Omron DEVICENET SAFETY - SYSTEM CONFIGURATION 07-2009 System Configuration Manual

Table of Contents

Advertisement

Quick Links

Cat. No. Z905-E1-07
DeviceNet Safety
SYSTEM CONFIGURATION MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Omron DEVICENET SAFETY - SYSTEM CONFIGURATION 07-2009

  • Page 1 Cat. No. Z905-E1-07 DeviceNet Safety SYSTEM CONFIGURATION MANUAL...
  • Page 5 DeviceNet Safety System Configuration Manual Revised July 2009...
  • Page 7 Indicates general mandatory actions for which there is no specific symbol. OMRON Product References All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
  • Page 8  OMRON, 2005 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
  • Page 9: Table Of Contents

    Overview ........
  • Page 10 Monitoring Functions ............Maintenance Functions (Unit Version 1.0 or Later) .......
  • Page 11 Index..........335 Revision History ........339...
  • Page 13 Obtain this manual and gain a firm understanding of its contents before using a DeviceNet system.
  • Page 15 WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS...
  • Page 16 The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: •...
  • Page 17 PERFORMANCE DATA Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements.
  • Page 19: Precautions

    Precautions for Safe Use ........
  • Page 20: Intended Audience

    This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this man- ual close at hand for reference during operation.
  • Page 21 • Moving or Transferring Devices or Equipment When moving or transferring devices or equipment, be sure to include this Manual to ensure that the person to whom the device or equipment is be- ing moved or transferred will be able to operate the system properly.
  • Page 22: Safety Precautions

    Safety functions may be impaired and serious injury may occasionally occur. Wire the output lines and 24-VDC line so that they will not touch each other to prevent a load from turning ON due to a short-circuit with the 24-VDC line.
  • Page 23: Precautions For Safe Use

    Precautions for Safe Use ■ Handling Do not drop the products or subject them to excessive vibration or impact. Doing so may result in error or malfunction. ■ Installation and Storage Do not install or store the products in the following locations: •...
  • Page 24 Precautions for Safe Use • Be careful not to get your fingers caught when attaching connectors to the plugs on the products. • Tighten the DeviceNet connector to the appropriate torque (0.25 to 0.3 N·m). • Incorrect wiring may reduce safety functions. Perform all wiring correctly and check operation prior to using the products.
  • Page 25 Network Configurator Version Upgrade Upgrade from Version 1.6@ to Version 2.2@ The WS02-CFSC1-E Network Configurator has been upgraded from version to 2.2@. The following changes have been made in line with the upgrade. Item Ver. 1.6@ Ver. 2.00 Ver. 2.01 Ver.
  • Page 26 NE1A-series Controller unit versions and the revisions. Checking the Unit The unit version (Ver. @.@) is listed near the lot number on the nameplate of Version on the Product the products for which unit versions are being managed, as shown below.
  • Page 27 2. Right-click on the Controller's icon to display the popup menu shown be- low. Select Property from the menu. The Controller's Property Window will be displayed. The Controller's model number (device name) and revision are displayed in the Property Window. The NE1A-series Controllers supported by Net-...
  • Page 28 Checking the Unit Version on the Product Nameplate The following unit version labels are provided with the Controller. These labels can be attached to the front of the Controllers to differentiate between Controllers with different unit versions from the front of the Controller.
  • Page 29 • RS Flip-flop • Multi Connector • Muting • Enable Switch • Pulse Generator • Counter • Comparator Selection of the rising edge of the reset Supported Supported Supported Supported condition for the Reset and Restart Function Blocks Use local I/O status in logic program-...
  • Page 30 Cannot be used. Cannot be used. Cannot be used. Can be used. Note Can be used as a Safety Logic Controller with unit version 1.0. Note (1) Network Configurator version 1.5@ or lower can be upgraded to version 1.6@ free of charge.
  • Page 31 Functions are added and functionality is expanded in various ways for the NE1A-series Controllers. The device type in an existing network configuration file can be changed to a higher version so that the new functionality can be used. The following table shows the NE1A-series Control device types in network configuration files and the device types that they can be upgraded to.
  • Page 32 Select the device to which the data is to be converted in the New Device Field and click the OK Button. The data will be converted to configuration data for the new devices and the model given on the display will change.
  • Page 33 I/O tags. Note Versions 1.5@ and higher have functions for creating text boxes on program screens and changing the I/O tag color. The text box and I/O color data is not xxxi...
  • Page 34 NE1A-series Controller, however, during download. For this rea- son, text box and I/O tag color data is not restored when the program is uploaded. xxxii...
  • Page 35: Overview

    Standard Models ........Basic System Startup Procedure ........
  • Page 36: Devicenet Safety System Overview

    About DeviceNet Safety DeviceNet is an open-field, multi-vendor, multi-bit network, which combines the controls in the machine and line control levels with information. The DeviceNet Safety network adds safety functions to the conventional standard DeviceNet communications protocol. The DeviceNet Safety concept has been approved by a third-party organization (TÜV Rhineland).
  • Page 37: Safety Network Controller Overview

    • As a Safety Logic Controller, the NE1A-series Controller executes safety logic operations and controls local I/O. • As a Safety Master, the NE1A-series Controller controls the remote I/O of Safety Slaves. • As a Standard Slave, the NE1A-series Controller communicates with the Standard Master.
  • Page 38: Ne1A Series Features

    Previously prepared logic functions and function blocks can be combined to create a user-defined function block using the Network Configurator version 1.5@ or higher. This can be used to standardize functions that are used fre- quently to facilitate reusing them. Passwords can also be used to protect the programming inside the function blocks by making them “black boxes.”...
  • Page 39: Standard Models

    DeviceNet, USB, or EtherNet/IP. System Startup and Error Recovery Support • Error information can be checked by using the error history or the indica- tors on the front of the NE1A-series Controller. • The NE1A-series Controller’s internal status information can be moni- tored from a standard PLC by allocating the information in the Standard Master.
  • Page 40: Network Configurator Overview

    AND/OR and other logic functions and emergency stop button/safety door/light curtain monitoring, and other previously prepared function blocks can be selected from the function block list and placed in the Work- space to create software connections in the logic of the Network Control-...
  • Page 41: System Requirements

    Network Configurator version 1.5@ or higher. New user-defined function blocks can be created. These can be used simply by selecting them from the function block list and placing them in the Workspace. Created user-defined function blocks can be saved to file and installed on another computer to use with the Network Configurator on that computer.
  • Page 42: Basic System Startup Procedure

    2. Configure the network system as a virtual network in the Network Config- urator. • Register all of the devices. If the system is a mixed safety control and standard control system, register both the safety devices and standard devices.
  • Page 43: Installation And Wiring

    Refer to 2-2 Allocating Network Bandwidth Usage and Calculating the Best EPI. • Calculating the Reaction Time Refer to 2-3 Calculating and Verifying the Reaction Time. IMPORTANT Allocate a unique safety network number to each safety network or safety subnetwork. 1-4-2 Installation and Wiring In this step, install and wire each device as shown below: •...
  • Page 44: Configuration

    • When selecting Open Only in the Open Type setting for the safety con- nection, check that the Safety Master and Safety Slave are correctly con- figured.
  • Page 45: Constructing A Safety Network

    Allocating Network Bandwidth Usage Rates and Calculating Best EPI........
  • Page 46: Applications

    Refer to 3-1-1 Starting and Exiting the Network Configurator. 2. Creating the Virtual Network Create the virtual network by adding a device from the Hardware List. If the user is to specify the network number, set the network number as well.
  • Page 47 • When selecting Open Only in the Open Type setting for the safety con- nection, check that the Safety Master and Safety Slave are correctly con- figured.
  • Page 48 Refer to 3-5-3 Reading a Network Configuration File. 18. Configuration Lock Lock the configuration of all the devices to indicate that they have been ver- ified as well as to prevent parameters from being mistakenly rewritten. Refer to 3-9-1 Locking the Device Configuration.
  • Page 49: Changing An Established Safety Network

    5. Resetting a Device Before changing device parameters and node address, clear the configu- ration of the device. Reset the device by setting the reset type to Return to the out-of-box configuration, and then emulate cycling power. Refer to 3-10-2 Resetting Devices.
  • Page 50 • Allocate a unique network number when establishing a network or sub- network. • If the parameters of a Safety Slave or Standard Slave are changed, the parameter information will not match in the Safety Master or Standard Master in which the Slave is registered. Therefore, a yellow [ ! ] symbol will be displayed next to the slave icon.
  • Page 51 Therefore, the parameters can be downloaded. • If downloading to a device with a key icon color that has changed to yel- low because of parameter changes, the icon must be returned to the state before verification (white [ S ] symbol).
  • Page 52 Refer to 3-5-3 Reading a Network Configuration File. 25. Configuration Lock Lock the configuration of all the devices to indicate that they have been ver- ified as well as to prevent parameters from being mistakenly rewritten. Refer to 3-9-1 Locking the Device Configuration.
  • Page 53: Allocating Network Bandwidth Usage And Calculating The Best Epi

    I/O communications. Even if 10% or more is available, however, safety or standard communications might time out, depending on the Network Configurator operation (e.g., moni- toring or other operations that create a load on the network) or if the user...
  • Page 54: Displaying Device Bandwidth Usage Conditions

    Refer to 2-2-3 Allocating Network Bandwidth Usage Rates and Calculating Best EPI and enter the network bandwidth used for each type of communica- tions and set the best average EPI for each safety connection and the com- munications cycle time of the Standard Master.
  • Page 55: Allocating Network Bandwidth Usage Rates And Calculating Best Epi

    Number of bits presently processed per seconds by the Ethernet port for a device. Usage of IP multicast addresses Number of multicast addresses used. Set Packet Interval (RPI) Button This button is not used for DeviceNet Safety-Ether- Net/IP systems. Close Button Closes the Usage of Device Bandwidth Dialog Box.
  • Page 56 Safety Network Controller cycle time. If they are shorter, the Safe- ty Network Controller cycle time will be the minimum that can be set for the EPI. The Safety Network Controller cycle time can be checked offline after creating the program, under Cycle Time on the Mode/Cycle Time Tab in the Edit Device Parameters Dialog Box.
  • Page 57 IMPORTANT The minimum possible EPI setting is larger value of either the Safety Network Controller cycle time or the Safety Slave cycle time (fixed at 6 ms). The mini- mum possible EPI will be affected, therefore, if the Safety Network Controller cycle time is longer than 6 ms.
  • Page 58 (e.g., for door switches not used in hazardous areas). Refer to the reaction time listed in the EPI field to check what the reac- tion time will be for each safety connection EPI setting.
  • Page 59: Example Of Epi Calculations

