Specifying the SYSMAC CS/CJ Interface Port as the Connection Interface
(Continued from step 3 on the previous page.)
1.
When SYSMAC CS/CJ I/F Port is selected as the connection interface, the Setup Interface Window will
be displayed. An example is shown below.
Set each item as described below.
Interface
Network Address
Node Address
CPU Bus Unit Number Enter the unit number of the DeviceNet Unit (i.e., the CS1W-DRM21(-V1)) as a
Communications Port
Baud Rate
Data Length
Parity
Stop Bits
IMPORTANT:
A-2 Specifying the Connection Interface
Select either one of the following interfaces as the serial communications mode
for the serial communications port on the CS/CJ-series PLC.
Peripheral bus (ToolBus)
Host Link
Enter the FINS network address of the destination DeviceNet Unit. Enter this
address when crossing the network farther than the serial communications port
of the CS/CJ-series CPU Unit. Enter 0 when not crossing network layers.
Enter this address when crossing the network farther than the serial communi-
cations port of the CS/CJ-series CPU Unit. Enter 0 when not crossing network
layers.
CPU Bus Unit (i.e., the value set on the rotary switches on the front of the De-
viceNet Unit).
The unit number is between 0 and 15.
Select the COM port on the computer running the Network Configurator (Ver.2).
Select from the list of available COM ports.
Set the baud rate for the serial communications port on the CS/CJ-series PLC.
9,600, 19,200, 38,400, or 115,200 bit/s.
The baud rates that can be selected for the peripheral bus (ToolBus) and Host
Link are different. For details, refer to the CS/CJ Series Operation Manual.
Set the data length for the serial communications port on the CS/CJ-series PLC.
This setting is required only when using the Host Link interface.
o 7 or 8 bits
Set the parity for the serial communications port on the CS/CJ-series PLC. This
setting is required only when using the Host Link interface.
o None, even, or odd
Set the number of stop bits for the serial communications port on the CS/CJ-
series PLC. This setting is required only when using the Host Link interface.
o 1 or 2 bits
Always select the peripheral bus (ToolBus) interface when making a serial connection
through the CS1W-CN226/626 or the XW2Z-200S-CV/500S-CV Connecting Cable to a
CS-series PLC with the CS1W-DRM21(-V1) mounted to the CPU Rack. A connection will
not be possible if the Host Link interface is selected.