✘ ✔
00
00
00
Notes
[O], [OI], [O2] terminal
functions