Advertisement

Panasonic Eco Solutions Nordic AB
MEW01624 Rev: -
5.2

Disable zone-address (B2)

Not available for users with access level / type "Information only".
Up to 100 addressable alarm points (zone-address) can be individually
disabled via menu B2. Also addressable manual call points.
Log in with a User name and Password for typ Building officer (or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press "2") to menu H2.
H2 Disable or re-enable
Press "A" to sub menu B1.
B1 Disable zone
Scroll (or press "2") to menu B2.
B2 Disable zone-address
Press "A".
Use the keypad to type the zone number (01-99) and the address (01-
99). Press "A".
The alarm point can be automatically re-enabled.
If automatic re-enabling shall not be used press "A". Go to
If automatic re-enabling shall be used, press "1" and use the keypad
to set the time. Press "A".
The alarm point (zone-address) is disabled. Press "A". When
required, disable more alarm points or press "Return" to menu B2.
Scroll to another menu or press "Return" to menu H2. Scroll to
another menu or leave the menu system by pressing "Return".
EBL128 version 2.0.x, Daily user's manual