Copying Constants

The Digital Operator can perform the following three functions using the built-in EEPROM (non-volatile
memory).
Store Inverter constant set values in the Digital Operator (READ)
Write constant set values stored in the Digital Operator to the Inverter (COPY)
Compare constant set values stored in the Digital Operator with Inverter constants (VERIFY)
Related Constants
Name
Con-
stant
Display
Number
Copy function
0: Normal operation
selection
1: READ (Inverter to Operator)
o3-01
2: COPY (Operator to Inverter)
Copy Function
3: Verify (compare)
Sel
Read permitted
selection
0: Read prohibited
o3-02
1: Read permitted
Copy Allow-
able
Setting
Description
Range
0 to 3
0 or 1
Digital Operator Functions
Control Methods
Change
Factory
during
V/f
Setting
Opera-
V/f
with
tion
PG
0
No
A
A
0
No
A
A
Open
Open
Flux
Loop
Loop
Vec-
Vector
Vector
tor
1
2
A
A
A
A
A
A