Omron VARISPEED G7 Instruction Manual page 273

Hide thumbs Also See for VARISPEED G7:
Table of Contents

Advertisement

Adjusting the Analog Monitor Items
Adjust the output voltage for multi-function analog output terminals FM-AC and AM-AC using the gain and
bias in H4-02, H4-03, H4-05, and H4-06. Also, adjust the output voltage for output channels 1 and 2 of Ana-
log Output Option Cards AO-08 and AO-12 using the gain and bias in F4-02, F4-04, and F4-06.
Adjusting the Meter
Display the data setting display for the gain and bias constants corresponding to the output channel of the
Inverter Unit and the AO Option Card while the Inverter is stopped to output the following voltages to the ana-
log monitor terminal, to enable meter adjusting while the Inverter is stopped.
Switching Analog Monitor Signal Levels
Monitor items corresponding to 0 to ±10 V output 0 to 10 V signals when the monitor value is positive (+),
and 0 to -10 V signals when the monitor value is negative (-). For monitor items corresponding to 0 to ±10 V,
refer to Chapter 5 User Constants.
INFO
-78
6
10 V/100% monitor output × output gain + output bias
Output voltage
Gain x 10 V
Fig 6.53 Monitor Output Adjustment
You can select the signal levels separately for multi-function analog output terminals and analog output option
terminals.
Bias x 10/100 V
Monitor item