Switch Settings - Omron CQM1 Operation Manual

Sysmac cqm1h/cqm1 series dedicated i/o units
Hide thumbs Also See for CQM1:
Table of Contents

Advertisement

Switch Settings

2-2
Switch Settings
!Caution Turn off the CQM1H/CQM1 power before setting the pins.
Remove the terminal block to expose the DIP switch underneath. Refer to the
CQM1H Operation Manual (W363) or the CQM1 Operation Manual (W226)
for the method of removing the terminal block.
Use a thin-tipped object, such as a small screwdriver, to set the pins.
CQM1-B7A21/CQM1-B7A12
Pin no.
4
Transmission delay
time
3
Transmission error
processing
2
Input mode
1
ERR indicator
Note On delivery from the factory, pin 1 is set ON and all others OFF.
CQM1-B7A03/CQM1-B7A02
Pin no.
4
Transmission delay
time
3
Not used (set OFF)
2
Not used (set OFF)
1
Not used (set OFF)
Note On delivery from the factory, all pins set OFF.
CQM1-B7A13
Pin no.
6
Transmission delay
time
5
Transmission error
processing
4
Input mode
3
ERR1 indicator
2
ERR2 indicator
1
Not used (set OFF)
Note On delivery from the factory, pins 2 and 3 are set ON and all others OFF.
Setting
OFF
STANDARD (19.2 ms)
HOLD
16IN
Not lit
Setting
OFF
STANDARD (19.2 ms)
–––
–––
–––
Setting
OFF
STANDARD (19.2 ms)
HOLD
16IN
Not lit
Not lit
–––
Section 2-2
DIP switch
ON
RAPID (3 ms)
LOAD OFF
15IN+ERR
Lit
ON
RAPID (3 ms)
–––
–––
–––
ON
RAPID (3 ms)
LOAD OFF
15IN+ERR
Lit
Lit
–––
17