Panasonic MEW01091 Operating Instructions Manual page 77

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
Action
74
Power down
up again. ("Cold restart")
Via menu H8/S4 Safe shut down
of control unit. ("Cold restart")
Automatically after download of
site specific data (SSD) via a PC
& Win128. ("Warm restart")
Automatically after download of
S/W or text file via a PC &
Win128. ("Cold restart")
Automatically due to external
76
disturbance.
("Cold restart")
Data, etc.
which will be
deleted
and then power
SSW
FFD, WASV
FFD, WASV
FF, WASV
FFD, WASV
FFD, WASV
NOTE! During the restart, the output "R1" for Fault tx will be
"activated", the supervised 24 V DC outputs S0-S1 will be not
supervised and S0-S1 programmed as normally high will be low for a
few seconds.
During the "restart", no fire alarm can be activated and the buzzer will
sound until the following text messages is show in the display:
*** EBL128 ***
Checking program memory......
And for a second (if everything is all right, else see Memory fault
below):
Booting......
A fault is now generated and the following text message will be
shown in the display:
FAULT: Restart code xx addr yyyy
Date: MM-DD
Time: HH:MM
74
Both rectifier (mains) and battery disconnected.
75
All alarm points, zones, units, outputs, COM loop etc. that were disabled
(disconnected) before a warm restart will remain disabled after the restart
provided they also exists in the new downloaded SSD.
disablement will be terminated.
76
If this happens often, call for service personnel / engineer.
75
EBL128 Operating Instructions V1.1.x
Data, etc.
Restart code
which will be
not deleted
SSD,
S/W
SSD,
S/W, SSW
SSD,
S/W, SSW
75
D
SSD,
S/W, SSW
SSD,
S/W, SSW
00
00 alt. 03
03
00 alt. 03
01, 02 alt.
04-20
If not, this

Advertisement