7-3-11 Hysteresis Set; 7-3-12 Hysteresis Read - Omron CQM1 Operation Manual

Sysmac cqm1h/cqm1 series dedicated i/o units
Hide thumbs Also See for CQM1:
Table of Contents

Advertisement

Commands and Responses

7-3-11 Hysteresis Set

Command
Command Code
Parameter
Response

7-3-12 Hysteresis Read

Command
Command Code
Parameter
Response
226
If the output word is set to the wrong command code, the following error
codes will be set to the input word.
E000: This error code will be set to the input word if a nonexisting command
code is used.
This command is used to set the hysteresis.
If the input type data is changed, the hysteresis will be reset to its factory-set
value.
The set data will be stored in the nonvolatile memory and will not be lost after
the Unit is turned OFF.
If the correct command code or parameter is set to the output word, the same
command code or parameter will be set to the input word.
If the wrong command code or parameter is set to the output word, one of the
following error codes will be set to the input word.
E000: This error code will be set to the input word if a nonexisting command
code is used.
E001: This error code will be set to the input word if the parameter is not
within the range covered by the Unit.
This command is used to read the hysteresis.
Parameters are not used with this command.
If the correct command code or parameter is set to the output word, the same
command code or parameter will be set to the input word.
If the wrong command code or parameter is set to the output word, one of the
following error codes will be set to the input word.
E000: This error code will be set to the input word if a nonexisting command
code is used.
Section 7-3
Range: 0001 to 0999
Factory-set value: 0001
Range: 0001 to 0999
Default value: 0001