Perform Monthly Test (H1) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
24
Action
"Access"
"A"
"A"
"A"
Write zone numbers
(e.g. 01, 02, 03, 04)
"A"
Rev: 3

Perform monthly test (H1)

EBL128 and the installation shall be tested on a regular basis. If one
twelfth of the alarm points are tested each month, the whole
installation will be tested after one year. In test mode, only the alarm
points are tested, i.e. no outputs (no sounders) will be activated during
the test. (Alarm devices can be tested via menu H8/S3.)
If a real fire alarm is activated by an alarm point not in test mode,
the normal fire alarm functions will be activated, i.e. fire alarm
presentation, outputs (sounders) activated, routing equipment (fire
brigade tx) activated, etc. but the zone(s) in test mode will remain in
test mode until the test mode is ended. During the fire alarm the
zone(s) in test mode can be displayed via menu X3, see chapter
"Display disablements (X3)", page 44.
See also chapter "The display in EBL128", page 20.
NOTE! If the EBL128 door is left open, the output(s) for routing
equipment (fire brigade tx) might be disabled (if set so in Win128).
There will be an automatic ending of the test mode one hour after the
latest tested alarm point / zone.
See also chapter "Perform ZONE TEST (test mode) (H7)", page 116.
Text in display
Perform monthly test
Check that all LEDs light up!
▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒
▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒
Zone to be set in TEST MODE:
??
??
??
??
Zone to be set in TEST MODE:
01
02
03
04
Zones are set in test mode
wait....
Zone in TEST MODE:
01
02
03
04
EBL128 Operating Instructions V1.1.x
ACCEPT? H1
ACCEPT
Start test:
ACCEPT
Start test:
ACCEPT
End test:
ACCEPT
79
Comments
According to chapter
"Access", see page 78.
The buzzer (in EBL128)
sounds and all dots in the
display are shown. All
LED:s light up, incl.
LED:s in units connected
via I/O Matrix board 4582.
Danish (DBI)
NOTE! In
convention, only one zone.
Press "A" to start the test
mode.
LED "Test mode" (L9)
will light up.
Perform the tests.