Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
FAULT: FBP x
FBP=1826 / 1828 (Ext. Fire Brigade Panel)
The ext. FBP is programmed as another type of unit than the SSD says
or a faulty unit.
FAULT: High current consumption in CU
EBL128 current consumption, including battery charging, is over 1.8
A, and because of this, the battery charging is turned off. The current
consumption, excluding battery charging, exceeds 0.8 A and the
battery charging is turned off as long as the current consumption
exceeds 0.75 A. (Normally this fault only appears when starting up /
expanding an EBL128.)
FAULT: Input
A fault on the supervised input I0 in EBL128.
Check the cables / connections (cut-off or short-circuit).
FAULT: Input x exp board x
A fault on the supervised input x on the expansion board (4583) with
address x.
Check the cables / connections (cut-off or short-circuit).
FAULT: Interlocking input AA/PP
An interlocking input is not activated within the time set for fault
activation (5-255 seconds). The time is counted from the activation of
the output (in the interlocking combination, area / point).
FAULT: Key cabinet
The key cabinet has been opened without a prior fire alarm (i.e.
somebody has opened the key cabinet illegally).
or
The key cabinet has not been closed within 5 minutes after reset of all
fire alarms.
FAULT: Loop unit xx-xx
Press "" to see the technical address.
59
EBL128 Operating Instructions V1.1.x