    Example: The CJ1W-DRM21 sets the standard connections between six DRT2-ID16 Input Terminals and five DRT2-OD16 Output Terminals. The default set values are used, and the communications cycle of the CJ1W- DRM21 is automatically set but it attempts to operate at a cycle time of about 3.2 ms.
  • Page 60 Checking the Safety Network Controller Cycle Time If, for example, the Safety Network Controller cycle time was 6 ms, it is shorter than the calculation result of 7 ms which means the result can be set as the EPI. Changing Settings...
  • Page 61 Section 2-2 Click the Update Device Configuration Button to batch set the calculation result of 7 ms as the EPI for all safety connections by selecting the baud rate to be used. Refer to 2-2-3 Allocating Network Bandwidth Usage Rates and Calculating Best EPI.
  • Page 62: Calculating And Verifying The Reaction Time

    4. Remote Input – Remote Output Safety DST1-series Network Network DST1-series NE1A-SCPU01 Actuator sensor/switch I/O Terminal I/O Terminal Note Even if a fault or failure occurs in a safety chain, the output shutoff time is ensured as the maximum reaction time.
  • Page 63: Calculating The Maximum Reaction Time

    Section 2-3 Calculating and Verifying the Reaction Time 2-3-2 Calculating the Maximum Reaction Time Reaction Time Components Reaction time components are displayed for each safety chain. 1. Standalone NE1A-series Controller (DeviceNet Communications Dis- abled) NE1A-SCPU01 Safety Actuator sensor/switch Local input/local...
  • Page 64 Network reaction time (ms) Use the Network Configurator calculation result. IMPORTANT In the SNC program, add the time for the NE1A-series Controller cycle time to the reaction time of the safety chain when the output from a function block is fed back to the input side of the function block.
  • Page 65 Section 2-3 Calculating and Verifying the Reaction Time Check the network reaction time in the Safety Connection Tab of the Edit Device Parameters Window.
  • Page 66 + NE1A-series Controller remote input/local output reaction time + Actuator reaction time = Switch reaction time + ON/OFF delay (DST1-series I/O Terminal) + 16.2 + 24 6 + 2.5 + Actuator reaction time = 48.7 + ON/OFF delay + Switch reaction time + Actuator reaction time...
  • Page 67: Verifying The Maximum Reaction Time

    • The NE1A-series Controller cycle time is automatically calculated based on the program size, the number of connections, etc. It is also possible to use different NE1A-series Controller Controllers for safety chains that require a high-speed reaction time and other safety chains.
  • Page 69: Basic Operation Of The Network Configurator

    Network Numbers........
  • Page 70 Device Properties ........
  • Page 71: Network Configurator Startup And Main Window

    Select Program -OMRON Network Configurator for DeviceNet Safety - Network Configurator from the Windows Start Menu (when using the default program folder name). The Network Configurator will start, and the following window will be dis- played. Exiting Select File -Exit in the Main Window.
  • Page 72: Checking The Version

    The procedure to check the Network Configurator version is as follows: Windows XP or Windows 2000 1. For Windows XP, select Control Panel - Add or Remove Programs from the Windows Start Menu. For Windows 2000, select Setting - Control Panel - Add/Remove Pro- grams from the Windows Start Menu.
  • Page 73: Main Window

    Section 3-1 Network Configurator Startup and Main Window 3-1-3 Main Window The Main Window consists of the Hardware List, the Network Configuration Pane, Maintenance Pane, and the Message Pane. Network Configuration Pane: Hardware List: Displays virtual networks. Displays the devices that can be added to the network.
  • Page 74: Menu List

    This section describes the function of each menu command of the Network Configurator. “Online” is the state in which the Network Configurator is connected to the network. “Offline” is the state in which the Network Configurator is discon- nected from the network.
  • Page 75: Network Menu

    Refer to 3-2-10 Main Window Display Modes. Open All Devices Displays all of the devices set for communications with the device that the configuration is based on. This function can be used only in Detailed Display Mode 1 or 2. Close All Devices Hides all of the devices set for communications with the device that the configuration is based on.
  • Page 76: Device Menu

    Displays the routing network if a device that supports routing is selected (NE1A-SCPU01-EIP, NE1A-SCPU02-EIP, or NE1A- EDR01). Property Displays the properties of a device. Note The Device Menu and Edit Menu can be partially displayed by right-clicking in the Network Configuration Pane.
  • Page 77: Eds File Menu

    Add to Network Adds a device on the Hardware List to the virtual network. O Property Displays the properties of an EDS file. Note The EDS File Menu can be displayed by right-clicking in the Hardware List Window. 3-2-7 Tools Menu Submenu...
  • Page 78: Help Menu

    Displays the version information of the Network Configura- tor. 3-2-10 Main Window Display Modes The Main Window display can be changed. Any of the following display modes can be selected: Communications Mode, Maintenance Mode, Detailed Dis- play 1, Detailed Display 2, Network Configuration Window, or Device’s Con- nection Structure Tree.
  • Page 79 Menu List In this mode, in addition to the information displayed in Communications Mode, the devices required for maintenance can be checked at a glance and device status can be displayed at the same time. Detailed Display 1 (Based on Master Devices)
  • Page 80 Closes items displayed in trees and displays only the top net- work. Note An exclamation mark [!] may be displayed below the device icon on the Net- work Configurator. This indicates that the information in the Slave and the information in the Master do not match.
  • Page 81 “R” indicates the number of communications resources required by each device. “F” indicates the number of communications required by each device. Users do not normally need to be aware of the these values because they are calculated automatically by the Network Configurator.
  • Page 82: Connecting To The Network

    3. Select Network - Connect from the menu bar. The Select Connect Network Port Dialog Box will be displayed. When connecting to a network for the first time, this dialog box will be dis- played and a network search will be performed automatically. Wait until the search has been performed for all addresses.
  • Page 83: Network Connection Via Devicenet Interface Card

    DeviceNet PCMCIA Card (3G8E2-DRM21-V1) is used. If you use another interface card, refer to the operation manual for the card. 4. Set the MAC ID (node address) and baud rate, and click the OK Button. The Select Connect Network Port Dialog Box will be displayed.
  • Page 84: Network Connection Via Ethernet

    Connecting to the Network In the first network connection, a network search is performed automatical- ly with this dialog box displayed. Wait until the search has been performed for all addresses. After the search, the networks that can be connected will be displayed.
  • Page 85: Connecting To A Network

    5. Select the network to be connected, and then click the OK Button. If an on- line connection is made normally, On-line will be displayed in the status bar at the bottom of the window. A tab for the network to be connected will be displayed in blue as in the fol- lowing figure. 3-3-4...
  • Page 86: Changing A Connected Network

    When the Network Configurator is connected to the network, a blue icon will be displayed on the tab of a destination network, and a green icon will be dis- played on the tab of an operable network, as in the following figure.
  • Page 87 If an online connection is made normally, On-line will be displayed in the status bar at the bottom of the window. A tab for the network to be connected will be displayed in blue as in the following figure. Note Until Select Connect Network Port is used again to change the con-...
  • Page 88: Creating A Virtual Network

    Note When a new virtual network is created with unit version 1.6@ or higher, the vir- tual network information that was displayed until then will be deleted. If the previous virtual network information is required, save the data before creating a new virtual network.
  • Page 89 Then download parameters using that master file. When connecting a new device to the network, use method 4 and reset the device to initial status before downloading.
  • Page 90 If the network number is set by the user, click the Get from the actual net- work Button in the Network Number Field on the Network Property Dialog Box to check the network number set for the target actual network.
  • Page 91: Adding Devices

    3. Select EDS File – Add to Network from the menu. Adding Devices from the Hardware List There are two ways to add a device to the virtual network from the Hardware List. 1. Double-click the selected device in the Hardware List.
  • Page 92 The network configuration can be read from the actual network and to create the same configuration in the virtual network. Connect the Network Configura- tor to the network, and then upload the network configuration using any of the following methods.
  • Page 93 NE1A-SCPU01-EIP, NE1A-SCPU02-EIP, or NE1A- EDR01 in the network. • The following dialog box will be displayed if the Yes Button is clicked here. • Uploading for the target network will start if the Yes Button is clicked here.
  • Page 94 1. Open the project file from which the configuration information is to be re- used. 2. Select File - Save As from the menu bar. The following dialog box will be displayed. 3. A Select target network Check Box will be displayed in the Option Area. If this check box is not selected, the configuration information for all networks will be saved.
  • Page 95 Section 3-4 Creating a Virtual Network 1,2,3... 1. Select File - Open from the menu bar. The Open Dialog Box will be dis- played. (You can also select project files saved from the previous version of the Network Configurator.) 2. Two check boxes will be displayed in the Option Area: Select target net- work and Add to current network.
  • Page 96: Deleting Devices

    Delete Button to delete the device. 3-4-5 Changing the Node Address or IP Address When a device is added from the Device List, an unused node address or IP address is automatically allocated sequentially in the order the device is added.
  • Page 97: Creating A Connected Network From A Device

    Creating a Connected Network from a Device When the NE1A-SCPU01-EIP, NE1A-SCPU02-EIP, or NE1A-EDR01 is regis- tered, either of the following methods can be used to create a new virtual net- work. 1. Select the device, and then select Device - Register to Routing Network from the menu.
  • Page 98 Section 3-4 Creating a Virtual Network A new connected network will be created as shown below.
  • Page 99: Saving And Reading Network Configuration Files

    Saving and Reading Network Configuration Files The created network configuration of the virtual network can be saved in a file. Also, you can open the saved file, modify it, or download it to the devices by connecting to the network.
  • Page 100: Saving The Network Configuration File

    Either way, the standard Windows dialog box for saving will be displayed. Select the saving location, name the file, and then click the Save Button. When saving the file for the first time, the Assign Password Dialog Box will be displayed. Enter the password to set for the network configuration file.
  • Page 101: Protect Mode

    If the password does not match when opening the network configuration file, the Network Configurator will open the file in Protect Mode. If the password does not match, the following message will be displayed in a dialog box and the Message Pane.
  • Page 102: Device Password Protection

    A password can contain from 6 to 16 alphanumeric characters. Device passwords are not stored in the Network Configuration File. There is no password in the default settings. If the device is reset by setting the Reset Type to Return to the out-of-box configuration, and then emulate cycling power, it will return to the no-password setting.
  • Page 103: Forgotten Device Passwords

    If you set the same password for multiple devices and perform an operation that requires entering a password, entering the password once can be treated as entering the password for all the devices. Select the Use this password for all device check box in the Password Input Dialog Box.
  • Page 104: Device Parameters And Properties

    Device parameters can be edited using any of the following methods. 1. Double-click a device icon. 2. Select a device, and then select Device - Parameter - Edit from the menu bar. 3. Select a device, and then click the Edit Parameter Button on the toolbar.
  • Page 105: Downloading Device Parameters

