Omron DEVICENET SAFETY - CONFIGURATION MANUAL 05-2005 System Configuration Manual page 143

Devicenet safety system
Table of Contents

Advertisement

For the network address, set the same value as the Ethernet Unit. The network address of the Ethernet
Unit is set in the routing table of the CPU Unit. Enter 0 when not using the routing table.
Setting the Node Address in the Host (PC) Information Area
Set the FINS node address of the computer.
For this setting, it is necessary to set the correspondence between the remote IP address and the FINS
node address using the OMRON Ethernet Unit. For details, refer to the SYSMAC CS/CJ Series Ether-
net Unit Operation Manual (W420, W421 and W343).
Setting the Network Address in the DeviceNet Unit Field of the Remote Information Area
Set the FINS network address of the DeviceNet Unit to which the destination DeviceNet network is con-
nected.
Enter the value when crossing the network farther than the Ethernet network directly connected to the
computer. Enter 0 when not crossing network layers.
Setting the Node Address in the DeviceNet Unit Field of the Remote Information Area
Set the Node Address of the DeviceNet Unit to which the destination DeviceNet network is connected.
Enter the value when crossing the network farther than the Ethernet directly connected to the computer.
Enter 0 when not crossing network layers.
Setting the CPU Bus Unit Number in the DeviceNet Unit Field of the Remote Information Area
Set the unit number (0 to F) of the DeviceNet Unit as a CPU Bus Unit to which the destination
DeviceNet network is connected.
Setting the Port Number in the Ethernet Unit Field of the Remote Information Area
Set the UDP port number with which the Ethernet Unit performs the FINS Communications Service. Set
the same value as in the setting in the CPU Bus Unit System Setting Area in the CPU Unit to which the
Ethernet Unit is mounted. Normally 9600 is used.
Setting the IP Address in the Ethernet Unit Field of the Remote Information Area
Set the IP address of the Ethernet Unit.
To set the IP address of the Ethernet Unit, refer to SYSMAC CS/CJ Series Ethernet Unit Operation
Manual (W420, W421 and W343).
4.
Click the Register Button. The set values will be registered and displayed in the Registration List.
• Name: Registration name of the destination DeviceNet network
• Node: FINS network address and FINS node address (the third number is always 0) of the computer
• Unit: FINS network address, FINS node address, and unit number of the DeviceNet Unit
• Port: FINS UDP port number of the Ethernet Unit
• IP Address: IP address of the Ethernet Unit
5.
Click the Close Button to exit and return to the Setup Interface Window.
Selecting the Registration Name (Destination DeviceNet Network)
Select the DeviceNet network that you want to connect from the registration names of the registered connec-
tion destinations in the Setup Interface Window.
1.
Select the destination registration name from the Registration Name Drop-down List in the Remote In-
formation Area.
In the Remote Information Area, the following set values of the selected registration name will be dis-
played.
• Network Address: FINS network address of the DeviceNet Unit
• Node Address: Node address of the DeviceNet Unit
• CPU Bus Unit Number: Unit number of the DeviceNet Unit
• Port Number: FINS UDP port number of the Ethernet Unit
• IP Address: IP address of the Ethernet Unit
2.
Click the OK Button.
Click the OK Button in the confirmation dialog box.
The connection to the DeviceNet network will be made.
When the connection is successful, the status indicator on the status bar will turn blue and "On-line" will
be displayed.
Note: For information on FINS network addresses and FINS node addresses, refer to the CS/CJ Series De-
viceNet Unit Operation Manual (W380) and the SYSMAC CS/CJ Series Ethernet Unit Operation Man-
ual (W420, W421 and W343).
A-2 Specifying the Connection Interface