Re-Enable Zone (H2/B5) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
25.5
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B5.
"A"
"A"
Rev: 3

Re-enable zone (H2/B5)

Disabled zones are listed in menu H4/U1.
Re-enabling via this menu has higher priority than automatic re-
enabling.
Zones disabled via the "Encapsulation function", see chapter "Single
encapsulated reset" page 50, have to be re-enabled via this menu
before they can activate a new alarm.
Zones disabled when the "New Zealand FB Silence switch" (outside
switch) is turned OFF, have to be re-enabled via menu B5 or B6
before they can activate a new alarm.
When all zones have been re-enabled, the LED "Disablements" (L8)
will be turned OFF, if there are no other disablements.
NOTE! Alarm points that have been individually disabled via menu
H2/B2 cannot be collectively re-enabled via this menu. They have to
be individually re-enabled.
Text in display
Disable or re-enable
Disable zone
Re-enable zone
Re-enable zone: 00
Re-enable zone
EBL128 Operating Instructions V1.1.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B5
ACCEPT?
ACCEPT? B5
86
Comments
According to chapter
"Access", see page 78.
If there are no zones to re-
enable, menu B5 will be
L
shown again. L=a list in
which you can scroll.
If it's the correct zone to
re-enable, press "A" to
accept. If not, scroll or
write the wanted zone and
press "A" to accept.
If more re-enablements
shall be done, continue like
above. If not, scroll or
press "Return" to menu
H2. Scroll or press
"Return" to log off.