    Device Parameters and Properties Section 3-7 IMPORTANT If there is a CS/CJ-series DeviceNet Unit in the network, disable the master function of the CS/CJ-series DeviceNet Unit, or disable I/O communications from the DeviceNet Unit monitor window, and then do the upload. If I/O com- munications are enabled, uploading the device parameters may fail.
  • Page 106 OK Button. When selecting multiple devices and setting the same device password for all the devices, select the Use this password for all device check box in the fol- lowing dialog box, and then entering passwords will no longer be necessary for each device.
  • Page 107 Section 3-7 Device Parameters and Properties First, the system will check whether the network configuration held by the Net- work Configurator and the actual network configuration match. The device type, device name, and network number will be checked. The following dialog box will be displayed if the configurations do not match.
  • Page 108 The Error Device List displays by device the errors that occurred during parameter download. • If the Error Device List shows that a parameter error has been found and if that error was caused by the I/O Terminal settings, the terminal with the error will be displayed in the Message Pane.
  • Page 109: Device Properties

    The Device Property Dialog Box can be displayed using any of the following methods. 1. Select a device, and then select Device - Property from the menu bar. 2. Select a device, and the click the Device Property Button on the toolbar.
  • Page 110 Section 3-7 Device Parameters and Properties I/O Information Tab Page In this tab page, you can check the standard I/O classification information of a device. Signature Tab Page In this tab page, you can check the safety signature that the Network Configu-...
  • Page 111 EtherNet/IP Network Display Windows (Only for NE1A-SCPU01-EIP and NE1A- SCPU02-EIP) General Tab Page In this tab page, you can check the device information and change the device icon displayed in the Network Configuration Pane. I/O Information Tab Page In this tab page, you can check the EtherNet/IP standard I/O types for...
  • Page 112: Parameter Verification

    With Network Configurator Ver. 2.0@ or higher, multiple devices can be selected and verified all at once. 1. Select a device, and then select Device - Parameter - Verify from the menu bar. 2. Select a device, and then click the Verify Parameter Button on the toolbar.
  • Page 113 Check whether the Logic Program matches. Note • Verification results can be saved. Click the Save Button at the top left of the window to save the results. • The displayed parameters and logic can also be printed. To print, click the Print Button.
  • Page 114 Note Click the Save Button to save the configuration parameter report in HTML format. Click the Print Button to print the report. Note • After verifying the parameters of all the devices, make sure to save the network configuration file. • The Verified configuration parameter symbol ensures that the device parameters in the network configuration file are correct.
  • Page 115 Parameter Mismatch When the Network Configurator detects a mismatch in parameter verification, the parameter with the mismatch will be displayed with the safety signature in the window as in the following example. Check the parameter values and perform the download again.
  • Page 116: Configuration Lock

    After the configuration lock has completed, the safety symbol attached to the device icon in the virtual network will change to a symbol of a lock, which indi- cates that the configuration lock has completed. IMPORTANT Operation of the device must be tested before lock the configuration.
  • Page 117: Unlocking The Device Configuration

    This function is enabled only when the Network Configurator is online. 1. Select one or more devices, and then select Device - Parameter - Unlock from the menu bar. 2. Select one or more devices, and then right-click each device and select Parameter - Unlock.
  • Page 118: 3-10 Device Reset And Status Change

    The information above is stored in the nonvolatile memory of the device, and so it is not cleared by cycling the power source once it is set. To clear the information (to return to the default settings), select Return to the out-of-box...
  • Page 119: 3-10-2 Resetting Devices

    Reset devices using either of the following methods. This function is enabled only when the Network Configurator is online. 1. Select one or more devices, and then select Device - Reset from the menu bar. 2. Select one or more devices, and then right-click each device and select Reset.
  • Page 120: 3-10-3 Reset Types And Device Status

    With Network Configurator Ver. 2.0@ or higher, modes can be changed all at once by selecting multiple devices. 1. Select a device, and then select Device - Change Mode followed by the desired mode. 2. Select a device, and then right-click the device and select Change Mode followed by the desired mode.
  • Page 121 Section 3-10 Device Reset and Status Change DeviceNet network EtherNet/IP network Refer to A-7 Function Restrictions for the NE1A-SCPU0 -EIP for information on functions that cannot be manipulated in the EtherNet/IP Network Window...
  • Page 123: Editing Safety I/O Terminal Parameters

    Parameter Groups ........
  • Page 124: Editing Parameters

    Device parameters can be edited using any of the following methods. 1. Double-click a device icon. 2. Select a device, and then select Device - Parameter - Edit from the menu bar. 3. Select a device, and then click the Edit Parameter Button on the toolbar.
  • Page 125 • The following dialog box will be displayed if a type with welding check is selected when the terminal is set. • In this dialog box, select the input for which welding is to be checked, and then click the OK Button.
  • Page 126 Note (1) Can be selected only when the terminal number is an even number. (2) Can be selected only when the terminal number is an even number and there are at least four remaining terminals. 5. Click the Next Button. If there are output terminals (e.g., DST1-MD12SSL- 1), the following dialog box will be displayed.
  • Page 127 8. After checking the settings, click the Finish Button. The following dialog box will be displayed. 9. Click the Save Button. The items set with the wizard will be saved in HTML. The file can be viewed using a web browser.
  • Page 128: Parameter Groups

    Safety I/O Terminal parameters are classified into groups as shown in the fol- lowing diagram. • Double-click a group name or click the icon to display or hide that group. • Parameter settings for a particular terminal can be batch copied to the parameters for another terminal.
  • Page 129: General Parameter Group

    ON. Threshold Run Hours 0 to 429,496,729 hours This parameter sets the threshold for unit 0 hours operating hours. When the operating hours exceeds the set threshold, the correspond- ing bit in general status will turn ON.
  • Page 130: Safety Input Parameter Groups

    Not used. Mode device not connected.) Test pulse from test out Specifies connecting a device with a contact output in combination with a test output. When this mode is selected, select the test output to use for the test source and then set the test output mode to Pulse Test Output.
  • Page 131 IMPORTANT When the Safety Input Channel Mode is set to Test Pulse from Test Out, spec- ify the test output to use for the test source and set the Test Output Channel Mode of the test output to Pulse Test Output.
  • Page 132: Test Output Parameter Groups

    I/O Comment 32 characters max. Sets an I/O comment for the test output. The None I/O comment set here is used as the I/O tag in the Logic Editor. Maintenance Counter Time (total ON time) Sets the operating mode for the mainte-...
  • Page 133: Safety Output Parameter Groups

    I/O Comment 32 characters max. Sets an I/O comment for the safety output. None The I/O comment set here is used as the I/O tag in the Logic Editor. Maintenance Counter Time (total ON time) Sets the operating mode for the mainte-...
  • Page 134: Operation Time Parameter Groups

    Editing I/O Comments I/O comments can be edited by setting the safety input terminals and safety output terminals. The edited comments here are used as I/O tags in the Logic Editor. In the following procedure, separate I/O tags for safety input terminals and safety output terminals are edited in one window.
  • Page 135 1. Click the Replace All Button in the window above. The following window will be displayed. 2. Input the character string to be searched for and the characters it is to be replaced with, and then click the OK Button. The comments will be re- placed.
  • Page 136: Editing Parameters For Logic Terminals (Dst1-Xd0808Sl-1)

    Valve Switch Safety Door Switch Safety Light Curtain One of the following methods can be used to edit parameters for a Logic Ter- minal. 1,2,3... 1. Select a device, and select Device - Parameter - Wizard from the menu bar.
  • Page 137: Setting Parameters Using The Wizard

    3. Select all the output devices to connect (the parameter options are the same as for the DST1-MD169SL-1) and click the Next Button. • Each time you click the Next Button after this, the Input Bits, Output I/O Comment, and Input I/O Comment Dialog Boxes will be displayed. Select...
  • Page 138: Editing Safety Logic: Inputs

    Section 4-2 Editing Parameters for Logic Terminals (DST1-XD0808SL-1) • When the Next Button is clicked in the Input I/O Comment Dialog Box, the Configuration Result Dialog Box will be displayed. 4. Check the configuration results and click the Next Button. The Safety Logic Wizard Input Dialog Box (Edit Safety Logic Dialog Box for inputs) will be displayed.
  • Page 139 Input Bits Dialog Box, the corresponding two inputs will be dis- played (e.g., IN0/IN1). 2. Terminal Name The comment that was set in the Input I/O Comment Dialog box will be dis- played. 3. Input Function Block The function block selected in the Input Bits Dialog Box will be displayed automatically.
  • Page 140 Editing Parameters for Logic Terminals (DST1-XD0808SL-1) (2) Specify Input Condition with Logical OR Only When this option is selected, the input condition can be selected from the options shown in the following figure. (3) Specify Input Condition with Logical AND or OR When this option is selected, the input condition can be selected from the options shown in the following figure.
  • Page 141: Editing Safety Logic: Outputs

    4-2-4 Editing Safety Logic: Outputs Click the Next Button in the Configuration Result Dialog Box in step 3 in 4-2-3 Editing Safety Logic: Inputs to display the following Safety Logic Wizard - Out- put Dialog Box (the dialog box to edit safety logic for output).
  • Page 142 2. Select the output condition. The options are as follows: (1) Remote I/O Output Outputs the signal that the logic terminal received from the Safety Mas- ter. When this option is selected, the result of the internal logic is ignored.
  • Page 143 Editing Parameters for Logic Terminals (DST1-XD0808SL-1) (2) Output from Logic The result of the internal logic is output to the local output terminal. The output condition can be selected from the following list. (The condition depends on the input settings. For example, if Input0 and Input1 are used as a single input, Input0/1 becomes Input0, Input1.)
  • Page 144 Editing Parameters for Logic Terminals (DST1-XD0808SL-1) (2) Output from the Logic The result of the internal logic is output to the local output terminal. The output condition can be selected from the following list. (The condition depends on the input settings. For example, if IN0 and IN1 are used as a single input, IN0/1 becomes IN0, IN1.)
  • Page 145 When output from logic is selected as the terminal mode, the following figure will be displayed for the output condition. (If a mode other than output from logic is selected, the following figure will be displayed.) Click the selection button when the above figure is displayed to enable select- ing the output condition.
  • Page 146: Using Application Templates

    Logic Terminal parameters. This section describes how to use the application templates. 1,2,3... 1. Select the Logic Terminal (DST1-XD0808SL-1), and select Device - Pa- rameter - Wizard from the menu bar. The following dialog box will be dis- played.
  • Page 147 2. Select the Use an application template Option shown above, and select the type of application template to use. Click the Detail Button to display a file with the details of the selected ap- plication. 3. Click the Next Button.
  • Page 148 Section 4-2 5. Check the settings and click the Next Button. The following Safety Logic Wizard - Input Dialog Box (the dialog box to edit safety logic for inputs) will be displayed. 6. Check the logic and make any changes as required. Click the Next Button.
  • Page 149: Editing Safety Network Controller Parameters

