Technical Address / Presentation Number; Technical Address For Com Loop Units; Presentation Number - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
15
15.1
15.2
Technical address / Presentation
number

Technical address for COM loop units

The technical address in EBL128 is used when programming (via
Win128) all units connected to the COM loop.
The technical address is also used to identify which unit has generated
a fault.
The technical address is equal to the address that is set in each unit
connected to the COM loop with the Address setting tool 3314.
Addresses 001 – 127 can be set (not 000).

Presentation number

For each fire alarm point / zone line input, a presentation number,
NN-NN, has to be programmed. The presentation number is shown in
the display in EBL128 and in Ext. FBP 1826 / 1828, Alert
Annunciation unit 1735 / 1736 and Ext. Presentation unit 1728, to
identify the point / zone generating a fire alarm. It is also used to
disable / re-enable fire alarm points / zones and in control conditions /
expressions to activate the programmable outputs.
Together with the presentation number, an alarm text with up to 40
alphanumeric characters can be displayed (if programmed via
Win128).
NN – NN
NOTE! Only the zone numbers 01-32 can be used.
35
The Addressable Base station for wireless units (4610) has a DIL-switch
for the COM loop address. See the Technical description for 4610.
37
EBL128 Operating Instructions V1.1.x
00 – 99
01 – 99 = The Address within the zone.
00 = Zone number only will be displayed.
E.g. for one or more conventional detectors
connected to a MIO (3361) or a zone line input
(4580)
01 – 32 = Zone number
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebl128

Table of Contents