Disable Interlocking Output (H9/C4) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
32.4
Action
"Access"
Scroll to menu H9.
"A"
Scroll to menu C4.
"A"
Write the area and point,
e.g.: "01", "01"
"A"
Rev: 3

Disable interlocking output (H9/C4)

Interlocking outputs (Type = Interlocking) will be disabled via this
menu but not via menu H2/B3.
The "Interlocking Combination" (Area / Point) is to be entered to
disable the output. If "00/00" is entered, all interlocking outputs will
be disabled at the same time.
All interlocking outputs can be disabled.
Disabled interlocking outputs are listed in menu H4/U1.
The LED "Disablements" (L8) is also indicating one or more disabled
interlocking outputs.
Text in display
Interlocking outputs and inputs
Activated interlocking outputs/inputs
Disable interlocking output
Disable interlocking output
area 00 point 00
Disable interlocking output
area 01 point 01
Disable interlocking output
EBL128 Operating Instructions V1.1.x
ACCEPT? H9
ACCEPT? C1
ACCEPT? C4
ACCEPT?
ACCEPT?
ACCEPT? C4
130
Comments
According to chapter
"Access", see page 78.
Press "A" to accept and/or
"Return" to menu C4.
Scroll or press "Return" to
menu H9. Scroll or press
"Return" to log off.