    Setting Test Outputs ........
  • Page 150: Safety Connection Settings

    1. Unregistered devices are listed in the upper pane, and registered devices are listed in the lower pane. 2. Select a Safety Slave to register in the Unregister Device List and click the Button. 3. The Safety Slave selected in step 2 will be registered.
  • Page 151 Section 5-1 Note With Configurator Ver. 2.0@ or higher, the following procedure can be used to register to a Safety Slave to more than one Safety Mas- ter all at once. a. Select the safety Slave to be registered, and then select Device - Reg- ister to Another Device - Multi device .
  • Page 152 I/O assembly used in the safety con- nection ( icon) is displayed. The EPI for the safety connection is displayed. For details on EPI, refer to 5-1-2 Setting Safety Connection Parameters. Reaction Time The network reaction time for the safety connection is displayed.
  • Page 153: Setting Safety Connection Parameters

    Slave has an output connection owner TUNID stored. If an attempt is made, the 7-segment display on the NE1A-series Safety Mas- ter will show “d6” and the status code (see note 3)(error code) shown on the Safety Connection Tab of the Device Monitor Window will be “01:0106”.
  • Page 154 Safety Slave correctly from the Network Configurator. If it is not correctly configured, a connection will not be established, so there is no need to send the safety signature from the Safety Master for check- ing.
  • Page 155 Description Multi-cast connection This connection type can be selected only with a Safety Input Slave. When a multi- cast connection is selected, a Safety Input Slave can transmit the input data to a maximum of 15 NE1A-series Controllers via a multi-cast connection.
  • Page 156 5. Select the baud rate to be used in the Update Device Configuration Dialog Box and click the OK Button. The best average EPI for all connections will be batch set as the EPI in the safety connection parameters for all devices.
  • Page 157 Network Delay Multiplier: This parameter is used when calculating the reaction time. Set the network delay as a percentage of the EPI. The default is 100% (i.e., the same as the EPI). ID Allocation: This parameter is used to set whether the master or the slave will allocate an ID for the safety connection.
  • Page 158: Stopping/Restarting Communications After An Error

    Device. Setting the Operating Mode after a Communications Error One of the following modes can be selected on the Extend Mode Tab Page to specify the Controller's operation when there is a connection timeout during safety I/O communications with the safety slave.
  • Page 159 Network Configurator to send a command to restart communications. It is also possible to write a logic routine in the logic pro- gram in advance to turn ON the Safety I/O Communications Restart Flag and restart communications with a specified trigger bit.
  • Page 160: Listing And Setting Connection Parameters

    5-1-4 Listing and Setting Connection Parameters The connection data currently set for all devices can be displayed in the Edit All Connection Window and parameters can be changed. New connections, however, cannot be created and existing connections cannot be deleted.
  • Page 161: Safety Slave Settings

    I/O tags name defined in the assembly icon) are displayed. Type The input/output type for the I/O assembly and the data types for the I/O tags are displayed. Size The I/O assembly size and the sizes of the I/O tags are displayed.
  • Page 162: Setting Assembly Data

    Section 5-2 Safety Slave Settings • To delete the I/O assembly, select the I/O assembly you want to delete and click the Delete Button. 5-2-2 Setting Assembly Data This section describes how to define I/O assembly data. I/O Type Select the data type to set. The transmission directions for the safety data are as follows: Safety Slave Input: NE1A-series Controller (Safety Slave) →...
  • Page 163 Logic Editor. • Click the New Button and set a tag name and data type when defining a new I/O tag. I/O tags for up to 16 bytes can be defined in each I/O assem- bly.
  • Page 164 Section 5-2 Safety Slave Settings 2. Click the Edit Comment Button. 3. Edit the I/O Tag. I/O Tags created in this way will be displayed as follows by the Logic Editor:...
  • Page 165 Section 5-2 Safety Slave Settings Status When the I/O type is Target Input, the NE1A-series Controller status informa- tion can be included in the I/O assembly. The following tag names are auto- matically used for the status information: Status Tag name...
  • Page 166 Section 5-2 Safety Slave Settings A button will be displayed next to the Input Check Box. The button will be labeled according to the number of input points ("Bit0-15" in the example dis- play). Click this button. The following dialog box will be displayed.
  • Page 167 Section 5-2 Safety Slave Settings...
  • Page 168: Standard Slave Settings

    I/O tags name defined in the assembly icon) are displayed. Type The input/output type for the I/O assembly and data types for the I/O tags are displayed. Size I/O assembly size and the sizes of I/O tags are displayed.
  • Page 169: Setting Slave Input Data In Idle State

    Delete Button. 5-3-2 Setting Slave Input Data in Idle State Set to hold or clear the last data for an input assembly that the NE1A-series Controller transmits to the Standard Master in either of the following condi- tions: •...
  • Page 170 • Click the New Button and set a tag name and data type when defining a new I/O tag. I/O tags for up to 16 bytes can be defined in each I/O assem- bly. If Bit-Strobe is selected, however, the maximum is limited to 8 bytes.
  • Page 171: Setting The Controller As An Ethernet/Ip Standard Target

    Setting the Controller as an EtherNet/IP Standard Target Setting the Controller as an EtherNet/IP Standard Target Click the EtherNet/IP Target I/O Tab to display the setting window for the Stan- dard Target I/O assembly that is required to operate an NE1A-series Control- ler that supports EtherNet/IP as a standard target.
  • Page 172: Setting Assembly Data

    Select the connection type to be used for the I/O assembly. Input assemblies and output assemblies can be set for each connection. I/O Tags Multiple I/O tags can be defined in an I/O assembly. The I/O tags defined here can be used by the Logic Editor.
  • Page 173 Setting the Controller as an EtherNet/IP Standard Target • To define a new I/O tag, click the New Button and set the tag name and data type. I/O tags for up to 16 bytes can be defined in each I/O assembly.
  • Page 174: Local I/O Settings

    Controller’s I/O Setting Window. Note (1) All I/O are in the Not Used state in the default settings. If you do not use the I/O of the NE1A-series Controller, it is not necessary to set the param- eters in this window.
  • Page 175 • The following dialog box will be displayed if a type with welding check is selected when the terminal is set. • In this dialog box, select the input for which welding is to be checked, and then click the OK Button.
  • Page 176 Description SLC 1 output Specify to use one input from a light curtain. Other PNP 2 outputs (See note 1.) Specify to use two inputs from other semiconductors. Other PNP output Specify to use one input from other semiconductors. Reset SW Specify to use inputs from a reset switch.
  • Page 177: Setting Safety Inputs

    Even if cause of the cause of the error has been removed, the error state is always latched for this time. It can be set between 0 and 65,530 ms in 10-ms increments.
  • Page 178 Local I/O Settings Section 5-5 Terminal Name A terminal name can be set for a safety input. The terminal name set here is used as the I/O tag in the Logic Editor. Channel Mode Set the Channel Mode for the safety input.
  • Page 179 These parameters set the ON delay time and OFF delay time for the safety input. The setting range is 0 to 128 ms, but it must be a multiple of the NE1A- series Controller cycle time. Check the displayed NE1A-series Controller cycle time and determine the set value.
  • Page 180: Setting Test Outputs

    Error Latch Time The test output is used in combination with a safety input. The same error latch time setting is thus used for all safety inputs. Refer to Error Latch Time in 5-5-2 Setting Safety Inputs.
  • Page 181: Setting Safety Outputs

    Local I/O Settings Section 5-5 Settings for Individual Test Outputs Double-click the row of the test output number to set, or select the row and click the Edit Button. Terminal Name Set the terminal name for the test output. The terminal name set here is used as the I/O tag in the Logic Editor.
  • Page 182 Even if the cause of the error is removed, the error state will be latched for the time set here. It can be set between 0 and 65,530 ms in 10-ms increments.
  • Page 183: Setting The Operating Mode And Confirming The Cycle Time

    IMPORTANT Even when Automatic Execution Mode is selected and the configuration has been locked, the next startup will not be performed in RUN Mode if the power is turned OFF in IDLE Mode. Turn OFF the power in RUN Mode to use auto- matic execution.
  • Page 184: Confirming The Cycle Time

    The NE1A-series Controller cycle time is automatically calculated and dis- played based on the set parameters and programs created in the Logic Editor. The cycle time is used in calculating the reaction time and the ON/OFF delay time settings. Check the value after all the parameters and programs have been set.
  • Page 185: Restarting A Connection Stopped Due To A Communications Error

    5-6-3 Restarting a Connection Stopped due to a Communications Error When I/O communications have stopped in a connection due to a connection timeout, I/O communications can be restarted in the stopped connection by turning ON the Communications Restart Flag from the logic program or send- ing a Communications Restart command from the Network Configurator.
  • Page 186 Communications restart tags for specific connections Communications restart tag for all connections When these tags have been set in the logic program in advance as I/O com- munications restart conditions, I/O communications can be restarted with these tags by turning ON (OFF → ON) the specified condition.
  • Page 187: Extend Mode Settings

    I/O communications have been stopped, use the Network Configura- tor to send a command to restart communications. It is also possible to write a logic routine in the logic program in advance to turn ON the Safety I/O Communications Restart Flag and restart communications with a specified trigger.
  • Page 188: Setting The Program Execution Delay

    Disable is selected.If communications never begins, Safety I/O.) the program will be executed but the Slave input signals will not be updated in the program. (Input values will be 0.) Note When the Program Execution Delay is disabled, the Slave input signals will not be updated in the program until communications begins.
  • Page 189: Setting Maintenance Information

    Section 5-8 Setting Maintenance Information Setting Maintenance Information The Maintenance Information can be set when using the NE1A-SCPU01-V1 or NE1A-SCPU02 Controller (including NE1A-SCPU01-EIP and NE1A- SCPU02-EIP). For details, refer to 7-2 Maintenance Functions (Unit Version 1.0 or Later).
  • Page 190: Displaying Memory Information

    Displaying Memory Information Information about the memory allocated to the NE1A-series Controller can be displayed by clicking the Memory Info. Tab in the Edit Device Parameter Dia- log Box. Users do not normally need to be aware of the memory addresses because...
  • Page 191: Programming The Safety Network Controller

    Saving the Program........
  • Page 192: Starting And Exiting The Logic Editor

    Starting and Exiting the Logic Editor 6-1-1 Starting the Logic Editor Use the Logic Editor to program the NE1A-series Controller. Use the following procedure to start the Logic Editor. 1. Click the Logic Tab in the Edit Device Parameters Window of the NE1A- series Controller.
  • Page 193: Exiting The Logic Editor

    2. Click the OK Button in the Edit Device Parameters Window. IMPORTANT • To save the program and exit, the user must click the OK Button in the Edit Device Parameters Dialog Box when exiting the Logic Editor. • If the user clicks the Cancel Button, none of the parameters entered until then, including the program, will be saved.
  • Page 194: Menu Commands

    Section 6-2 Menu Commands Menu Commands The following tables describe the commands in the Logic Editor menus. 6-2-1 File Menu Command Description Online Offline Apply Temporarily saves the current program in the Config- urator. Refer to 6-3-6 Saving the Program.
  • Page 195: View Menu

