Omron CQM1 Operation Manual page 269

Sysmac cqm1h/cqm1 series dedicated i/o units
Hide thumbs Also See for CQM1:
Table of Contents

Advertisement

Nomenclature
Temperature Ranges
Units for Thermocouples
Code
Input
No.
type
0
K
FF38 to FFFF to 0514
(–200 to –1 to 1300)
1
K
0000 to 1388
(0.0 to 500.0)
2
J
FF9C to FFFF to 0352
(–100 to –1 to 850)
3
J
0000 to 0FA0
(0.0 to 400.0)
4
T
F830 to FFFF to 0FA0
(–200.0 to –0.1 to 400.0)
5
L
FF9C to FFFF to 0352
(–100 to –1 to 850)
6
L
0000 to 0FA0
(0.0 to 400.0)
7
R
0000 to 06A4
(0 to 1700)
8
S
0000 to 06A4
(0 to 1700)
9
B (See
0064 to 0708
note 3.)
(100 to 1800)
Units for Platinum
Resistance Thermometers
Code
Input
No.
type
0
Pt100
F830 to FFFF to 1964
(–200.0 to –0.1 to
650.0)
1
JPt100
F830 to FFFF to 1964
(–200.0 to –0.1 to
650.0)
2
Pt100
F830 to FFFF to 61A8
(–20.00 to –0.01 to
250.00)
3
JPt100
F830 to FFFF to 61A8
(–20.00 to –0.01 to
250.00)
4 to 9
---
Do not set. (See note 4.)
250
The setting ranges are shown in the following table. Indication ranges are the
setting range 20 C/ F. (See note 1.)
C
Binary
(4-digit Hex)
F200 to 1300
(–200 to 1300)
0000 to 5000
(0.0 to 500.0)
F100 to 0850
(–100 to 850)
0000 to 4000
(0.0 to 400.0)
F999 to 4000 (See
note 2.)
(–99.9 to 400.0)
F100 to 0850
(–100 to 850)
0000 to 4000
(0.0 to 400.0)
0000 to 1700
(0 to 1700)
0000 to 1700
(0 to 1700)
0100 to 1800
(100 to 1800)
The setting ranges are shown in the following table. Indication ranges are the
setting range 20 C/ F. (See note 1.)
C
Binary
(4-digit Hex)
F999 to 6500 (See note
2.)
(–99.9 to 650.0)
F999 to 6500 (See note
2.)
(–99.9 to 650.0)
F999 to 9999 (See note
2.)
(–9.99 to 99.99)
F999 to 9999 (See note
2.)
(–9.99 to 99.99)
Note
1. For binary indications, a sensor error (E400) will occur if the specified
range is exceeded. In Auto Mode, the output for the corresponding loop will
turn OFF if this error occurs.
2. For BCD indications, the indicated values will be clamped to the upper or
lower limit between the upper or lower limit of the setting range and the val-
ues that will cause a sensor error (E400),
0.1 C/ F Indications: Lower limit = –99.9, Upper limit = 999.9
0.01 C Indications: Lower limit = –9.99, Upper limit = 99.99
3. The lower limit of indications for B thermocouples is 0 C/ F.
BCD
Binary
(4-digit Hex)
FED4 to FFFF to 08FC
(–300 to –1 to 2300)
0000 to 2328
(0.0 to 900.0)
FF9C to FFFF to 05DC
(–100 to –1 to 1500)
0000 to 1D4C
(0.0 to 750.0)
F448 to FFFF to 1B53
(–300.0 to –0.1 to 700.0)
FF9C to FFFF to 05DC
(–100 to –1 to 1500)
0000 to 1D4C
(0.0 to 750.0)
0000 to 0BB8
(0 to 3000)
0000 to 0BB8
(0 to 3000)
012C to 0C80
(300 to 3200)
BCD
Binary
(4-digit Hex)
F448 to FFFF to 2EE0
(–300.0 to –1 to 1200.0)
F448 to FFFF to 2EE0
(–300.0 to –1 to 1200.0)
Do not set. (See note 4.)
Section 2-3
F
BCD
F300 to 2300
(–300 to 2300)
0000 to 9000
(0.0 to 900.0)
F100 to 1500
(–100 to 1500)
0000 to 7500
(0.0 to 750.0)
F999 to 7000 (See
note 2.)
(–99.9 to 700.0)
F100 to 1500
(–100 to 1500)
0000 to 7500
(0.0 to 750.0)
0000 to 3000
(0 to 3000)
0000 to 3000
(0 to 3000)
0300 to 3200
(300 to 3200)
F
BCD
F999 to 9999 (See note
2.)
(–99.9 to 999.9)
F999 to 9999 (See note
2.)
(–99.9 to 999.9)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cqm1h - 08-2005

Table of Contents