Acknowledged Alarm; Isolated Alarm - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
17.7
17.8

Acknowledged alarm

NOTE! Valid for the New Zealand convention only.
A fire alarm presented in the LCD can be acknowledged by pressing
the button "Acknowledge fault" (P6).
Acknowledged alarms are indicated in the fire alarm list in the LCD
by "ACK" in front of the alarm, see page 42. This indication is the
only difference between a fire alarm and an acknowledged alarm.
Acknowledged alarms ("ACK") have to be reset like fire alarms
("ALM").

Isolated alarm

NOTE! Valid for the New Zealand convention only.
A fire alarm ("ALM") or an acknowledged alarm ("ACK") presented
in the LCD can be isolated as follows:
When the "New Zealand FB Silence switch" (outside switch) is turned
OFF (from activated to not activated), any fire alarm and
acknowledged alarm will be isolated (=disabled).
Isolated alarms are indicated in the fire alarm list in the LCD by "ISO"
in front of the alarm respectively, see page 42.
Isolated alarms do not activate any control outputs, do not activate the
output for routing equipment (Fire brigade tx), do not activate the
c.i.e. buzzer and do not activate the LED:s "Fire" in the c.i.e.
Isolated alarms ("ISO") have to be reset like fire alarms ("ALM").
Isolated alarms have to be re-enabled via menu H2/B5 or B6 before
they can activate a new fire alarm again.
57
LED "Disablements" (L8) is indicating that one or more zones / alarm
points are isolated (disabled).
53
EBL128 Operating Instructions V1.1.x
57