Panasonic Electric Works Nordic AB
MEW01091
25.10
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B10.
"A"
"A"
Rev: 3
De-activate alert annunciation function
(H2/B10)
Normal function (1):
For alarm points / zones programmed for Alert Annunciation (via
Win128) is normally the AA function enabled via a time channel, e.g.
enabled daytime (during working hours) and disabled night time.
As an alternative, the AA function can be continuously enabled.
Off (0)
Via this menu (H2/B10) it is possible to de-activate (disable) the AA
function, i.e. the AA function will be disabled for the alarm points /
zones programmed for Alert Annunciation in spite of the time channel
is "on" or if they are programmed to be continuously enabled.
The AA function will stay de-activated (disabled) until re-activated
(re-enabled) again via this menu.
Text in display
Disable or re-enable
Disable zone
De-activate alert annunciation function
Alert annunciation function? 1
(1 = Normal, 0 = Off)
De-activate alert annunciation function
NOTE! De-activated Alert Annunciation function is not indicated by
LED "Disablements" (L8).
EBL128 Operating Instructions V1.1.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B10
ACCEPT?
ACCEPT? B10
92
Comments
According to chapter
"Access", see page 78.
Write "0" or "1" and press
"A" to accept.
Scroll or press "Return" to
menu H2. Scroll or press
"Return" to log off.