Show Configuration And Alarm Counter (H4/U6) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
27.6
Action
"Access"
Scroll to menu H4.
"A"
Scroll to menu U6.
"A"
"Return"
Rev: 3
Show configuration and alarm counter
(H4/U6)
NOTE! ...and alarm counter... is not valid for some conventions,
e.g. the Swedish (SBF) and the Norwegian conventions.
Menu H4/U6 can be used to see the settings (done via Win128).
Alarm counter The alarm counter is increased with "1" every time
the c.i.e. enters the real "alarm condition" (Fire alarm indication in the
display, LEDs "Fire" lit and the c.i.e. buzzer sounding), i.e. not for
zones in test mode. It starts on 000 and goes to 999. It can be reset to
000 via Win512 (Control unit menu "Reset alarm counter..."). It is
stored in an EEPROM, i.e. the value will be retained also after the
c.i.e. has been de-energized.
Language The language for the texts shown in the EBL128 display.
The text / language file (nnnn.sst) is selected and downloaded via the
Win128 menu "Download software / texts to control unit" dialog
86
box.
Convention
Because of country specific functions, etc. different
conventions are used in different countries.
selected the very first time Win128 is opened but can, if required, be
changed in the "Win128 Settings" dialog box).
Text in display
Present system status on display
Disablement
Show configuration and alarm counter
Alarm counter: yyy
Language:nnnnnnnnnn Conv.:cccccccccc
Show configuration and alarm counter
86
In order to present all language specific characters correct, also the
"Control unit language" has to be set to the correct language. This is done in
the "Win128 settings" dialog box.
87
To set (change) the convention in Win128, Level 2 has to be selected and
to do this a password is required.
EBL128 Operating Instructions V1.1.x
ACCEPT? H4
ACCEPT?
ACCEPT?
ACCEPT?
102
The convention is
87
Comments
According to chapter
"Access", see page 78.
U1
Press "A" to accept.
U6
Press "Return" to menu
U6.
Scroll or press "Return"
U6
to menu H4. Scroll or
press "Return" to log off.

Advertisement