Omron CQM1 Operation Manual page 106

Sysmac cqm1h/cqm1 series dedicated i/o units
Hide thumbs Also See for CQM1:
Table of Contents

Advertisement

Nomenclature
DIP Switch Function
Input Range Settings
(Pins 1 to 8)
Input 1
Pin 1: ON
Pin 3: ON
Pin 2: ON
Pin 4: ON
Pin 1: OFF
Pin 3: OFF
Pin 2: ON
Pin 4: ON
Pin 1: ON
Pin 3: ON
Pin 2: OFF
Pin 4: OFF
Pin 1: OFF
Pin 3: OFF
Pin 2: OFF
Pin 4: OFF
Word Settings (Pin 9)
Average Processing
Function (Pin 10)
Caution
The DIP switch is used to decide the operating method of the Analog Input
Unit.
ON
OFF
1
2
3 4 5 6 7 8
Factory setting
The following tables provides DIP switch settings for Analog Input Unit opera-
tion.
Input range settings can be made for all inputs.
Input setting
Input 2
Input 2
Pin 5: ON
Pin 6: ON
Pin 5: OFF
Pin 6: ON
Pin 5: ON
Pin 6: OFF
Pin 5: OFF
Pin 6: OFF
The Analog Input Unit will occupy four words (64 points) when pin 9 is set to
ON. The Analog Input Unit will occupy two words (32 points) when pin 9 is set
to OFF.
Set pin 10 to ON to use the average processing function of the Analog Input
Unit. Set pin 10 to OFF if the average processing function is not used.
All pins must be set before mounting the Analog Input Unit to the CQM1H/
CQM1.
An error will result if pins 1 to 8 are all set to OFF (i.e., if all input conversion is
prohibited).
When pin 9 is set to OFF so that the Analog Input Unit will occupy two words,
be sure to set pins 5 to 8 to OFF.
Do not touch any internal components other than the DIP switch.
The time required for the Analog Input Unit to convert data will not be short-
ened even if some inputs are prohibited or if pin 9 is set to OFF so that the
Analog Input Unit will occupy two words.
9 10
Input 4
Pin 7: ON
–10 to 10 V
Pin 8: ON
Pin 7: OFF
0 to 10 V
Pin 8: ON
Pin 7: ON
4 to 20 mA at 1 to 5 V
Pin 8: OFF
Pin 7: OFF
Conversion is prohibited
Pin 8: OFF
Section 2-1
Input range
87