Maximum
Capacity
F
(kHz)
(kW)
c
0.75
15
1.5
15
2.2
15
3.7
15
5.5
15
7.5
15
11
15
15
14
95% (30.4A or less)
18.5
10
90% (34.2A or less)
22
6
75% (36.0A or less)
30
10
75% (43.5A or less)
NOTE: When replacing an SJ300 inverter combined with LCR filter, please check the type
code of LCR filter and consult for compatibility (75 to132kW).
400V Class Inverters
Derating at
Capacity
Maximum Fc
(kW)
100%
37
100%
45
100%
55
100%
75
100%
90
100%
110
100%
150
185
315
400
—
SJ700
Inverter
2
Maximum
Derating at
F
(kHz)
Maximum Fc
c
8
80% (60.0A or less)
9
75% (68.2A or less)
6
60% (67.2A or less)
6
85% (126.7A or less)
4
75% (132.0A or less)
6
70% (151.9A or less)
3
60% (156.0A or less)
3
100%
3
100%
3
80% (640.0A or less)
—
—
1–13