18.2

Fault acknowledge

The LEDs "Fault tx activated" (L11) and "General fault" (L7) are
turned ON.
(LEDs "Fault / Disablements Alarm devices" (L13), "System fault"
(L14) and/or "Fault / Disablements Fire brigade tx" (L15) might be
turned ON as well.)
Output for routing equipment (Fault tx) is activated.
Output for general fault is activated.
Output for general charge fault might be activated.
A fault message, date and time, is shown in the EBL128 display.
After the time might be shown
fault is generated.
After the time might be shown
"Serviced"
serviced / corrected.
are set to be "Not latched".
 Login, according to chapter "Access", page 78.
 Use menu H6 (access code for level 2B required) for fault
acknowledge, see chapter "Acknowledge FAULTS (H6)",
page 115. Menu H6 is a list showing a maximum of 100
faults (not acknowledged faults and/or acknowledged but not
corrected faults). The first fault in the list is the most recent
fault. When a fault is acknowledged and corrected it will be
removed from the list (and a new fault can be shown, if there
are more than 100). Corrected faults are shown in the event
log (menu H4/U5).
 All faults have to be individually acknowledged one by one
with push button "Fault acknowledge" (P6). Use  or 
keys to scroll.
 If a fault has been serviced / corrected before it has been
acknowledged, the text
63
time.
It still has to be acknowledged.
 When a fault is corrected and acknowledged, it will
disappear from the list (H6).
 When all faults have been acknowledged, the LED "Fault tx
activated" (L11) will be turned off and output for routing
equipment (Fault tx) is "reset" (as in normal operation).
 As long as there are faults (not acknowledged faults and/or
acknowledged but not corrected faults) the LED "General
fault" (L7) will be lit and general fault (and maybe general
charge fault) output(s) are activated.
63
Via Win128 the faults can be set to be not latched. Corrected faults will
in this case automatically disappear from the list without being acknowledged
before.
67