    Message Setting Refer to Sending Explicit Messages in 6-3-3 Pro- gramming Using Function Blocks. Monitoring Monitors I/O tag values and signal states of all the connection lines in the Logic Editor. Refer to 6-3-9 Monitoring the Program. Jump Make New Creates a new jump address (jump source).
  • Page 196: Function Block Menu

    Function Block Menu Command Description Online Offline Import Imports a user-defined function block from a function block file (*.fbd). Refer to Creating User-defined Function Blocks in 6- 3-4 Programming User-defined Function Blocks. Export Exports a user-defined function block to a function block file (*.fbd).
  • Page 197: Programming

    • Each output tag can be used only once, even on different pages. • When a function block is pasted, it is placed in the same position as the function block that was copied. When pasting a function block on the same page, move the source function block.
  • Page 198: Function Blocks

    Section 6-3 Programming 6-3-2 Function Blocks The Network Configurator can create Safety Logic by combining any logic functions and function blocks supported by the NE1A-series Safety Network Controller. These are listed below. Function Blocks Name Notation on Display on the Network...
  • Page 199 Evaluates the input signal and external Device Moni- device status and sends a safety out- toring put to the external device. Function Blocks Supported by NE1A-series Controllers with Unit Version 1.0 or Later (Including NE1A-SCPU01-EIP and NE1A-SCPU02-EIP) Notation on Display on the Network Details...
  • Page 200 Outputs ON/OFF pulses on Output 1 while Input 1 is ON. Counter Counter Counts the number of input signals and turns ON Output 1 hen the count reaches the number set in the configu- ration data. Comparator Comparator Compares input signals (8 max.) with...
  • Page 201: Programming Using Function Blocks

    I/O tags being used in programs can be searched. Double-click the high- lighted item in the I/O list in the Object List to display the page in the pro- gram where the I/O tag is being used and the I/O tag will appear flashing in red.
  • Page 202 Input Tag Placement 1. Click the Input Tab in the Object List. 2. Select the input tag to be used and drag-and-drop it to the desired location in the Workspace. More than one I/O tag can be selected and drag-and- dropped to the Workspace.
  • Page 203 Output Tag Placement 1. Click the Output Tab in the Object List. 2. Select the output tag to use, drag it to the Workspace, and then drop it where you want to position it. The user can select multiple output tags and position them at the same time.
  • Page 204 Click the source connector (■) and drag it to the destination connector. Note The position of connections can be moved and saved after they are con- nected. Connection position data, however, cannot be saved to an NE1A- series Controller. Therefore, if the programming is uploaded from the device, connection position data will be lost, and the system will return to automatic connections.
  • Page 205 The following useful functions for I/O tags are supported in the version upgrade. • The I/O tags used in the program are highlighted in the Object List, as shown in the following diagram. • I/O settings are displayed with symbols with the I/O tags in the Object List.
  • Page 206 I/O or standard I/O. Display Safety I/O Standard I/O None • Double-click the I/O tag in the Object List to display the location in the pro- gram it is being used. Double-click. Flashing in red Note If an input tag is being used on more than one page, keep double-clicking to change the display to the next page.
  • Page 207 Use any of the following methods to delete I/O tags, function blocks, or con- nections. 1. Select the item to delete and then select Edit - Delete from the menu bar. 2. Select the item to delete and then click the Delete Button on the toolbar.
  • Page 208 Programming Section 6-3 Jump Addresses The Jump Address menu commands can be used when the program is com- plex or when it spans multiple pages. 1. First, set the source jump address using either of the following methods: a. Select Function - Jump Address - New from the menu bar.
  • Page 209 I/O point on the screen. Editing Function Block Parameters To edit the parameters of a function block, use any of the following methods to display the Parameter Edit Window. 1. Double-click the function block.
  • Page 210 Section 6-3 Programming Parameters Click the Parameter Tab to set the parameters of the function block. Input/Output Settings Click the In/Out Setting Tab to set the number of inputs or outputs and the Fault Present Option.
  • Page 211 Programming Section 6-3 Setting Output Points Click the Set Output Point Tab and set whether or not to use the different out- put point functions for function blocks. Setting Comments Click the Comment Tab to enter names for the function block or I/O signals.
  • Page 212 Programming Sending Explicit Messages An explicit message can be set in advance and then sent when an output tag turns ON as a trigger. One explicit message can be set for the entire program. (A response is not received to indicate the results of sending the message.) Select Function - User EM from the menu bar.
  • Page 213 Note Open I/O connections are displayed in red. If a jump address is used for the I/O and the corresponding jump address is not used, however, the I/O will not be displayed in red and will appear to be connected.
  • Page 214: Programming User-Defined Function Blocks

    The Logic Editor for creating a function block and the IO Property Dialog Box will be displayed. 2. The number of inputs and outputs and the tag name are set in the IO Prop- erty Dialog Box. The tag name can also be set later.
  • Page 215 Example Programming a User-defined Function Block: 4. Save the user-defined function block. • Select File – Apply from the Logic Editor menu for creating a user- defined function block. • Set the user-defined function block name in the Function Block Name Dialog Box and click the OK Button.
  • Page 216 Creating Programs Using User-defined Function Blocks Importing User-defined Function Blocks User-defined function blocks must be imported before they can be used in a program. (They do not need to be imported if they are already present.) 1. Use the Network Configurator to allocate a new NE1A-series Controller to the network and open the Logic Editor.
  • Page 217 Section 6-3 Programming 3. Select the file and click the Open Button. The imported user-defined function block will be displayed in the Logic Ed- itor Object List. Example Screen: User defined function blocks are displayed. Right click a user defined function block and select Edit to enable editing the user defined function block.
  • Page 218 Block when the menu is displayed. The following Function Block List Window will be displayed. 2. In the Function Block List Window, select the function block to be edited, and click the Edit Button. The menu for editing the parameters of the cor-...
  • Page 219 Section 6-3 Programming 3. Edit the parameters, and then click the OK Button. The parameter will be changed, and then the filter will be updated. Note (1) Parameter changes are performed for the file. If a user-defined function block is edited, the changes will be applied to all instances of that user-defined function block.
  • Page 220 Reusing User-defined Function Block Files Project files (*.ncf files) and user-defined function block files (*.fbd files) exist as separate files. This allows a user to reuse user-defined function blocks cre- ated by a different user when creating programs. The procedure to reuse user-defined function blocks is described below.
  • Page 221 Importing User-defined Function Blocks A user-defined function block must first be imported before it can be used in a program. 1. Use the Network Configurator to allocate a new NE1A-series Controller to the network and open the Logic Editor.
  • Page 222 User-defined function blocks that are no longer required can be deleted. 1. Click the user-defined function block to be deleted on the Logic Editor Ob- ject List. 2. Select Function Block – Delete from the Logic Editor main menu.
  • Page 223 Programs cannot be edited without the user-defined function block file. Always import the user-defined function blocks before editing. A warning message like the one shown below will appear if the Logic Editor is started without the user-defined function block file.
  • Page 224 The following diagram shows how the program will appear if the Logic Editor is started in this status. A user-defined function block without a file will appear as a question mark (?) and the connections will be deleted. Editing operations (copy, paste, undo, redo, etc.) cannot be used for the user-defined function block.
  • Page 225 The following section describes the proce- dure. 1. Click the Edit Button in the Logic Tab of the Edit Device Parameters Win- dow of the NE1A-series Controller to start the Logic Controller. The follow- ing message will be displayed.
  • Page 226 (output tags and connections to jump addresses will not be affected). • If the Yes Button is clicked, changes to the user-defined function block file will be updated in the programming. If changes to the user-defined function block affect the function block exe- cution sequence (e.g., newly adding or deleting parts of the function...
  • Page 227: Password Protection For User-Defined Function Blocks

    The program password is now set. From now on a dialog box requesting the password will be displayed when- ever Function Block – Edit is selected from the function block list. Unless the set password is entered, the screen for creating user-defined function blocks will not be displayed and the function blocks cannot be edited.
  • Page 228: Saving The Program

    2. After exiting the Logic Editor, click the OK Button in the Edit Device Param- eters Dialog Box. 3. To save the file, select File and Save or Save As in the Main Window of the Network Configurator. IMPORTANT •...
  • Page 229: Password Protection For Programs

    Download the file with the password to the Safety Network Controller. 1. Select Enable Password on the Logic Tab Page of the Edit Device Param- eters Dialog Box shown below.
  • Page 230: Updating The Program

    1. Select Function - Monitoring from the menu bar. 2. Click the Monitoring Button on the toolbar. During monitoring, the I/O tags or connections that are ON will be displayed in a darker green color. User-defined function block contents can be monitored.
  • Page 231 Monitoring from the pop-up menu. 2. The Monitoring Screen will be displayed. 3. Click the Monitoring Button on the toolbar. During monitoring, the I/O tags or connections that are ON will be dis- played in dark green. Stopping Online Monitoring...
  • Page 232 Click the Print Button on the toolbar. The following dialog box will be displayed. 2. Click the Yes Button to also print the function block I/O comments when printing the program. A Print Dialog Box like the one shown below will be displayed.
  • Page 233 Jump addresses can be used in programs to create loopbacks. If a program contains more than one loopback (e.g., Jump 1 to Jump 1 and Jump 2 to Jump 2 in the following example), the sequence of execution will be in the order that the function blocks are positioned.
  • Page 235: Monitoring Devices

    Monitoring Status ........
  • Page 236: Monitoring Functions

    Monitoring Status Using the Network Configurator The user can monitor the status using any of the following methods: 1. Select a device and select Device - Monitor from the menu bar. Click the Status Tab in the displayed window. 2. Select a device and click the Monitor Device Button on the toolbar. Click the Status Tab in the displayed window.
  • Page 237 If there is an alarm, the device will stop operation. Therefore the problem must be resolved. If there is a warning, the device will continue to operate but the incident may develop into a problem. Therefore it is recommended that the cause of the...
  • Page 238: Monitoring Safety Connections

    Status codes (error codes) can be monitored (version 1.5@ or higher). This is useful when a connection cannot be established, because the status code returned by the target device can be used to check the cause of the error. Refer to 8-1 Connection Status Tables for details of status codes.
  • Page 239 Connection error has occurred. For the local node address (i.e., the node address of the Safety Slave), the color gray indicates that there is no connection or that an error has occurred in the connection. The color blue indicates normal communications.
  • Page 240: Monitoring Parameters

    Monitoring Using the Network Configurator The user can monitor the parameters using any of the following methods: 1. Select a device and select Device – Monitor from the menu bar. Click the Parameters Tab in the displayed window. 2. Select a device and click the Monitor Device Button on the toolbar. Click the Parameters Tab in the displayed window.
  • Page 241 Item Description Test Output Value Output value of the test output. Test Output Status Evaluation result of the test output. “Alarm” is displayed if an error occurs. Reason for Test Output The cause of the error is displayed. Alarm Safety Input Terminal Status...
  • Page 242: Monitoring The Error History

