Omron DEVICENET SAFETY - CONFIGURATION MANUAL 05-2005 System Configuration Manual page 76

Devicenet safety system
Table of Contents

Advertisement

Item
S Dual Channel Safety
Input Mode
S Dual Channel Safety In-
put Discrepancy Time
I/O Comment
Maintenance Counter
Mode Choice
Threshold Maintenance
Counter
IMPORTANT:
74
Settings
Single Channel
Dual Channel Equiva-
lent
Dual Channel Comple-
mentary
0 to 65,530 ms
(in 10-ms increments)
32 characters max.
Time
Count
0 to 4,294,967,295
hours
When the Safety Input Channel Mode is set to Test Pulse from Test Out, specify the test
output to use for the test source and set the Test Output Channel Mode of the test output
to Pulse Test Output.
Description
Specifies using Single Channel Mode.
If Single Channel is selected, the safe-
ty input that would be paired for the
dual channel parameter will also be set
to Single Channel Mode.
Specifies using the Dual Channel
Equivalent Mode with a paired safety
input.
Specifies using Dual Channel Comple-
mentary Mode with a paired safety in-
put.
Sets the time to monitor the logic
discrepancy in the dual channel input
logic.
Sets an I/O comment for the safety in-
put. The I/O comment set here is used
as the I/O tag in the Logic Editor.
Sets the operating mode for the main-
tenance counter.
Sets the threshold value for the main-
tenance counter.
Section 4: Editing Safety I/O Terminal Parameters
Default
Dual Chan-
nel Equiva-
lent
0 ms
None
Time
0