11. PERFORM ZONE TEST (H7)

Up to 100 zones can be set in test mode, which is indicated by the LED "Test mode" on the front. After one hour without any testing
activity, the test mode will be automatically ended. Valid for each zone respectively.
When an alarm point in a zone, set in test mode, is tested, it is presented in the display as a fire alarm, but with the information "Test
mode" added. If a printer is available the test mode alarm will be printed with the information "(test mode)" added.
No outputs will be activated except the fire door outputs. The test mode alarm will be automatically reset after approximately 10
seconds.
a) Log on to the c.i.e.
b) Navigate to menu H7.
c) Press
.
d) Use the keypad to type a zone number.
e) Press
.
Putting the zone into test mode is indicated by a beep and a "√". It will also be shown in the
"End test mode" list.
A not successful zone in test mode is indicated by another beep and a "X".
END TEST MODE
a) Press soft key
b) Scroll with
and
c) Press
to select. When ending the test mode for a zone, it is indicated by a beep and it will also disappear from the "End
test mode" list.
to toggle between: "Set in test mode" and "End test mode".
.
14