    Depending on the error type, some errors are saved in non-volatile memory and not cleared when the power is turned OFF. Other errors are saved in RAM and cleared when the power is turned OFF. Refer to the relevant operation manual for details.
  • Page 243 You can use any of the following methods to monitor the EtherNet/IP error his- tory. 1. Select a device and then select Device - Monitor from the menu bar. Click the EtherNet/IP Error History Tab in the displayed window. 2. Select a device and then click the Monitor Device Button on the toolbar.
  • Page 244 Contents Displays the error contents. Saving the Error History The error history information can be saved in CSV format. Click the Save But- ton to save the information. Clearing the Error History Click the Clear Button to clear the error history saved internally in the NE1A- series or DST1-series Safety I/O Terminal.
  • Page 245: Maintenance Functions (Unit Version 1.0 Or Later)

    ■ Calculating the Total ON Time with 0.5-s ON Pulses In figure A, the bit is actually ON for 0.5 s × 3 = 1.5 s, but the bit is ON just once when the status is checked, so the total ON time is measured as 1 s.
  • Page 246 ■ Calculating the Total ON Time with 1.5-s ON Pulses In figure C, the bit is actually ON for 1.5 s × 2 = 3 s, but the bit is ON four times when the status is checked, so the total ON time is measured as 4 s.
  • Page 247 PV to the alarm threshold SV. Monitoring the Total ON Time from the Network Configurator Any of the following methods can be used to monitor the total ON time in the local inputs, test outputs, or local outputs.
  • Page 248: Contact Operation Counter

    Maintenance Functions (Unit Version 1.0 or Later) Section 7-2 Each I/O point’s accumulated total ON time can be cleared. To clear the time, select the total ON time to be cleared and click the Clear Value Button. 7-2-2 Contact Operation Counter Overview In Ver.
  • Page 249 (Threshold Maintenance Counter) can be set for each local input, test output, and local output terminal. If the alarm threshold (Threshold Maintenance Counter) is set to 0, the Con- troller will not compare the count or time PV to the alarm threshold SV.
  • Page 250 Maintenance Functions (Unit Version 1.0 or Later) Monitoring Operations from the Network Configurator Any of the following methods can be used to monitor the number of contact operations in the local inputs, test outputs, or local outputs. 1. Select the device and select Device – Maintenance information from the menu bar.
  • Page 251: Displaying Safety Device Status

    Network Configurator. • Uploading networks • Downloading networks • Downloading parameters • Updating maintenance information • Uploading device modes (RUN/IDLE) • Resetting devices In addition, while online, the display can be updated at any time by selecting Network –Update Device Status.
  • Page 252 Displaying Safety Device Status Automatic Updates of Device Status Displays When the Network Configurator is connected to the system and online, device information can be automatically acquired and the status displayed. To have device status updated and displayed automatically when an online connection is made, select Options –...
  • Page 253: Troubleshooting

    Errors When Changing Modes ........
  • Page 254: Connection Status Tables

    • Is the network bandwidth allocation suitable? 01:0105 Configuration Owner Error The Safety Slave was configured from a configuration tool or Safety Master at a different node address last time. Reset the Safety Slave to the default settings and download the device parameters again.
  • Page 255 It may not be possible to communicate with the Safety Slave. Safety Slave timed out Check the status of the Safety Slave to see if it is online (the NS indicator should be flashing or lit green). If the Safety Slave is online, check the following items.
  • Page 256: Connection Status For The Ne1A-Series Controller (Safety Slave Function)

    Safety Slave to default settings and download the device parameters to the Safety Slave again. 2. The Open Type of the Safety Master connection is set to Configure the Safe- ty Slave when the execution mode of the DST1-XD@@ Safety Slave is set to Auto Execution mode.
  • Page 257 EPI has been set for a safety slave I/O. • To share one safety slave I/O on a Safety Slave with more than one Safety Master, make the EPI all the same and set the connection type to Multi-cast.
  • Page 258 Section 8-1 Status Countermeasure 0C:0002 The Safety Slave is in The NE1A-series Controller operating as a Safety Slave is in IDLE mode, and IDLE mode safety I/O connection cannot be established. Change the operating mode to RUN mode. D0:0001 IDLE Mode The NE1A-series Controller that is the Safety Master (d6/b6 is displayed) is in IDLE mode, and has not started a safety I/O connection.
  • Page 259: Errors When Downloading

    The configuration data is locked. (LOCK indicator is lit.) Release the lock. The TUNID not matched. The device is waiting for a TUNID setting after being reset (NS indicator is flashing green/red) or the TUNID of the Network Configurator is different from the device when downloading.
  • Page 260 • One of the safety inputs in a dual channel setting is set as a standard input and the other has a different setting. • One of the safety inputs in a dual channel setting is set to Not Use and the other has a different setting.
  • Page 261 Safety Master to which the safety connections are reg- istered to IDLE mode. 3. If the above causes do not apply, noise or other factors may be making communications unstable. Check the following items. • Do all nodes have the same baud rate? •...
  • Page 262: Errors When Resetting

    8-3-1 Outline When the NE1A-series Controller or a DST1-series or other Safety Device is reset, the device may return an error response. The cause of the error can be determined from the error information shown in the Network Configurator. 8-3-2...
  • Page 263: Errors When Changing Modes

    Check that the correct password is being used. Specified device can not be accessed, or The device has just been reset or the power cycled and the device is not wrong device type or password. ready for communications (i.e., not online with the NS indicator flashing or lit green.) Check that the device is communications ready then reset.
  • Page 264: Errors That Can Be Found Using The Connection Check Function

    Controller, and check the device types of the registered node addresses and devices in the virtual network. The Safety Slave (node address) TUNID is incorrect. Go to Network - Property and make sure that the network num- bers are unified.
  • Page 265 The EPI of the connection (node address: network Check the Register Device List of the corresponding NE1A-series name: connection name) is outside the supported Controller, and adjust the EPI of the connection to within the sup- range. ported range. The number of OUT connections has exceeded the Check the number of Masters the corresponding device is regis- limit.
  • Page 267: Maintenance Tool

    Read this section before you attempt to use the Maintenance Tool. Overview of Maintenance Tool........
  • Page 268: Overview Of Maintenance Tool

    The Maintenance Tool is a special software application used to perform main- tenance for DeviceNet Safety Networks. It must be installed on a personal computer to use it. The Maintenance Tool will be automatically installed if the Network Configurator is installed, but it is also possible to install only the Maintenance Tool.
  • Page 269 Network configuration files (*.ncf) and device parameter files (*.dvf) are cre- ated with the Network Configurator and used with the Maintenance Tool. Display of Errors and Countermeasures The status of and countermeasures for errors are displayed in a dialog box.
  • Page 270: Differences With Network Configurator Functions

    Section 9-1 Overview of Maintenance Tool 9-1-2 Differences with Network Configurator Functions The differences between the Maintenance Tool and Network Configurator functions are outlined in the following table. OK: Possible, ---: Not possible Item Maintenance Tool Network Configurator Controllable DeviceNet Safety Devices • NE1A Series •...
  • Page 271: Starting And Exiting The Maintenance Tool And Version Information

    Starting and Exiting the Maintenance Tool and Version Information Starting and Exiting the Maintenance Tool and Version Information This section describes how to start and exit the Maintenance Tool and how to check the version. 9-2-1 Starting and Exiting the Maintenance Tool Start Procedure 1,2,3...
  • Page 272: Displaying The Version Information

    Version information for the Maintenance Tool can be displayed. 1,2,3... 1. Select About from the menu bar. The version information of the Maintenance Tool will be displayed. 2. Click the OK Button. The display will return to the Main Window.
  • Page 273: Screen Names And Functions

    Tool and information about connected DeviceNet Safety Devices will be dis- played. Menu Display Function Menu Display Click the function icon to execute a function. The icons of the functions that cannot be used offline will be displayed in gray and cannot be selected. Device Information Status The status of the connected device is displayed.
  • Page 274: Function Icons

    Function Icons Function name Icon Description Reference Reconnect Connects a device online when the Maintenance Tool and a device are not 9-5-1 connected. Device Status Displays the device status as well as details of alarms and warnings. Mainte- 9-6-3 nance information for the connected device will be displayed on the Mainte- nance Tab Page.
  • Page 275: Setting The Monitor Refresh Time

    1. Click the Monitor Settings Icon in the Main Window. The following dialog box will be displayed. 2. Set the new refresh timer value and click the OK Button. The new setting will be applied and the display will return to the Main Win- dow.
  • Page 276: Basic Online Operations

    9-5-1 Connecting the Maintenance Tool The Maintenance Tool can be used by connecting it to the USB port on an NE0A/NE1A-series Controller. When the Maintenance Tool is connected to the USB port of an NE0A/NE1A- series Controller, the following Main Window will be displayed.
  • Page 277: Specifying The Network Number

    Specifying the Network Number DeviceNet Safety enables building systems using multiple networks, and so it is necessary to specify the network number even if the user system has only one network. Specify the network number with the Maintenance Tool in the following cases.
  • Page 278 Note To obtain the network number from the network, turn ON the DeviceNet net- work power supply. If there is more than one network number on the same network, be sure to select the correct network number. IMPORTANT If the network number is specified manually, it will be displayed with zeros inserted between the fifth to eighth digits from the right when the network number is obtained from a network.
  • Page 279: Changing The Connected Device

    Changing the Connected Device This section describes how to change the connected device. The Mainte- nance Tool can be connected to devices that are on the same DeviceNet net- work as the NE0A/NE1A-series Controller connected with the USB cable. 1,2,3...
  • Page 280 You can specify whether to save the status of updated devices in the Browse Network Dialog Box. If the browse status is set to Save, the status of updated devices will be held even if the Browse Network Dialog Box is opened again.
  • Page 281: Reading Device Information

    Error History functions are the same. The items displayed will depend on the connected device. (2) The device status will be displayed as an icon in the Main Window when a device is online. (Refer to 9-5-1 Connecting the Maintenance Tool.) Procedure 1,2,3...
  • Page 282 Section 9-6 Reading Device Information The current status of the I/O terminals will be displayed on the Parameters Tab Page. 2. Click the Maintenance Tab. If an error exists in the connected device, the following will be displayed.
  • Page 283: Reading Device Status, Alarms, And Warning Information

    • Click the Clear Value Button to reset the terminal maintenance counters to 0. 9-6-3 Reading Device Status, Alarms, and Warning Information The status of the connected device as well as information on alarms and warnings can be displayed. The displayed parameters depend on the device that is connected. 1,2,3...
  • Page 284 Section 9-6 Reading Device Information • Click the Detail Button to display details on current alarms and warn- ings as shown below. Error information will be displayed in pairs. Address of node with error or error response value. • The icon will be displayed for alarms and the icon for warnings.
  • Page 285: Reading The Error History

