Omron VARISPEED G7 Instruction Manual page 237

Hide thumbs Also See for VARISPEED G7:
Table of Contents

Advertisement

Set the Torque Limit Value Using an Analog Input
You can change the analog input level torque limit value by setting the torque limit in multi-function analog
input terminals A2 and A3.
The analog input terminal signal level is factory-set as follows:
Multi-function analog input terminal A2: 4 to 20 mA
Multi-function analog input terminal A3: 0 to 10
The following diagram shows the relationship between the torque limits.
Setting Torque Limits Using Constants and an Analog Input
The following block diagram shows the relationship between torque limit using constants and torque limit
using an analog input.
Multi-function analog input
Forward torque limit
Terminal
(set value = 10)
A2 or A3
Negative torque limit
(set value = 11)
Regenerative
(set value = 12)
Positive/negative torque limit
(set value = 15)
Forward torque limit
(L7-01)
Reverse torque limit
(L7-02)
Constants
Forward regenerative torque
limit (L7-03)
Reverse regenerative torque
limit (L7-04)
-42
6
Regenerative torque limit
Reverse operation
Negative torque limit
Fig 6.35 Torque Limit by Analog Input
Positive forward drive
torque
torque
limit
Fig 6.36 Torque Limit Using Constants and an Analog Input
Output torque
Positive
Negative
Reverse positive regenerative torque
Forward negative regenerative torque
Reverse
drive
reverse
torque
175% of Inverter rated current
Positive/negative torque limits
Forward torque limit
No. of motor rotations
Forward operation
Regenerative torque limit
Positive/negative torque limits
Min: Minimum value priority circuit
Forward torque limit
Reverse torque limit
Forward regenerative
torque limit
Reverse regenerative
torque limit