Reset the device by setting the reset type to Return to the out-of-box configuration, and then emulate
cycling power.
Refer to 3-1-2 Changing an Established Safety Network (page 56).
11. Downloading Device Parameters
Download the parameters to all the devices.
Refer to 2-7-3 Downloading Device Parameters (page 41).
12. Confirming the Downloaded Device Parameters and Safety Signatures
Verify the parameters for all the devices and check if the device parameters and program that the user
input have been correctly downloaded and saved in the devices.
Refer to 2-8 Parameter Verification (page 45).
13. Saving the Network Configuration File
Save the network configuration file in which parameter verification of all the devices has been com-
pleted.
Refer to 2-5-2 Saving the Network Configuration File (page 38).
14. Exiting the Network Configurator
Exit the Network Configurator.
IMPORTANT: • After downloading the device parameters, verify the parameters to confirm that the param-
User Testing
15. User Testing
The user himself must verify device parameters and operation to confirm that safety system require-
ment specifications are met.
16. Starting the Network Configurator and Connecting to the Network
Start the Network Configurator and connect it to the network via the USB port on the NE1A-SCPU01 or
a DeviceNet Interface Card.
Refer to 2-3 Connecting to the Network (page 32).
17. Reading the Network Configuration File
Read the saved network configuration file with parameters that are already verified.
Refer to 2-5-3 Reading a Network Configuration File (page 39).
18. Configuration Lock
Lock the configuration of all the devices to indicate that they have been verified as well as to prevent
parameters from being mistakenly rewritten.
Refer to 2-9-1 Locking the Device Configuration (page 48).
19. Saving the Network Configuration File
Save the network configuration file of the virtual network in which the configuration is locked.
Refer to 2-5-2 Saving the Network Configuration File (page 38).
20. Exiting the Network Configurator
Exit the Network Configurator.
Safety functions may be impaired and serious injury may occasionally occur. Before operat-
ing the system, perform user testing to confirm that the configuration data of all the devices
is correct and that they are operating correctly.
IMPORTANT: • After configuring all the devices, user testing must be performed to check if the configura-
Running the System
21. Running the System
Run the system.
3-1 Applications
eters and the safety signature saved in the devices are correct.
• When selecting Open Only in the Open Type setting for the safety connection, check that
the Safety Master and Safety Slave are correctly configured.
tion data and device operation of each device are correct. User testing is performed to ver-
ify the safety signature for each device.
• The configuration must be locked after the user testing has completed.
! WARNING
55