    Some errors are not deleted even if power supply is interrupted because they are saved in nonvolatile memory. Other errors are deleted when the power supply is interrupted because they are saved in the RAM. Refer to the device manual for details.
  • Page 286 Save Button Saves the error history information in CSV format. Help Button Select an error and click the Help Button to display the coun- termeasures. 2. Click the Maintenance Tab. Current errors in the connected device will be displayed as shown below.
  • Page 287 Section 9-6 Reading Device Information • Refer to 9-6-2 Monitoring I/O Terminals for details on the Maintenance Tab Page.
  • Page 288: Replacing A Device

    9-9-1 Creating Device Parameter Files. (2) If a system error occurs because of a fatal hardware error in the device to be replaced, it will not be possible to use the Device Replacement func- tion (on an NE1A-series Controller, the left side of the seven-segment dis- play will show “H”, and on an NE0A-SCPU01 or DST1-series Controllers,...
  • Page 289 4. Click the OK Button. Note When replacing a device with a new device, the new device must be in default status. If a device is replaced with a configured device, the correct network number may not be set, which would prevent establishing connections for Safety I/O.
  • Page 290 8. Click the Yes Button. The password input dialog box will be displayed. 9. Enter the device password of the device connected online and then click the OK Button to start downloading. The following dialog box will be dis- played after downloading has been completed.
  • Page 291 14. Click the OK Button. The display will return to the Main Window. Note The Maintenance Tool cannot be used to set the node address or IP address of a device. Set the node address and IP address of the replacement device in advance.
  • Page 292: Uploading To Individual Devices

    Section 9-8 Uploading to Individual Devices Uploading to Individual Devices It is possible to obtain and save parameters of the device that is connected online. 1,2,3... 1. Click the Upload (Backup) Icon in the Main Window. The following dialog box will be displayed.
  • Page 293 The Save device parameters Dialog Box will be displayed. The file name will be automatically entered as shown in the following figure. 4. Confirm the file save location and file name, and then click the Save But- ton. This completes the uploading procedure.
  • Page 294: Downloading For Individual Devices

    The system may not operate correctly the file that is used has not been verified or locked. 3. Select the device, and then select Device - Parameter - Save As from the menu bar.
  • Page 295 Section 9-9 Downloading for Individual Devices The Open device parameters Dialog Box will be displayed. 2. Confirm the file save location and file name, and then click the Open But- ton. The following dialog box will be displayed. 3. Confirm the report information, and then click the Close Button.
  • Page 296 Downloading for Individual Devices Note Be sure to confirm that the network number is correct. Safety I/O connections may not be established if the device is configured with the wrong network number. Refer to 9-5-2 Specifying the Network Number for information on net- work numbers.
  • Page 297 Serious personal injury may possibly occur due to loss of safety functions. Observe the following precautions. Perform a user test before operating the system, and check to make sure that all the device configuration data and operations are correct. After replacing a device, check to make sure that the replacement device is in...
  • Page 298: Uploading (Network)

    The following dialog box will be displayed. 2. Specify the network to connect online and click the OK Button. IMPORTANT To obtain the network number from the network, turn ON the DeviceNet net- work power supply. (EtherNet/IP networks are not supported.)
  • Page 299 • If you click the No Button, uploading will be canceled. The Save Network Configuration Dialog Box will be displayed after upload- ing has been completed. 4. Confirm the file save location and file name, and then click the Save But- ton. The Assign Password Dialog Box will be displayed.
  • Page 300: Downloading (Network)

    The following dialog box will be displayed. Note Be sure to confirm that the network number is correct. The system may not operate correctly if the devices are configured without the correct network number. Refer to 9-5-2 Specifying the Network Number for information on net- work numbers.
  • Page 301 IMPORTANT The network download function is supported only for DeviceNet networks. (EtherNet/IP networks are not supported.) The Open Dialog Box will be displayed. 4. Confirm the file save location and file name, and then click the Open But- ton. The Confirm Password Dialog Box will be displayed.
  • Page 302 Button. The Input the Device Password Dialog Box will be displayed. 7. Enter the device password for the device and then click the OK Button to start downloading. The following dialog box will be displayed after down- loading has been completed.
  • Page 303: 9-12 Resetting A Device

    The information above is saved in nonvolatile memory in the device. It will not be cleared by restarting the power supply. To clear the information (to return to the default settings), select the Reboot and reset configuration or Reboot...
  • Page 304: 9-12-2 Resetting A Device

    1,2,3... 1. Click the Reset Icon in the Main Window. The following dialog box will be displayed. 2. Select the reset type and click the OK Button. This completes the resetting procedure. 3. Click the OK Button. After resetting, the display will return to the Main Window.
  • Page 305 With the Maintenance Tool, it is not possible to set device node addresses with software. It is also not possible to set IP addresses. To reset node addresses or IP addresses that have already been set for devices, select the Return to the out-of-box configuration, and then emulate cycling power Option, and then select Node Address (Software) Settings.
  • Page 306: 9-13 Changing The Mode

    The following dialog box will be displayed. Note Be sure to confirm that the network number is correct. Safety I/O connections may not be established if the device is configured with the wrong network number. Refer to 9-5-2 Specifying the Network Number for information on net- work numbers.
  • Page 307 Section 9-13 Changing the Mode 4. Enter the password of the connected device and click the OK Button. This completes changing the mode. 5. Click the OK Button to return to the Main Window. Note The mode cannot be changed for a DST1-series Controller.
  • Page 308: 9-14 Locking/Unlocking Devices

    Note This dialog box will not be displayed if the device is locked. 2. Confirm the report information of the device for which the configuration will be locked, and then click the Close Button. One of the following dialog boxes will be displayed.
  • Page 309 Note When locking the configuration, confirm that the network number is correct. Note Be sure to check that the network number is correct. If configuration is not performed with the correct network number, Safety I/O connections may not be established. For details on network numbers, refer to 9-5-2 Specifying the Network Number.
  • Page 310: 9-15 Change Passwords

    1,2,3... 1. Click the Change Password Icon in the Main Window. The following dialog box will be displayed. 2. Enter the present device password and the new device password, and then click the OK Button. This completes changing the password.
  • Page 311: Appendix

