The user must check whether all the displayed parameters match the input values. If the device is the NE1A-
SCPU01, the Logic Program will also be displayed as in the following window. Check whether the Logic Pro-
gram matches.
Note: The displayed parameters and logic can also be printed. To print, click the Print Button at the upper
left of the window.
After completing the verification, click the Close Button in the upper left to close the window.
The following window will be displayed.
If the parameters match, click the Yes Button.
After the verification has been completed, the safety symbol attached to the device icon in
the virtual network will turn green, which indicates that verification is done.
IMPORTANT:
Note: – After verifying the parameters of all the devices, make sure to save the network configuration file.
– The Verified configuration parameter symbol ensures that the device parameters in the network
configuration file are correct. This information is saved in the network configuration file, but not in
the device itself. Therefore, the Verified configuration parameter symbol will not be attached even
though the network configuration is obtained by network upload from a device that has been already
verified.
– If you edit parameters that have been verified, the Verified configuration parameter symbol will dis-
appear. The device parameters must be verified again.
46
After downloading the configuration data, verify the parameters and
check whether the parameters saved in the device and the safety signa-
ture are correct.