A time channel can instead be used to disable and re-enable
automatically.
Disconnect / Re-connect zone line
Disconnect a zone line (on a 4580 board) via menu H5/A2.
Disconnected zone line will stay disconnected until re-connected.
Re-connect via menu H5/A2.
For more information see EBL128 Operating Instructions.
Disable zone / address
Individual alarm points can be disabled via menu H2/B2.
Re-enable via menu H2/B5 or automatic re-enabling at a specified
time.
A time channel can instead be used to disable and re-enable
automatically.
Disable control output
Individual control outputs can be disabled via menu H2/B3. Disabled
output will stay in (or return to) the normal condition for the output
respectively until re-enabled.
Re-enable via menu H2/B6.
Disable / Re-enable all control, exting. and ventilation
outputs
The control outputs of type "Control (general)", "Fire ventilation" and
"Extinguishing system" can be collective disabled via menu H2/B7.
Disabled outputs will stay in (or return to) the normal condition for the
output respectively until re-enabled.
Re-enable via menu H2/B7.
Disable / Re-enable alarm devices
The control outputs of type "Alarm device (sounder)" can be
collective disabled via menu H2/B8. Disabled outputs will stay in (or
return to) the normal condition for the output respectively until re-
enabled.
Re-enable via menu H2/B8.
Disable outputs for routing equipment
The control outputs of type "Routing equipment (Fire brigade tx and
Fault tx)" can be collective disabled via menu H2/B9.
outputs will stay in (or return to) the normal condition for the output
respectively until re-enabled.
Re-enable via menu H2/B9.
Disable interlocking output
The control outputs of type "Interlocking output" can be disabled via
menu H9/C4, see chapter "Disable interlocking output (H9/C4)", page
79.
Re-enable via menu H9/C5.
EBL128 Planning Instructions V1.1.x
97