Switch Settings

2-2
Switch Settings
Terminator Setting Switch
Output Hold Setting Pin
Word Setting
Switch
4
3 (x 2
)
3
2 (x 2
)
2
1 (x 2
)
Word allocation
Output
of Master
Input
There is a terminator setting switch and DIP switch under the terminal board.
To disconnect the terminal board, refer to the CQM1H Operation Manual
(W363) or the CQM1 Operation Manual (W226). Use a small flat-blade screw-
driver for setting the terminator setting switch and DIP switch.
The terminator setting switch of the CQM1-LK501 I/O Link Unit mounted to
the CQM1H/CQM1 located at the end of the SYSMAC BUS system must be
set to ON.
Master
CQM1H/CQM1 (1)
If this pin is set to OFF, when an error has occurred, the CQM1H/CQM1's out-
put word (i.e., the Master's write word) will hold the value just before the error
has occurred. If this pin is set to ON, the value will be cleared.
0
0
0
0
0
1
0
1
0
Words
Words
Words
+0, 1
+4, 5
+8, 9
Words
Words
Words
+2, 3
+6, 7
+10, 11
SYSMAC BUS system
Other Slave
Terminator setting switch
DIP switch (with output hold setting pin)
DIP switch
Output hold setting pin:
Word setting pins
(see table below)
Setting
0
1
1
0
1
0
Words
Words
+12, 13
+16, 17
Words
Words
+14, 15
+18, 19
Section 2-2
CQM1H/CQM1 (2)
Set the terminator setting
switch of the CQM1-LK501 I/O
Link Unit mounted to this
CQM1H/CQM1 to ON.
1
1
1
0
1
1
1
0
1
Words
Words
Words
+20, 21
+24, 25
+28, 29
Words
Words
Words
+22, 23
+26, 27
+30, 31
71