    Refer to 3-3 Connecting to the Network to connect to the network via the USB port on the NE1A-series Con- troller, a DeviceNet Interface Card installed in the computer, or an EtherNet/IP port on an NE1A-series Control- ler that supports EtherNet/IP.
  • Page 312 The window corresponding to the specified connection interface will be displayed. Refer to Specifying the CS/CJ Serial Port -> DRM Unit I/F as the Connection Interface on page 279 or Spec- ifying the Ethernet -> CS/CJ ETN-DRM Unit I/F as the Connection Interface on page 283 for the procedure.
  • Page 313 Specifying the CS/CJ Serial Port -> DRM Unit I/F as the Connection Interface (Continued from step 3 on the previous page.) 1. When CS/CJ Serial Port -> DRM Unit I/F is selected as the connection interface, the Setup Interface Dialog Box will be displayed. An example is shown below.
  • Page 314 For information on the FINS node address, refer to the (W380). Host link is selected, it may take several minutes to download from the network. It is recom- When mended to select the Peripheral Bus (ToolBus) for the serial connection.
  • Page 315 (2) Select the Message Timer Tab in the Edit Device Parameters Window and set the timer value to 10000 (ms) (i.e., 10 s) for the device to be downloaded from. (It is not necessary to change the node numbers of devices for which data is not to be downloaded.)
  • Page 316 Appendix A (3) The data with changed settings will be downloaded to the CJ/CS-series CPU Unit. 2. Stopping Remote I/O Communications of the CS/CJ-series CPU Unit (1) Right-click the CS/CJ-series CPU Unit and select Monitor from the displayed menu. (2) Click the Stop Remote I/O Communication Option on the Status Tab Page.
  • Page 317 When multiple PLCs with both Ethernet Units and DeviceNet Units are connected to the Ethernet network, the specified DeviceNet network can be connected to online by switching the connection destination. The destina- tion DeviceNet network is registered by specifying the IP address of the Ethernet Unit and the unit number of the DeviceNet Unit.
  • Page 318 Appendix A Registering Destination DeviceNet Networks It is necessary to register the destination DeviceNet network in advance for a connection via Ethernet. A maxi- mum of 20 DeviceNet networks can be registered. Use the following procedure to register the destination DeviceNet network.
  • Page 319 Appendix A 3. Click the Set Button. The Destination Registration Window will be displayed. An example is shown below. Destination Registration Window Registration Set the registered name of the destination DeviceNet network. Up to 20 names can be registered. A Name registration name can use up to 25 characters.
  • Page 320 Setting the CPU Bus Unit Number in the DeviceNet Unit Field of the Remote Information Area Set the unit number (0 to F) of the DeviceNet Unit as a CPU Bus Unit to which the destination DeviceNet net- work is connected.
  • Page 321 Click the OK Button in the confirmation dialog box. The connection to the DeviceNet network will be made. When the connection is successful, the status indicator on the status bar will turn blue and “On-line” will be displayed. Note For information on FINS network addresses and FINS node addresses, refer to the CS/CJ Series DeviceNet Unit Operation Manual (W380) and the SYSMAC CS/CJ Series Ethernet Unit Operation Manual (W420, W421 and W343).
  • Page 322 3. The Edit Device Parameters Window for the master will be displayed. Note (1) If the I/O size of the device displayed in the Network Configuration Pane and the I/O data size of the device registered in the Scan List do not match, the following warning dialog box will be displayed and the I/O size set in the Scan List will be given priority.
  • Page 323 Appendix A Modify the registered slave in the Scan List. (3) To operate the master function, select a device, select Device - Properties, and then select the En- able Master Function Option in the Property Dialog Box of the CS1W-DRM21(-V1)/CJ1W-DRM21.
  • Page 324 Device List above. Auto allocation as is registered Select this option to allocate unused words in the registration order when registering slaves to a master in the Edit Device Parameters Window. Register/Unregister Button Click this button to cancel and re-allocate the I/O allocations (allocation of unused words with no unallocated words) to the selected slave.
  • Page 325 Appendix A Slave Registration and Automatic I/O Area Allocation If a slave is registered when the master function is enabled, words are automatically allocated to it in the mem- ory block set for I/O allocation. Allocation is performed forward from the beginning of Memory Block 1 in the order of registration for both the input and output areas.
  • Page 326 (2) The number of displayed words is the number of words of a block displayed in the Network Config- urator. This value is not downloaded to the Unit. If the allocated area in a block is 100 words or less when uploaded, the number of displayed words will be set to 100 and displayed.
  • Page 327 Appendix A 5. Setting Remote I/O Allocations The Scan List Wizard-Set how to allocate I/O data to PLC Memory Block Window, which specifies the I/O data allocation method for devices, will be displayed. An example is shown below. Specify the allocation method and click the Next Button.
  • Page 328 If there are 1-byte I/O slaves, allocation is in the order of of allocated words is minimized low byte (lower 7 bits) to high byte (upper 7 bits) to create (two devices may be allocated to as few unused areas as possible.
  • Page 329 6. Slave Registration and Deletion The Scan List Wizard-Register Device Window will be displayed. An example is shown below. Specify the slave devices to register to the master device and click the Next Button. Devices in the network will be displayed in the Registered Device List as already registered. If there is a device that you do not want registered, click the Button to unregister it.
  • Page 330 8. Downloading Parameters to a Master Device The following dialog box will be displayed when the Network Configurator is online. If you click the Yes Button to download to a master device, the remote I/O communications will start with the new settings.
  • Page 331 The product name of the device to which memory is allocated in each area and the first CPU Unit word allo- cated are displayed in the Allocation State List for the blocks. The first bit that is allocated is given in the Ch column. The word address is given first followed by the first bit. Example: “3300: Bit 00”...
  • Page 332 (1) The number of words of a block displayed on the Network Configurator is set for Words. This value is not downloaded to the master. (2) If the number of allocated words in 1 block is 100 or less, the number of words will be displayed as 100 words when uploading.
  • Page 333 2. Click the Edit Button. 3. The Edit I/O Allocation Dialog Box will be displayed. Examples are shown below. Specify Block 1 or 2, the allocated word, start byte (low byte: Low, high byte: High), and the number of allo- cated bytes (occupied).
  • Page 334 • Registered Device List Contents In the Registered Device List at the top of the window, the node address is displayed in the # column, the slave product name (i.e., model) in the Product Name column, the number of allocated bytes in the Size column, and, when memory is already allocated, the start byte (i.e., word address and start bit address) in...
  • Page 335 Information Button on the I/O Allocation Tab Page Information, such as I/O comments of registered slave devices, can be accessed on the I/O Allocation Tab Page. (To set I/O comments for the I/O data of the slave devices, select Edit I/O Comment from the Device Menu.) Use the following procedure to display the slave information.
  • Page 336 Appendix A It is possible to display device information and to perform checks for the slave devices. Use the following proce- dure. 1. Select a slave device from the Registered Device List. 2. Click the Advanced Setup Button. 3. The following window will be displayed.
  • Page 337 Allocate memory again. IMPORTANT • COS and Cyclic cannot be set at the same time. • If both a poll and COS connection or a both poll and cyclic connection are used, the output settings for both connections must be the same.
  • Page 338 Communications Cycle Time Tab Page. Click the Communications Cycle Time Tab to display the following window. The communications cycle time is set between 1 and 500 ms. Click the Default Setup Button or specify 0 ms to enable automatic setting.
  • Page 339 The following dialog box will be displayed. 2. Enter a value and click the OK Button. Note To set the same value for all the devices, select the node address value you want to set and click the Copy to All Device Button.
  • Page 340 Up to 2 connections can be set. IMPORTANT • COS and Cyclic cannot be set at the same time. • If both a poll and COS connection or both a poll and cyclic connection are used, the output settings for both connections must be the same.
  • Page 341 Dialog Box. Right-click the icon to display the pop-up menu, and select Parameter - Edit. 2. Click the Tag Sets Tab at the top of the Edit Device Parameters Dialog Box. There are two kinds of tag sets: input (consume) and output (produce).
  • Page 342 3. Click the Edit Tags Button. The Edit Tags Dialog Box will be displayed. Register the input (consume) tags and output (produce) tags separately. 4. Click the In - Consume Tab, and click the New Button. The Edit Tag Dialog Box will be displayed.
  • Page 343 Close Button. 8. Click the Out - Produce Tab, and click the New Button. The Edit Tag Dialog Box will be displayed, like the dialog box for input tags, except for the Over Load setting. The Over Load setting determines whether out- puts are cleared or continue their previous status when outputs are turned OFF with the PLC’s output inhibit...
  • Page 344 If the Yes Button is clicked, more tags can be registered at the end of the tag set. In this case, only the tags will be registered and they will not be registered in tag sets.
  • Page 345 Bit 7 Bit 0 Bit 7 Bit 0 In this case, set the tags for the CS/CJ-series EtherNet/IP Unit for two bytes, so that they can be used in the PLC program. NE1A-series Controller Supporting EtherNet/IP CS/CJ-series EtherNet/IP Unit Bit 7...
  • Page 346 Open the Edit Device Parameters Dialog Box, select the tag set containing the tag that you want to delete, and click the Delete Button. (If there are other tags registered in that tag set, it is possible to delete just one tag by selecting the tag that you want to delete, and clicking the Button.
  • Page 347 The Tag List on the left side of the dialog box shows the tags that are already registered, and the Candidate Tag List on the right side of the dialog box shows the other tags that have not been registered yet. To add a tag, select it in the Candidate Tag List and click the Button.
  • Page 348 Appendix A 3. In the Unregister Device List, select the target device that requires connection settings by clicking the device so its color changes to gray, and click the Button. The selected target device will be displayed in the Register Device List, as shown in the following diagram.
  • Page 349 Error Flag, Registered Target Node Flag, and Normal Target Node Flag. By default, the target ID is auto- matically set to the rightmost 8 bits of the IP address. In the example above, the target device’s IP address is 192.168.250.2, so the device number is #002. If a target node ID is duplicated and you want to change the device number, click the Change Target Node ID Button and change the target ID.
  • Page 350 Sets the time until a connection timeout is detected. The time out value is set as a multiple of the packet interval (RPI) and can be set to a 4, 8, 16, 32, 64, 128, 256, or 512 multiple. The default set- ting is 4×...
  • Page 351 Sets the time until a connection timeout is detected. The time out value is set as a multiple of the packet interval (RPI) and can be set to a 4, 8, 16, 32, 64, 128, 256, or 512 multiple. The default set- ting is 4×...
  • Page 352 Appendix A Setting Example 2. After completing the settings, click the OK Button. Confirming the Connections Settings 1. An overview of the connections set in the Register Device List is displayed in the Connections Tab Page.
  • Page 353 4. If the tag set’s size is changed in either the originator or target after the connection was set, the size will not match the other node and a parameter data mismatch will occur. In this case, if the connection settings have been changed, be sure to check the connections.
  • Page 354 1. Select EDS File - Install. The following window will be displayed. 2. Select the EDS file to install. The device information will be displayed in the lower part of the window. 3. Click the Open Button. The file will be added to the Hardware List Window as new hardware.
  • Page 355 Refer to the relevant device manual and set an I/O connection and an I/O size that the device supports. 5. Click the OK Button. The file will be added to the Hardware List Window as a new device in the same way as in the EDS file in- stallation.
  • Page 356 1. Select the hardware (i.e., device) in the Hardware List Window. 2. Select EDS File - Save. A window for specifying the folder and file name for saving the EDS file will be displayed. An example is shown below. 3. Specify a folder and file name and click the Save Button.
  • Page 357 4. Click the Cancel Button to exit the search. Note (1) The search will be made for devices below the present cursor position in the Hardware List Window. (2) To search all the devices, select Hardware in the Hardware List Window and then perform the search.
  • Page 358 Appendix A Using General-purpose Tools to Set Devices This section describes how to set parameters that are not written in an EDS file and how to set node addresses and baud rates through the network. A-5-1 Setting Device Parameters by Specifying Class and Instance Tool - General Parameter The following items can be set to enable setting device parameters that are not written in an EDS file.
  • Page 359 5. Specify the class and instance of the parameters for which the settings are to be read or written. 6. Enter the data based on the specified service type. 7. Enter all the items and click the Send Button. The response from the device will be displayed in the Result Field.
  • Page 360 The following window will be displayed. 4. Specify the present node address of the target device in the Target Node Address Field. 5. To change the node address, specify a new node address in the New Node Address Field and click the Change Button.
  • Page 361 1. In the EtherNet/IP network, have only the target device and the Network Configurator operating. For the de- fault IP address for a device that is to be used, refer to the operation manual for that device. 2. Connect the Network Configurator online.
  • Page 362 Appendix A Using the Password Recovery Tool If the password set for a device is lost, use the Password Recovery Tool to reset the password and to return to the state without any password setting (default settings). Use the following procedure to reset a device password.
  • Page 363 Appendix A 4. Set the node address range to search for and click the OK Button. 5. The devices in the network will be displayed. Select a device for which to reset the password and click the OK Button. 6. The necessary information for resetting the password will be displayed. The information is required when inquiring from the Support Center.
  • Page 364 Appendix A 7. Click the Next Button to display the Reset Key Enter Window. Enter the Reset Key obtained from the Sup- port Center and click the Reset Button. 8. If the password is successfully reset, the following dialog box will be displayed. The device will be returned to the state without any password setting (default setting).
  • Page 365 Appendix A Function Restrictions for the NE1A-SCPU0@-EIP The following operations cannot be performed in the EtherNet/IP Network Window with the NE1A-SCPU01- EIP or NE1A-SCPU02-EIP. Menu Submenu/Command Network Download Upload Device Parameter Download Upload Verify Lock/Unlock Change password Reset Change mode Perform these operations in the DeviceNet Network Window.
  • Page 367: Glossary

    A logical communications path used to communicate between devices. DeviceNet Safety A safety network that adds a safety protocol to DeviceNet to comply with up to SIL3 according to IEC61508, up to Safety Category 4 according to EN954-1. discrepancy time The time period from a change in one of two inputs until the other input changes.
  • Page 368 A CPU Unit with one of the following model numbers: NE1A-SCPU01-EIP or ing EtherNet/IP) NE1A-SCPU02-EIP Standard CPU Unit A CPU Unit used for standard control, such as CPU Units in OMRON’s CS or CJ Series. This term is used to differentiate from Safety CPU Units.
  • Page 369: Index

    EPI DeviceNet Interface Card allocation by word DeviceNet Safety Communications allocation minimizing the number of allocated words...
  • Page 370 Get from the actual network Button network bandwidth network configuration file hardware list Network Configuration Pane Network Configurator network numbers node address...
  • Page 371 Index setting slave input data in idle state setting test outputs reaction time setting the node addresses and baud rates via the network reading the network configuration file Register Device List setting the operating mode registering devices setting unit functions...
  • Page 373: Revision History

    Revision History The manual revision is indicated at the end of the Cat. No. printed at the lower left of back cover of the manual. Cat. No. Z905-E1-07 Revision code The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
  • Page 376 Tel: (1) 510-608-3400/Fax: (1) 510-744-1442 Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 Japan OMRON ASIA PACIFIC PTE. LTD. Tel: (81) 75-344-7093/Fax: (81) 75-344-8197 No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711 Regional Headquarters OMRON (CHINA) CO., LTD.

This manual is also suitable for:

Devicenet safety

Table of Contents