– If downloading to a device with a key icon color that has changed to yellow because of parameter
changes, the icon must be returned to the state before verification (white [ S ] symbol).
– If downloading to a device with a key icon color that has not changed because parameters have not
been changed, the icon must be returned to the state indicating that verification has been completed
(green [ S ] symbol).
Additional User Testing
22. User Testing
The user himself must verify device parameters and operation to confirm that the safety system require-
ment specifications are met.
23. Starting the Network Configurator and Connecting to the Network
Start the Network Configurator and connect it to the network via the USB port on the NE1A-SCPU01 or
a DeviceNet Interface Card.
Refer to 2-3 Connecting to the Network (page 32).
24. Reading the Network Configuration File
Read the saved network configuration file with verified parameters.
Refer to 2-5-3 Reading a Network Configuration File (page 39).
25. Configuration Lock
Lock the configuration of all the devices to indicate that they have been verified as well as to prevent
parameters from being mistakenly rewritten.
Refer to 2-9-1 Locking the Device Configuration (page 48).
26. Saving the Network Configuration File
Save the file of a virtual network with a locked configuration.
Refer to 2-5-2 Saving the Network Configuration File (page 38).
27. Exiting the Network Configurator
Exit the Network Configurator.
Safety functions may be impaired and serious injury may occasionally occur. Before operat-
ing the system, perform user testing to confirm that the configuration data of all the devices
is correct and that they are operating correctly.
IMPORTANT: • After configuring all the devices, user testing must be performed to confirm that the config-
Restarting the System
28. Running the System
Run the system.
58
uration data and operation of each device are correct. User testing is performed to verify
the safety signature for each device.
• The configuration must be locked after user testing has been completed.