The zero-servo function is enabled when one of the multi-function inputs (H1-01 to H1-10) is set to 72 (zero
servo command). If the zero servo command is ON when the frequency (speed) reference falls below the zero
speed level, a zero-servo status is implemented.
Related Constants
Name
Con-
stant
Display
Number
Zero speed
Used to set the frequency which
level (DC injec-
starts DC injection braking in
tion braking
units of Hz when deceleration to
starting fre-
stop is selected.
b2-01
quency)
When b2-01 is less than E1-09,
E1-09 becomes the DC injection
braking starting frequency.
DCInj Start
(For flux vector control, zero-
Freq
speed control from B2-01)
Zero-servo gain Adjust the strength of the zero-
servo lock.
Enabled when the zero-servo
command is set for a multi-func-
tion input. When the zero-servo
command has been input and the
frequency reference drop below
b9-01
Zero Servo
excitation level (b2-01), a posi-
Gain
tion control loop is created and
the motor stops. Increasing the
zero-servo gain in turn increases
the strength of the lock. Increas-
ing it by too much will cause
oscillation.
Zero-servo
Sets the output width of the P-
completion
lock completion signal.
width
Enabled when the "zero-servo
completion (end)" is set for a
multi-function input. The zero-
servo completion signal is ON
when the current position is
b9-02
within the range (the zero-servo
position + zero-servo completion
Zero Servo
width.)
Count
Set the allowable position dis-
placement from the zero-servo
position to 4 times the pulse rate
of the PG (pulse generator,
encoder) in use.
Multi-function Contact Input Functions (H1-01 to H1-10)
Set-
ting
Value
72
Zero-servo command (ON: Zero-servo)
Setting
Description
Range
0.0 to
10.0
0 to 100
0 to
16383
Function
Individual Functions
Control Methods
Change
Factory
during
V/f
Setting
Opera-
V/f
with
tion
PG
0.5 Hz
No
A
A
5
No
No
No
10
No
No
No
Control Methods
V/f
V/f
with
PG
No
No
Open
Open
Flux
Loop
Loop
Vec-
Vector
Vector
tor
1
2
A
A
A
No
A
No
No
A
No
Open
Open
Loop
Flux
Loop
Vec-
Vec-
Vec-
tor
tor
tor
1
2
No
Yes
No
129
6-

Hide quick links: