Perform Zone Test (Test Mode) (H7) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
30
Action
"Access"
Scroll to menu H7.
"A"
Write zone numbers
(e.g. 01, 02, 03, 04).
"A"
The zone(s) will stay in test mode until the test mode is ended but after 60 minutes or if you press
"Return" two times you will be out-logged from menu H7.
Perform the test as quickly as possible, since the output(s) for routing equipment (fire brigade tx) are disabled
(also the parts of the zones in test mode, not visible for the test personnel, are disabled).
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled",
i.e. fire alarm will be detected faster than normally.
In the tested alarm point, the LED will light up, and the LED:s "Fire" (L1) in EBL128 will light up, about ten
Rev: 3
Perform ZONE TEST (test mode)
(H7)
Normally, zones are tested during the monthly test via menu H1, see
page 79. Via menu H7 it is possible to perform the zone test solely.
In test mode, only the alarm points are tested, i.e. no outputs (no
sounders) will be activated during the test. (Alarm devices can be
tested via menu H8/S3.)
If a real fire alarm is activated by an alarm point not in test mode,
the normal fire alarm functions will be activated, i.e. fire alarm
presentation, outputs (sounders) activated, routing equipment (fire
brigade tx) activated, etc. but the zone(s) in test mode will remain in
test mode until the test mode is ended. During the fire alarm the
zone(s) in test mode can be displayed via menu X3, see chapter
"Display disablements (X3)", page 44.
See also chapter "The display in EBL128", page 20.
There will be an automatic ending of the test mode one hour after the
latest tested alarm point / zone.
NOTE! If the door in EBL128 is left open, the output(s) for routing
equipment (fire brigade tx) might be disabled (if set so in Win128).
Text in display
Perform ZONE TEST
Zone to be set in TEST MODE:
??
??
??
??
Zone to be set in TEST MODE:
01
02
03
04
Zone in TEST MODE:
01
02
03
04
EBL128 Operating Instructions V1.1.x
ACCEPT? H7
Start test:
ACCEPT
Start test:
ACCEPT
End test:
ACCEPT
116
Comments
According to chapter
"Access", see page 78.
NOTE! In Danish (DBI)
convention, only one zone.
Press "A" to start the test
mode.
LED "Test mode" (L9)
will light up.
Perform the tests.